LAD6K
LADN
LADT
12
LAD4RC
LAD4V
LAD4T
LAD4BB
LAD4T
DL
LAD4DDL
1
2
LADN
LADT
LADR
, , LC, AC/DC
A2 -
A1 +
, , AC/DC
13/NO
14
1/L1
3/L2
5/L3
22 21/NC
03/2017 1/2
W9 1378323 0211 A11
LC1D
LC1D09/
D12
LC1DT20/
DT25/
D098/D128
LC1D18 LC1D25/
D32/D38
LC1DT32/
DT40/
D188/D258
LC1D,
LA
8 mm
5/16"
12 mm
6/13"
8 mm
5/16"
10 mm
3/8"
12 mm
6/13"
8 mm
5/16"
[mm²] 1…4 1…4 1.5…6 2.5…10 2.5…10 1…4
[mm²] 1…4 1…4 1.5…6 2.5…10 2.5…10 1…4
[mm²] 1…4 1…4 1…6 1…10 2.5…10 1…4
[mm²] 1…2.5 1…2.5 1…4 1.5…6 2.5…10 1…2.5
[mm²] 1…4 1…4 1.5…6 1.5…10 2.5…16 1…4
[mm²] 1…4 1…4 1.5…6 2.5…10 2.5…16 1…4
AWG 10-18
CU 75°C
10-18
CU 75°C
8-18
CU 75°C
6-14
CU 75°C
8-12
CU 75°C
10-18
CU 75°C
6 mm 6 mm 6 mm 6 mm 6 mm 6 mm
C1.7 N.m
15 lb-in
1.7 N.m
15 lb-in
1.7 N.m
15 lb-in
2.5 N.m
22 lb-in
1.8 N.m
16 lb-in
1.7 N.m
15 lb-in
WARNING /
警告
RISK OF FIRE OR ELECTRIC SHOCK (FOR CONTACTOR WITH UL HI-FAULT
SHORT CIRCUIT CURRENT RATINGS ONLY)
The opening of the branch-circuit protective device may be an indication that a fault
current has been interrupted.
the controller should be examined and replaced if damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
可能有火灾或者触电的危险(仅限UL高故障短路电流额定值的接触器)
支路保护设备断开,表明故障电流已被中断。
为降低火灾或触电风险,应检查带电部件和 其他控制元件,如有损坏,需及时更换。
不遵循上述规定将可能导致人员伤亡或设备损坏。
3P AC TeSys D contactors are grade 3 (LC1D09 -> LC1D18) and grade 2
(LC1D25 -> LC1D38) according to GB 21518.Maximum power consumption
lower than 9.5 VA.
根据GB 21518标准,三极 TeSys D 系列交流接触器能效等级为3级
(LC1D09 -> LC1D18)和2级(LC1D25 -> LC1D38),产品最大吸持功率低于9.5VA。
www.schneider-electric.com/contact
W9 1378323 0211 A11
03/2017
Schneider Electric Industries SAS
35, rue Joseph Monier CS 30323
F - 92506 Rueil Malmaison Cedex
AC/DC: - use of this product in EMC environment B may require mitigation
measures to avoid unwanted disturbance.
- full open AC at 10%Us