T5000 LCD Digital Fan Coil Thermostat-Installation Instructions
T5000 液晶数字式风机盘管温控器-安装说明
42mm
41mm
15mm
60mm
88mm
8mm
52.5mm
88mm
8mm
Application
T5000 series thermostats are designed to on/off control the fans and valves in
air conditioner applications via comparison of the room temperature and setting
temperature as reaching the aim of comfort and saving energy.
T5000 are microprocessor based thermostat with LCD display. It shows the following
items: working states (cool/heat/ventilation), fan speed, room temperature, settin
g
temperature. T5000 features with one on/off button (
)one mode button (
M
)one
fan speed selection button (
), two adjustment buttons (
).
2
:
T5200-TC/TB/TF-9JS0T5200-TB-9JR0系列温控器尺寸 (mm)
Figure
2
:
T5200-TC/TB/TF-9JS0T5200-TB-9JR0 Series Thermostat Dimensions in (mm)
3
:
T5200-TF-9JR0系列温控器尺寸 (mm)
Figure
3
:
T5200-TF-9JR0 Series Thermostat Dimensions in (mm)
安装
T5000温控器安装在用户容易观看屏幕和调节温度设定点的地方。并使温控器位
于能代表房间总体环境温度的地方。避免将温控器安装于冷热源附近,如通风
口、加热器、室外或阳光照射到的地方。
安装
T5000系列温控器设计为标准75x75x35mm装接线盒安装。 (
4
) 按照指示
打开后盖底座,把它安装在墙上并接线。
注意
:
所有T5000系列温控器型号,需要两枚M4x25安装螺钉 (不包含)
Installation
Install the T5000 where the occupant can read the display and adjust the setpoint
easily. Situate the thermostat where the temperature is representative of the general
room conditions. Avoid installing the T5000 near cold or warm air drafts, radiant heat,
on an outside wall, or in direct sunlight.
Mounting
Mount the T5000 Series thermostat to a 75x75x35mm standard electrical wallbox. (See
Figure
4
)
Follow the instruction in Removing the Base and then proceed to the Wall Mounting
and the Wiring sections.
Note:
All T5000 Series models require two M4x25 mounting screw (not included).
应用
T5000系列风机盘管温控器,适用于中央空调风机盘管系统的室内温度控制,通
过室内温度和设定温度相比较,对空调系统末端的风机盘管及电动阀进行开启
和关闭控制,达到调节室内温度、舒适及节能的目的。
T5000采用微电脑控制技术,大屏幕液晶显示,液晶显示状态有:工作状态(制
冷、制热、通风)、风机风速、室内温度、设置温度等。按键有:电源开关 (
)
模式转换键(
M
)、风速选择键 (
) 及温度设置键(▲
)。
602B-B01A-NB Issue Date 04 2013
This document is subject to change without notice 本文档如有变化,恕不另行通知
1
:
T5000液晶数字式风机盘管温控器
Figure
1
:
T5000 LCD Digital Fan Coil Thermostat
1
4
2
2×1.5mm
2
OR
1×2.5 mm
2
3
M4X25
墙装盒安装
安装T5000系列温控器:
把外部接线从墙里拉出并通过打开的方形底座。
通过两个安装孔,把底座固定在安装盒上,如
2和图3
两枚M4x25螺钉。
根据应用产品的要求进行正确的接线。
Wallbox Mounting
To mount the T5000 Series Thermostat:
Pull the external field wiring from the wall through the rectangular opening in the base.
Fasten the base to the wallbox using the appropriate two holes, as shown in
Figure
2
and Figure
3
, and two M4 x 25 screws.
Proceed to the Wiring section for
the correct configuration for the application and units.
4
:
上图为T5200-TC/TB/TF-9JS0T5200-TB-9JR0安装图 (T5200-TF-9JR0安装方法一致)
Figure
4
:
Installation diagram of T5200-TC/TB/TF-9JS0 and T5200-TB-9JR0 (Same procedure for T5200-TF-9JR0)
T5000 LCD Digital Fan Coil Thermostat-Installation Instructions
T5000 液晶数字式风机盘管温控器-安装说明
602B-B01A-NB Issue Date 04 2013
2
Check-Out Procedure
After the installation, observe the complete operation cycles for cooling and heating
control. This is to make sure that all control devices are functioning correctly. If the
device is not working properly and the wiring is correct, the thermostat should be
replaced by contacting your nearest Johnson Controls
®
Representative.
Instructions
On/off:
press " " to turn on, press again to turn off, close the fan and valve.
Setting temperature:
Press either "
" or "" buttons to increase or decrease by
0.5.
Mode selection:
press "
M
" to change the working mode, " " cooling, " " heating,
"
" ventilating. no heat mode for T5200-TC-9JS0
Fan speed selection:
press "
" to choose the speed
(hi) (med) (low)
AUTO
(auto).
Under AUTO mode, the fan-speed will be changed automatically. Auto LOW-
speed when the difference between room temperature and set-point exceed 1,
Auto MED-speed when exceed 2, Auto HI-speed when exceed 3.
Valve Control:
under cool (heat) mode, the valve will be open while the difference
between room temperature and setpoint exceed 1; while the room temperature
reaches setpoint, the valve is closed with the fan still running.
检查步骤
温控器安装完毕,在离开之前要检查制冷和加热完整的操作循环。这样可以
保所有控制设备功能正常。如果接线正确,而设备又不能正常工作,请就近联
JohnsonControls
®
办事处来替换温控器。
使用说明
/
开机
阀。
设定温度
开机状态,按
”键降低置温度,按“”键升高设置
度,每按键一次设置温度变化0.5℃。
模式选择:
开机状态下,按“
M
”键进行工作模式切换。液晶显示“
”表示
制冷,显示
”表示制热,显示“ ”表示通风T5200-TC-9JS0制热
模式)。
风速选择
开机状态下,按“
”键选择风机风速 (高)、 (中)、
(低)、
AUTO
(自动)档。
在“自动”模式下,风速自动换档。即当室温与设置温度相差1时,自动
择低风速;当室温与设置温度相差2℃时,自动选择中风速;当室温与设置温
度相差3℃时,自动选择高风速。
控制
制热)设1
时,打开电动阀;当室温达到设置温度时,关闭电动阀,风机继续运行。
接线
根据指导,给适当型号的温控器接线。
注意:
T5000系列数字式风机盘管温控器接线时,使用接线螺帽完成和绝缘每
个接线端。
当接线完成后
:
通过底座方形孔,把连接线推入墙装盒里。
在底座咬合处把温控器钩住并轻轻推动温控器至安装底座上面。
固定松紧螺丝。
按设定调节键设定想要的参数。
根据
5
的典型应用,给指定接线端接线。
Wiring
Wire the unit according to the instructions for the appropriate model.
Note:
When wiring the T5000 Series Digital Fan Coil Thermostat, use wire nuts to
finish and isolate each connection.
When the wiring is completed:
Push the connected wiring through the rectangular hole in the base into the wallbox
space.
Hook the thermostat to the hinge at the bottom of the base and gently slide the
thermostat down into position on the mounting base.
Tighten the retention screw.
Proceed to the Setup and Adjustment section to establish the desired settings.
Wiring terminal designations and connections for typical applications appear in
Figure
5
.
5
:
T5200-TC-9JS0接线图
Figure
5
:
Wiring Diagram for T5200-TC-9JS0
T5200-TF-9JS0接线图
Wiring Diagram for T5200-TF-9JS0
T5200-TB-9JS0接线图
Wiring Diagram for T5200-TB-9JS0
T5200-TB-9JR0接线图
Wiring Diagram for T5200-TB-9JR0
T5200-TF-9JR0接线图
Wiring D
iagram for T5200-TF-9JR0
AC85 260V 50/60Hz
N L
T5200-TC-9JS0
N
Hi
Med
Low
L
Fan
Valve
VO
VC
AC85 260V 50/60Hz
N L
L
Low
Fan
S1
S2
N
Hi
Med
Val
Valve
T5200-TB-9JS0
T5200-TF-9JS0
N
Hi
Med
Low
L
1 Val1
2 Val2
Fan
Cool
Heat
AC85 260V 50/60Hz
N L
CN version
T5200 -TB -9J R0
Low
Valve
AC85260V 50/60Hz
N L
L
Val
Med
Hi
N
S2
S1
风机
AC85~260V 50/60Hz
AC85~260V 50/60Hz
AC85~260V 50/60Hz AC85~260V 50/60Hz
Med
Hi
Low
风机
Fan
L
2Val2
N
1Val1
AC85 260V 50/60HZ
N L
热水阀 Heat
冷水阀 Cool
T5200 -TF-9J R0
S2
S1
AC85~260V 50/60HZ
602B-B01A-NB Issue Date 04 2013
3
T5000 LCD Digital Fan Coil Thermostat-Installation Instructions
T5000 液晶数字式风机盘管温控器-安装说明
Time-On and Time-Off Operation
Hold down the "
M
" button for 3 seconds will enter the Timer On-Off setting. When the "
""
ON
" and ''
hh
'' of ''
hh mm
'' appear, press "" and "
" keys to set the time duration .
To confirm setting, press M/ button once, press other keys to cancel the setting.
Press "
M
" button again, "
""
OFF
" and ''
mm
'' of ''
hh mm
'' appear, press "" and
"
" keys to set the time duration. Set time duration to "
--
", to cancel the setting. After
one cycle for Time-on and Time-off the setting will be automatically canceled.
Lock function
Lock function: The thermostat will be locked automatically after 30 seconds under
the lock function. Hold down the fan key 5 seconds to unlock.
Unoccupied energy-saving mode
T5200-TB-9JS0
Unoccupied energy-saving mode (by entrance card): While entrance card is pulled
out, the temperature automatically set to 26, fan is on LO-speed if the thermostat
is in cool mode; the temperature set to 18, fan is on LO-speed if in heat mode.
Low Temperature protection setting
On power Off status and when room temperature is lower than 5, heat function
will be automatically switched on, "
" appears, the fan is set to HI-speed and
the valve (heat valve for T5200-TF-9JS0, T5200-TF-9JR0) is opened. When the
room temperature reaches 7, the setting will be automatically canceled.
On power Off status, press "
M
" and keep 5 seconds, display "
OF
" or "
On
",
press """
" to adjust the parameter. "
OF
" means cancelling low temperature
protection, "
On
" means the protection function is on. Factory setting is "
OF
".
Remote Temperature sensor
T5200-TB-9JR0, T5200-TF-9JR0)
When remote sensor is connected, the built-in sensor will be disable.
定时开关机设置
M
3
ON
”和
hh mm
”的
hh
”符同时闪烁此时按“▲”或“
”键调
整延时多少小时定时开机。再按“
M
”键,“
”、“
OFF
”和“
hh mm
”的
mm
”符同时烁,此时“▲或“
”键整延多少小时时关
机。取消定时开关机设置:只要把定时开关机的时间调整为
--
”即可;或
者当定时开关机功能运行过一次后,会自动取消定时开关机。
锁按键功能
锁按键功能:如果温控器开启了锁按键功能,在没有人使用的情况下30秒后
会自动把按键锁上。按风速按键5秒即可解锁。
门卡节能模式
T5200-TB-9JS0
可通过门卡进入节能模式。当门卡拔出后,如果温控器处于制冷模式时,
度自动设置26℃,风机低速运行;如果温控器处于制热模式时,温度自动
设置为 18℃,风机低速运行;
低温保护功能的设置
控器关机当室低于5时,自动制热
”符号,风机自动高速运行并开启电动阀T5200-TF-9JS0T5200-
TF-9JR0开启热水阀);当室内温度升高到7℃时,温控器自动关闭输出。
关机状态下,按住
M
”键并保5秒,显示
OF
”或
On
”,按“▲”
”键调整此项参数。“
OF
”表示取消低温保护功能,
On
”表示开启低
温保护功能。出厂默认值为“
OF
”。
外接温度传感器
T5200-TB-9JR0, T5200-TF-9JR0)
当温控器接上外置传感器时,内置NTC传感器自动失效。
编码
Code
T
5200
-TC-
9
JS
0
T
5200
-TB-
9
JS
0
T
5200
-TB-
9
JR
0
T
5200
-TF-
9
JS
0
T
5200
-TF-
9
JR
0
参数名
Parameter Name
默认值
Default
功能
Function
01
失电重启
Restart after Power
Failure
00
00:关闭;01:开启;
02:恢复掉电前状态
00off01on02keep last status
02
摄氏华氏转换
°F
/ C
F:华氏度(
°F
);C:摄氏度( ℃)
FFahrenheit Degree
°F
);
CCelsius Degree(℃)
03
设定温度上限
Upper limit of set temp
35.0
设定范围249.5
Setting Range 249.5
04
设定温度下限
Lower limit of set temp
5.0
设定范围047.5
Setting Range 047.5
05
键盘锁
Keypad lockout
00
00:无01所有02关键
03:锁定除了开关键之外其他键
00No lock01Lock all keys02Lock ON/
OFF Key 03Lock the keys except ON/OFF key
06
屏幕显示
Screen Display
00
00:显示室内温度;01:显示设定温度
00Display room temp01Display set temp
07
自动或手动模式转换
Auto or Manual Mode
Switch
01
00:手动模式转换;01:自动模式转换
00Manual Mode01Auto Mode
08
门卡状态
Key Card Status
01
00S1S2短接时代表插卡状态;断开时代表拔卡
状态。
01S1S2代表;短
卡状态。
00S1S2 Short Connection indicates key card is
inserted; Disconnection indicates key card is pulled
out.
01S1S2 Disconnection indicates key card is
inserted; Short Connection indicates key card is
pulled out.
09
门卡拔出后制冷温
Cooling Temp when key
card is pulled out
26.0
设定范围2232℃。
Setting Range 2232℃。
10
门卡拔出后制热温度
Heating Temp when key
card is pulled out
18.0
设定范围1021℃。
Setting Range 1021℃。
Functional Code Setting Table
功能编码表
进入参数表:关机状态下同时按住“ ”和“
”键5秒,显示“01”及参数值,之后按“M”键选择要查看的参数,用“
”和“
”修改。
Enable the setting table: hold down the "
" and "
" for 5 seconds, "01" and code appear, after which press 'M' button to select code, use "
" and "
" buttons to adjust the value.
* 失电后温控器重启动,用户可选择重启动,不启动或恢复上次状态
* Power failure memory supports "restart" or "recover to previous status" after power resume
T5000 LCD Digital Fan Coil Thermostat-Installation Instructions
T5000 液晶数字式风机盘管温控器-安装说明
602B-B01A-NB Issue Date 04 2013
4
IMPORTANT
Use this T5000 Series Line Voltage Fan Coil Thermostat only as an operating
control. Where failure of malfunction of the T5000 Series Thermostat could
lead to personal injury or property damage to the controlled equipment or other
property, additional precautions must be designed into the system. Incorporate
and maintain other devices such as supervisory or alarm systems or safety or
limit contro
ls intended to warn of, or protect against, failure or malfunction of
the T5000 Series Thermostat.
Do not install this thermostat in condensing, wet, or damp environments.
Moisture may cause damage to the thermostat.
Do not remove PCB from the enclosure cover. Removing the PCB from the
enclosure cover voids the product warranty.
Make all wiring connections in accordance with local, nation, and regional
regulations. Do not exceed the T5000 Series thermostat's electrical ratings.
WARNING:
Disconnect power supply before making electrical connections. Contact with
components carrying hazardous voltages can cause electrical shock and may
result in severe personal injury or death.
Risk of Electrical Shock
Ground the thermostat according to local, national, and regional regulations.
Failure to ground the thermostat may result in electrical shock and severe
personal injury and death.
Risk of Electrical Shock and Property Damage
Insulate and secure each unused wire lead before applying power to the
thermostat. Failure to insulate and secure each unused wire lead may result
property damage, electrical shock, and severe personal injury or death.
CAUTION:
Do not apply power to the system before checking all wiring connections. Short
circuited or improperly connected wires may result in permanent damage to the
equipment.
重要:
T5000列温控器仅用作在线电压风机盘管控制使用。T5000列温控器调
置失障时会导伤害损失配备增加
措施, 如常使用监控及报警系统、电压保护开关等,在安装系统中。来加强此温
度调节装置的机能失常和失效时的保护。
不要把温控器装在结露、潮湿或有湿气处。湿气会损坏温控器
要把封入前盖PCB板移出,从前盖中把封入PCB板拆卸移出将不再享有
保服务。
使线合国的规T5000流容
量。
警告:
电器线确保断开电时部件起电而导
致人员受伤甚至死亡
电击危险
照国区和的规控器接地能导和人
甚至死亡。
电击危险和财物损坏
温控前把使用的线护好使绝缘一个使的线
绝缘和保护可能导致财产损坏,电击和人员伤亡甚至死亡。
注意:
在所有的接线未检查好之前,不要给系统通电。短路或不正确的接线可能导致设
永久性的损坏。
温度调整
如果用户希望温控器显示的温度高于或低于实际温度(±5),可进行以下操
作:
在关机状态下,时按下“▲”及“
”键并保持5秒钟,显示
XX
”(不
示温控器工作模式),按“▲”或
”键调整温度值,6秒钟后自动确认。
报警
闭风电动并显
E
1
E
2
”。
E1:传感器短路报警。
E2:传感器断路报警。
当温度高于55℃显示“
HI
,当温度低于0℃显示“
LO
”。
故障检修
电源中断,温控器模式和所有设置回到最近使用和设置过的状态。
维修和替换
T5000
Johnson Controls
®
办事处联系。当联系办事处更换产品的时候,请说明外部标
签或参数表上印有的类型/型号。
技术参数
请参考产品说明书。
Temperature setting
If customers hope the displayed temperature higher or lower than the real
temperature, operate as follows:
On power off status, press both "" and "
" , keep 5 seconds, display "
XX
" (no
working mode display), press "" or "
" adjust the temperature, auto-confirmed
after 6 seconds.
Alarm
When the sensor is in fault, thermostat will close the fan and valve, display " ",
"
E
1
" and "
E
2
".
E1: Sensor short cut alarm
E2: Sensor circuit breaker alarm
Display "
HI
", temperature > 55; display "
LO
", temperature < 0
Troubleshooting
After a power outage, the thermostat mode and all settings return as most recently
used or set.
Repair and Replacement
Do not attempt to repair the T5000 Series thermostat. In case of an improperly functioning
control, contact the nearest Johnson Controls
®
representative, and specify the desired
product code number. When contacting the supplier for a replacement please state the
type/model number of the control located on the data plate or cover label.
Specifications
Refer to Product Catalog for Details.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Johnson Controls T5000 インストールガイド

カテゴリー
サーモスタット
タイプ
インストールガイド