Danfoss GreenCon RC-T2/T4 room thermostat インストールガイド

タイプ
インストールガイド
Installation Guide
GreenCon RC-T2/T4
Room thermostat
3
Installation Guide GreenCon RC-T2/T4
GB
Danfoss Heating Solutions VIE2D22P
1. Installation Steps
User Guide can be downloaded from: heating.danfoss.com.
1. Installation must be done by an authorised
electrician.
2. The room thermostat should be installed at approx.
1.5 m above oor and where the eects of sunlight,
draught or other heat sources (eg. TVs) are avoided,
see g. 1.
3. First of all, carefully remove the cover, see g. 2.
4. Connect the wire before mounting the back plate to
the wall box using the enclosed screws. Then mount
the cover to the back plate, see g 3.
2. Wiring
1. Dimensions, see g. 4
2. Wiring diagram, see g. 5 and g. 6
3. Follow the illustrations to complete the wiring:
1) RC-T4, see g. 5
2) RC-T2, see g. 6
4
Installation Guide GreenCon RC-T2/T4
GB
VIE2D22P Danfoss Heating Solutions
3. Error codes
Display Description
E1 Alarming for short circuit of
sensor
EE EEPROM chip error
Lo Indicating temperature lower
than 0°C
Hi Indicating temperature
higher than 50°C
4. Notes
1. Correct wiring is essential; using instrument to con-
rm L and N before wiring is recommended.
2. Don’t remove too much of the insulation cover from
the wire to avoid short circuit caused by the naked
wire touching the metal 86 size mounting wall box.
3. Don’t let the screw press or touch the wire when
using screw to x room thermostat in wall box. A
short-circuit risk exists if the wire insulation cover is
damaged by the screw, and if the naked wire con-
nects with the screw.
4. If walls must be painted, mount the room thermostat
after painting, to avoid dust or paint material pen-
etrating the room thermostat and thus damaging
the PCB.
5. The max load of relay is 3 A (resistive) or 1 A (induc-
5
Installation Guide GreenCon RC-T2/T4
GB
Danfoss Heating Solutions VIE2D22P
tive). The relay will be damaged if the load exceeds
the limit.
6. Don’t cover the thermostat, for instance by hanging
towels directly in front of it.
7. The room thermostat should be connected to the
corresponding actuator and valve in individual room
temperature control.
5. Technical Specications
Feature Description
Approval CE Marking, EN60730
Ambient temperature 0 - 45 ° C
IP Class 30
Max. load, inductive <1 A
Max. load, resistive <3 A
Power consumption 2 W
Power supply 85-250 Vac, 50/60 Hz
Room temp. set range 5 - 35 ° C
Shell material ABS + PC
6
Installation Guide GreenCon RC-T2/T4
GB
VIE2D22P Danfoss Heating Solutions
6. Interface
Symbols Description Symbols Description
Temperature
indication
Valve
Temperature
setting
Frost protec-
tion
Heating Eco mode
Cooling Keyboard lock
Ventilation Timer ON/OFF
Fan control 5/2 4 event
program
Clock
Actual week-
day
7
Installation Guide GreenCon RC-T2/T4
GB
Danfoss Heating Solutions VIE2D22P
7. Operation
1. Power On/O and Eco mode.
When powered o, press power button on top of
GreenCon to turn on;
When powered on, press power button for 2 sec-
onds to turn o thermostat;
When powered on, short press power button to
enter ECO mode;
In ECO mode, press” < ” or > for temperature
setting, short press power button to exit.
2. Mode selection
Press “ M to change system working mode:
Cooling “ ”, heating “ ” or ventilation “ ”
3. Setting temperature
Press “ < to reduce temperature, press > to raise
temperature. (0.5°C changed each press)
During setting temperature, SET icon will be dis-
played, after setting nished, this icon disappears
and LCD shows actual temperature.
4. Fan speed selection
Press “ ” to select (close) (Low),
(Med), (Hi), (Auto);
In Auto mode, fan speed will change according to
the dierence between room temperature and set-
ting temperature, Low-speed when this dierence
exceed 1°C, Med-speed when exceed 2°C, Hi-speed
when exceed 3°C.
*In default setting, fan speed will be “Close when
8
Installation Guide GreenCon RC-T2/T4
GB
VIE2D22P Danfoss Heating Solutions
room temperature reaches setting temperature. See
parameter P11 in chapter 9 for more details.
5. Time setting and ON/OFF timer
Time setting
Long press“ ” for 3 seconds till “hh” start ashing,
press “ < or > to adjust hour;
Short press “ ” , “mm ash, press < or > ” to
adjust minute;
Short press “ ” , “week” ash, press < or > ” to
adjust weekday;
Timer On/O setting
After nishing time setting, short press“ ” to
congure timer On/O function, press other button
or wait for 6 seconds to exit.
Short press “ ” till ON start ashing;
Press“ < or > to adjust timer ON hour;
Press “ ” to conrm;
Press“ < or > to adjust timer ON minute;
Press “ ” to conrm;
After setting timer ON”, “ OFF start ashing;
Press“ < or > to adjust timer OFF hour;
Press “ ” to conrm;
Press“ < or > to adjust timer OFF minute;
Press “ ” to conrm;
Cancel ON/OFF timer
During above steps, adjust hour and minute to “--:--“
to cancel timer function; Or congure P02 to “02” in
parameter setting to disable timer function.
6. Keyboard lock
9
Installation Guide GreenCon RC-T2/T4
GB
Danfoss Heating Solutions VIE2D22P
Press and hold M, within 6 seconds, short press >
to lock keyboard, icon “ ” will be displayed on LCD,
repeat this to unlock.
7. Reset
During power o, press and hold both M and“ < ”,
> for 10 seconds, thermostat will be reset and
restart.
8. Programming
1. 5-2 day programming
To enable this function, please congure P01 to “02”
in parameter setting.
When this function is enabled, system automatically
changes setting temperature four times per day.
Both setting temperature and event time can be
modied.
Programming function allows users to dene tem-
perature setting for 4 time period during workdays
(Mon-Fri) and weekend (Sat-Sun)
2. Default set up
Starting time and temperature for each period
7:00 / 18 °C / 28°C
9:00 / 22 °C / 26°C
18:00 / 18 °C / 28°C
21:00 / 15 °C / 30°C
3. Programming of workday set up;
Long press“ ” for 5 seconds till Mon.Tue.Wed.
Thu.Fri icon displays;
Press “ < or > to adjust starting hour of rst event,
10
Installation Guide GreenCon RC-T2/T4
GB
VIE2D22P Danfoss Heating Solutions
press “ ” to conrm;
Press “ < or > to adjust heating temperature dur
ing rst event, press “ ” to conrm;Press < or >
to adjust cooling temperature during rst event,
press “ ” to conrm;
Repeat above operation for next 3 events
4. Programming for weekend set up;
After nishing programming of work days, Sat.Sun
will appear on screen, repeat above steps to set start-
ing time and temperature on weekends.
From next event, GreenCon will automatically change
setting temperature according to this set up.
9. Parameter setting
Long press “M for 6 seconds to enter param-
eter setting mode.Then, short press M” to
select parameter; press < or > to adjust
value.
Parameter Denition Setting range
Factory
setting
P01 Programming
function On/O
01: O02:5/2
days 4 event
01
P02 Timer ON/OFF 01:ON02:OFF 01
P03 Maximum room
temperature
setting
5-35°C 30°C
11
Installation Guide GreenCon RC-T2/T4
GB
Danfoss Heating Solutions VIE2D22P
Parameter Denition Setting range
Factory
setting
P04 Minimum room
temperature
setting
5-35°C 5°C
P05 Frost protection 01: ON; 02: OFF 01
P06
Frost protection
temperature
5-17°C 5°C
P07
Default heating
temperature
5-35°C 20°C
P08
Default cooling
temperature
5-35°C 25°C
P09
Default heating
temperature for
ECO mode
5-35°C 15°C
P10
Default cooling
temperature for
ECO mode
5-35°C 28°C
P11
Fan speed when
reaching setting
temperature (DA/
DB conguration)
01: Low (DA);
02: Stop (DB) 02
P12 Clock
01: 24hour;
02: 12hour
01
P13
Display room
temperature after
turned o
01: OFF; 02: ON 01
P14
Save user set up
when powered o.
01: ON; 02: OFF 01
12
Installation Guide GreenCon RC-T2/T4
CN
VIE2D22P Danfoss Heating Solutions
1. 安装指南
可通过以下网址下载《用户指南》:heating.danfoss.com.cn
1.必须由经过专业培训合格的电工进行安装。
2.室内温控器应当安装在地面上方大约1.5米处,并且
避免受到日光、气流或者其他热源(例如:电视)的
影响。请见图1。
3.首先,小心拆下前盖。请见图2。
4.在将背板固定至暗线箱之前,使用随附的螺钉连接导
线,然后将盖子安装至背板。请见图3。
2. 接线
1. 外形尺寸,请见图4。
2. 接线端子,请见图5和6。
3. 请按照以下说明完成接线:
1)RC-T4时,请见图5。
2)RC-T2时,请见图6。
13
Installation Guide GreenCon RC-T2/T4
CN
Danfoss Heating Solutions VIE2D22P
3. 错误代码
显示屏 说明
E1
室温传感器故障
EE
EEPROM故障
Lo
房间温度低于0℃
Hi
房间温度高于50℃
4. 注意事项
1. 正确接线至关重要;接线之前,建议使用仪器确
定L与N。
2.请勿从导线上拆下过多绝缘护套,以免裸露导线接
触金属86盒造成短路。
3. 使用螺钉固定暗线箱中的室内温控器时,避免螺
钉按压或接触导线。如果螺钉将导线绝缘护套损
坏,以及裸线与螺钉连接,则有可能造成短路。
4. 如果必须对墙壁涂漆,请在涂漆后安装室内温控
器,以免灰尘或涂料渗入室内温控器,从而损坏
PCB。
5. 继电器的最大负载为3A(纯阻性)或1A(感
性负载)。如果负载超过限值,则继电器将会受
损。
6
. 请勿覆盖温控器,例如:将毛巾直接挂在温控器
前部。
7.
进行分室温控时,温控器所在房间与阀门所在的
回路要对应。
14
Installation Guide GreenCon RC-T2/T4
CN
VIE2D22P Danfoss Heating Solutions
5. 技术参数
特点 说明
认证
CE标志, EN60730
环境温度
0 - 45 °C
IP防护等级
30
最大负载(感性)
<1 A
最大负载(阻性)
<3 A
功耗
2 W
电源
85-250 Vac, 50/60 Hz
室温设定范围
5 - 35 °C
外壳材质
ABS + PC
15
Installation Guide GreenCon RC-T2/T4
CN
Danfoss Heating Solutions VIE2D22P
6. 显示界面
图标
含义 图标 含义
温度显示
电动阀门
温度设定 低温保护
供热模式 节能模式
制冷模式 键盘锁
通风模式 定时功能
开/关
风速显示 5/24时段
编程
时钟
星期显示
16
Installation Guide GreenCon RC-T2/T4
CN
VIE2D22P Danfoss Heating Solutions
7. 操作说明
1. 开关机和节能模式
关机状态下:短按位于GreenCon顶部电源键开
机;
开机状态下:长按2s关机,短按电源键进入节能
模式,液晶显示“”;
节能模式下:按“<”和“>”设置节能模式的温
度,短按电源键返回开机状态。
2. 设置运行模式
开机状态下,短按“M”键切换运行模式。
运行模式包括(供热)、(制冷)和
(通风)。
3. 设置房间温度和风速
开机状态下,按“<”降低设置温度,按“>”升
高设置温度,液晶上显示。
设定温度时,液晶显示“SET”,释放按键后,
液晶显示当前的实际温度。
短按“”键设置风速。
风速包括(关闭)、(低)、(中)、
(高)和(自动)档,短按“”键
循环选择。
*默认设置下,当房间温度达到设定温度时,风机
自动关闭,改变该设置请见第9节P02参数设置。
4.
设置时间和定时开关机
长按“”3秒,直到“hh”开始闪烁,按“<
和“>”调整小时;
再次短按“”此时“mm”闪烁,按“<
和“>”调整分钟;
17
Installation Guide GreenCon RC-T2/T4
CN
Danfoss Heating Solutions VIE2D22P
再次短按“”此时“week”闪烁,按“<
和“>”调整星期。
完成设置之后,如果开启定时开关机功能则短
按“”键进入定时开关机的时间设置,否则按
任意按键可退出(无操作6秒钟自动退出)。
若开启定时开关机功能,短按“”键,
“ON”闪烁进行定时开机设置。
按“<”和“>”设置定时开机的小时。
按“”键确认设置。
按“<”和“>”设置定时开机的分钟。
按“”键确认设置。
“OFF”闪烁进行定时关机设置。
按“<”和“>”设置定时关机的小时。
按“”键确认设置。
按“<”和“>”设置定时关机的分钟。
按“”键确认设置。
把分钟或小时设置为“--”表示该时间无效。
5.键盘锁
按住“M”键,6秒钟之内短按“>”锁定全部按
键。重复该操作可退出锁定。
6.复位
在关机状态下,同时按住“M”键和“<
、“>”键10秒,复位完成后会自动开机。
8. 5/2时间编程
如果选择了编程功能,正常工作状态下,系统会
根据事先设定好的时间自动改变设定温度;
编程操作将一个星期分为两部分:工作日和休息
日,每部分有4个时段。
18
Installation Guide GreenCon RC-T2/T4
CN
VIE2D22P Danfoss Heating Solutions
1).默认设置
各时段默认开始时间和供热/制冷温度:
7:00/18/28
9:00/22/26
18:00/18/28
21:00/15/30
2).工作日编程
长按“”键5秒,直到出现显示Mon.Tue.Wed.
Thu.Fri
按“<”和“>”设置第一个时段的开始时间
按“”键确认设置。
按“<”和“>”设置时段内的供热温度。
按“”键确认设置。
按“<”和“>”设置时段内的制冷温度。
按“”键确认设置。
重复上述操作,完成2-4时段的设置;
“OFF”闪烁进行定时关机设置。
3).休息日编程
结束工作日编程后,界面显示Sat.Sun
其余设定与工作日编程的操作方法相同。
9. 参数设定
长按“M”6秒钟进入参数设置模式。短按“M”选
择设置的参数项,按“<”和“>”调整该参数的
值。参数表如下所示。
19
Installation Guide GreenCon RC-T2/T4
CN
Danfoss Heating Solutions VIE2D22P
序号 功能定义 功能选择及设定 默认
P01 工作模式 01:手动;
02:5+2天4时段
高级可编程
01
P02 定时开关机
功能
01:开启;
02:关闭
01
P03 最高房间温度
限制
5-35℃ 30℃
P04 最低房间温度
限制
5-35℃ 5℃
P05 防冻保护功能 01:开启;
02:关闭
01
P06 防冻保护温度
设定值
5-17℃ 5℃
P07 默认制热温度
设定点
5-35℃ 20℃
P08 默认制冷温度
设定点
5-35℃ 25℃
P09 节能模式制热
温度设定点
5-35℃ 15℃
P10 节能模式制冷
温度设定点
5-35℃ 28℃
P11 DA/DB设置 01:DA(达到设
定温度时风机低
速运行);
02:DB(达到设
定温度时风机停
止运行)
02
20
Installation Guide GreenCon RC-T2/T4
CN
VIE2D22P Danfoss Heating Solutions
序号 功能定义 功能选择及设定 默认
P12 时钟显示选择 01:24hour;
02:12hour
01
P13 关机后温度显
示状态
01:不显示当前
温度;02:显示
当前温度
01
P14 保存用户设置 01:开启;
02:关闭
01
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Danfoss GreenCon RC-T2/T4 room thermostat インストールガイド

タイプ
インストールガイド