6 – Circuit Card ZM-SKS B / Rev.A 1.3
5. Initial operation
DIP switch Setting Function Connection
DIP 5 ON Red trafc light with delay
(relates to the functions of DIP 4, OFF)
- Light shines continuously or ashes (DIP 6) to give advance
warning of automatic closing 3 seconds beforehand.
- Light shines continuously or ashes (DIP 6) to give advance
warning 3 seconds before every door movement.
- Light shines continuously or ashes during door movement (DIP 6).
- Signal (continuous or ashing / DIP 6) continues for 5 seconds after door has
closed.
-
OFF Red trafc light without delay
(relates to the functions of DIP 4, OFF)
- Light shines continuously or ashes (DIP 6) to give advance
warning of automatic closing 3 seconds beforehand.
- Light shines continuously or ashes during door movement (DIP 6).
-
DIP 6 ON - Continuous signal – for the red trafc light function the light remains on
continuously during door movements and warning periods.
-
OFF
- Flashing signal – for the red trafc light function, the trafc light ashes
during door movements and warning periods.
-
DIP 7 ON „Learning“ the door open duration. The door open duration always includes a
warning time of 3 seconds.
Example: The door is required to stay open for 20 seconds:
1. Drive the door to the OPEN position.
2. Switch off the mains power supply.
3. Switch on the automatic closing timer using DIP switch 3.
4. Switch on the mains power supply.
5. Switch on DIP switch 7 (LED ashes); switch off again after 20 seconds.
6. The open door duration is now programmed to 20 seconds.
-
5.5 LED messages
LED signal Meaning Remedial measures
LED ashes once Closing edge safety device activated /
malfunctioning
Check the closing edge safety device,
remove any obstacles from path of door
LED ashes twice Photocell barrier is interrupted Check the photocell barrier,
remove any obstacles from path of door
LED ashes three times Pressure switch testing is negative, now the door can be
closed in deadman mode only
Close the door in deadman mode.
After a positive pressure switch test,
the malfunction has been remedied
LED ashes four times A running time of 120 seconds has been
exceeded
Give a new OPEN or CLOSE command
LED ashes quickly Door open duration is expiring