Danfoss FHM-CN2 Pre-assembled Mixing Shunt インストールガイド

タイプ
インストールガイド
088U7040 / VIIKD12P
© Danfoss | FHH | 2016.07 | 1
Installation overview
Installation
The FHM-CN2 must be connected to a system
according to the illustrations.
A
E
B
C
1 4
6
2
5
3
E1
Fig 2.
A
Primary water side (horizontal direction)
B
Secondary water supply
C
Secondary return
D
Primary water supply (vertical direction)
E
Primary return
1. Remove the union nuts 1, 2 and 3 and gasket
5 from mixing shunt which to be used in steps
below, as shown in Fig. 2.
2. Pre-mounted union nut 1 for connection to
the primary side supply pipe . The union nut
1 to control valve 4 must be tightened with a
torque of at least 85 Nm without any sealing
materials, as shown in Fig. 2.
3. Pre-mounted union nuts 2 and 3 for connec-
tion to the secondary side pipe or directly on
a Danfoss manifold. The union nuts 2 and 3 to
mixing shunt must be tightened with a torque
of 30 to 40 Nm with enclosed flat gasket, as
shown in Fig. 2.
4. The end of primary side return pipe E1 for con-
nection to primary side return pipe E.
5. Remove the blue cap 6, as shown in Fig. 2.
6. FTC thermostatic sensor is in package. Mount it
on the valve according to the enclosed instruc-
tion, as shown in Fig. 3.
FTC
Fig 3.
Fig. 1: Overview
Installation Guide
FHM-CN2
Pre-assembled Mixing Shunt
2 | © Danfoss | FHH | 2016.07
088U7040 / VIIKD12P
Optional Installation
Type
C
D
E
B
Fig. 4: RA-C Flow of Primary Side Install Vertically
C
D
E
B
Fig.5: RA-C Return of Primary Side Install
Refer to Fig. 2, Fig. 4, Fig. 5 structure, can choose to install the manifold in the mixing shunt left.
Fig. 6
Tips
Connection 8 and 9 are tightened from the
factory. If leaks occur due to loosening during
transportation, moving or similar, please tighten:
Connection 8 and 9 at a torque of 30 to 40 Nm.
Connection 4 and 7 at a torque of min. 85 Nm.
Connection 7 and 10 at a torque of 30 to 40 Nm
Adjust bypass control valve AVDO to required
different pressure according to actual
application, as shown in Fig. 7.
10
8
9
47
AVDO
Fig. 7
Danfoss A/S
Floor Heating Hydronics • Ulvehavevej 61 • DK-7100 Vejle • Denmark • Phone: +45 7488 8500 • Fax: +45 7488 8501
heating@danfoss.com • www.floorheating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Installation Guide FHM-CN2 Pre-assembled Mixing Shunt
088U7040 / VIIKD12P
© Danfoss | FHH | 2016.07 | 3
安装指南
FHM-CN2
水中心
安装概览
安装步骤
必须按图示要求将FHM-CN2连接至系统
A
E
B
C
1 4
6
2
5
3
E1
图2
A
水( 向)
B
次侧供
C
次侧回水
D
水(
E
一次侧回
1. 将活及密水中拆下备
,见 图 2 。
2. 将图所示活接①装到一次侧供水管A上。
再将活接①与RA-C控制阀④进行连接
不小于 85 Nm的力矩拧紧螺母, 该活接与
RA-C控制阀的连接为硬密封连接时勿需使
用任何密封材料见图2。
3. 将图所示活接分别装到二次侧供水管B
和二次侧回水管C上或丹佛斯分集水器
将活接与混水中心连接,密封料为产品附带
的密垫片⑤用 30-40 Nm 的力矩拧
。见 图 2
4. 将一次侧回水端E1与一次侧回水管E相连
图2。
5. 移除蓝色保护帽见图2。
6. FTC 恒温头在。 根据随附说明将
安装到混水中心上,见图3 。
FTC
图3
1: 安装概览
4 | © Danfoss | Danfoss | FHH | 2016.07
088U7040 / VIIKD12P
丹佛斯自动控制管理(上海)有限公司
地址:上海市宜山路900号科技大楼C楼22层
邮编:200233
电话:+86 21 61513000 传真:+86 21 61513100
电子邮件: [email protected] http://heating.danfoss.cn
连接螺⑨和活接头⑦在厂时已拧。 如
果由于在输、程中出现而导
致泄漏,请参考下述力矩拧紧相关活母:
· 用30-40 Nm 的力矩拧紧连接螺母⑧⑨ 。
· 用不小于85 Nm 的力矩拧紧活接头⑦与控
阀④。
· 用30-40 Nm 的力矩拧紧活接头⑦和一次侧
供水⑩。
请根据实际应用情况,调节压差旁通阀AVDO
所 需 压 差 ,见 图 7
10
8
9
47
AVDO
图7
其它可选
小贴士
C
D
E
B
图4: RA-C阀门一次侧供水竖直安装
C
D
E
B
图5:RA-C阀门次侧回水竖直安装
参 考 图 2 ,图 4 ,图 5 结 可 选 择 将 分 集 水 器 安 装 于 混 水 中 心 左 侧 。
图6
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Danfoss FHM-CN2 Pre-assembled Mixing Shunt インストールガイド

タイプ
インストールガイド