Installation overview
Bottom in bottom out Side in side out
Installation procedure
A
C
B
D
1
The FHM-CN5 must be connected to a system according to the illustrations.
1. Bend 1 is in package. Install bend 1 to the primary side pipe rstly. And then connect bend 1 and
connector 2 together with torque of 30 to 40 Nm with enclosed O-ring. Finally, connector 2 to 3-way
mixing valve must be tightened with a torque of 15 to 25 Nm with enclosed rubber gasket.
2. Pre-mounted union nut 3 for connection to the secondary side pipe or directly on a Danfoss manifold.
The nut 3 to mixing shunt must be tightened with a torque of 15 to 25 Nm with enclosed rubber
gasket.
Supply of primary side
Supply of secondary side
Return of secondary side
Return of primary side
B
C
A
D2
3
Installation Guide
FHM-CN5
Pre-assembled 3-Way Mixing Shunt
Installation Guide FHM-CN5 Pre-assembled 3-Way Mixing Shunt
2 | © Danfoss | HydronicS | Sub-systems | 2023.07 AN45665685584401-CN0101
Tips
RoHS compliance
1. If the primary side pipe is coming from the side,
the bend 1 must be tightened with T-connec-
tion 4 with a torque of 30 to 40 Nm.
2. Connection 5 are tightened from the factory.
Please double check the connection 5 during
installation. Please tighten at a torque of 15 to
25 Nm if loosening or leaks occur due to trans-
portation or moving.
Supply of primary side
Supply of secondary side
Return of secondary side
Return of primary side
B
C
A
D
A
C
B
D
1
4
5
5
Part Name Hazardous Substances Table
Pb Hg Cd Cr(VI) PBB PBDE
Pump X O O O O O
Brass parts X O O O O O
O: Indicates that this hazardous substance contained in all of the homogeneous material for this
part is below the limit requirement in GB/T 26572.
X: Indicates that this hazardous substance contained in at least one of the homogeneous material
for this part is above the limit requirement in GB/T 26572.
© Danfoss | HydronicS | Sub-systems | 2023.07 AN45665685584401-CN0101 | 3
安装指南
FHM-CN5
整体式三通混水中心
安装概览
A
C
B
D
12
3
底进底出 侧进侧出
安装步骤 必须按图示要求将 FHM-CN5 连接至系统。
1. 活接弯头(1)在包装内。先将图中所示活接弯头(1)装到一次侧供水管上。再将活接弯头(1)
与活接(2)进行连接,密封材料为活接弯头自带的密封圈,并用30~40 Nm的力矩拧紧。然后再
将活接(2)与三通混水阀进行连接,密封材料为产品附带的密封橡胶垫片,并用15~25 Nm的力
矩拧紧螺母。
2. 将图中所示活接(3)先装到二次侧供回水管上或丹佛斯分集水器上。 再将活接(3)与混水中心
连接,密封材料为产品附带的密封橡胶垫片,并用 15~25 Nm 的力矩拧紧螺母。
一次侧供水
二次侧供水
二次侧回水
一次侧回水
B
C
A
D
4 | © Danfoss | HydronicS | Sub-systems | 2023.07 AN45665685584401-CN0101
小贴士 1. 如果一次侧供回水管是侧进侧出, 可将活接
弯头(1)与T型接头(4)连接,密封材料为
活接弯头自带的密封圈,并用30~40 Nm的
力矩拧紧。
2. 连接件(5)出厂时已拧紧。 请在安装时再
次检查连接件(5),如果发现由于运输或搬
运导致松动或泄漏,请用15-25Nm拧紧。
一次侧供水
二次侧供水
二次侧回水
一次侧回水
B
C
A
D
RoHS 指令
A
C
B
D
1
4
5
5
部件名称 有害物质含量表
六价铬 多溴联苯 多溴二苯醚
水泵 X O O O O O
铜制部分 X O O O O O
O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
X: 表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T 26572规定的限量要求。
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Danfoss FHM-CN5 インストールガイド

タイプ
インストールガイド

他の言語で