602Q-B01A-NB-Issue Date 12 2013
3
T8200-TB20-9JS0/9JR0、T8200-TF20-9JS0/9JR0、T8200-TB21-9JS0/R0 Series Touch Screen Fan Coil Thermostat - Installation Instructions
T8200-TB20-9JS0/9JR0、T8200-TF20-9JS0/9JR0、T8200-TB21-9JS0/R0系列触摸屏风机盘管温控器 - 安装说明
Instructions
On/Off Setting:
Press " " to turn on, press again to turn off, close the fan and valve.
Mode Selection:
Press "
M
" to change the working mode, " " for Cooling, " " for
Heating, " " for venting. (For model T8200-TF20-9JS0/9JR0, key "
M
" is unavailable
under auto mode. When setting temperature is more than 1℃ higher than indoor
temperature, the mode will change to heating automatically, When setting
temperature is more than 1℃ lower than indoor temperature, the mode will change
to cooling automatically.)
Temperature Setting:
Press either "
∧
" or "
∨
" button to increase or decrease by 0.5℃.
Fan Speed Adjustment:
Cooling or Heating Mode Operation
T8000, has 4 speeds fan control: Auto "
", High " ", Middle " ",
Low "
" fan. Short press the " " button switches through the sequence.
Fan only Operation
T8000, has 3 speeds fan control; High "
", Middle " ", Low
"
" fan. Short press the " "button switches through the sequence.
Note:
Fan stops at Floor Heating Mode.
Time Adjustment and Time-On/Off Operation:
Time Adjustment:
Continuously press "
" button until "
mm
" in "
hh:mm
" blinks,
then press "
∧
" or "
∨
" to adjust the minute. Press "
" button again until "
hh
" in
"
hh:mm
" blinks, then press "
∧
" or "
∨
" to adjust the hour. Press " " button again
and adjust the weekday by the same method.
Time-On/Off Operation:
Continuously press "
" button until the ''
hh:mm
'', " ",
"
ON
" appear, and " ", "
ON
" blink. Press either "
∧
" or "
∨
" key to adjust the Time-On
by 30 minutes. Press " " button again until " ", "
OFF
" blink. Then adjust the Time-
Off by the same method. Time-On/Off setting performs only once within one day.
Time-On/Off Cancel:
Continuously press "
" button until the ''
hh:mm
'', " ",
"
ON
" appear, and " ", "
ON
" blink. Press either "
∧
" or "
∨
" key to adjust the Time-
On ''
00
:
00
''. Press " " button again until " ", "
OFF
" blink. Then adjust the Time-
Off ''
00
:
00
'' by the same method.
Lock function:
Lock function:
If Lock function is enabled, the thermostat will be locked
automatically after 30 seconds unused.
Unlock function:
Hold down the fan key 5 seconds to unlock.
Unoccupied mode (T
8200
-TB
20
-
9
JS
0
/ T
8200
-TF
20
-
9
JS
0
/T
8200
-TB
21
-
9
JS
0
):
Occupied/Unoccupied mode "
" is active if monitor is equipped, which is operated
by entrance card.
To T8200-TB20-9JS0 and T8200-TB21-9JS0: While entrance card is pulled out,
the temperature automatically set to 26℃, fan is on LO-speed if the thermostat
is in cool mode; the temperature set to 18℃, fan is on LO-speed if in heat mode.
Temperature Setting is invalid until the entrance card is inserted again.
To T8200-TF20-9JS0:
In Manual mode, while entrance card is pulled out, the
temperature automatically set to 26℃, fan is on LO-speed if the thermostat is in
cool mode; the temperature set to 18℃, fan is on LO-speed if in heat mode. In
Auto mode, while entrance card is pulled out, if the room temperature is over 26℃,
the thermostat becomes cooling mode automatically, cold water valve is opened
and fan is on LO-speed; if the room temperature is below 18℃, the thermostat
becomes heating mode automatically, hot water valve is opened and fan is on LO-
speed; If the room temperature is between 18℃ to 26℃, both cold and hot water
valve are closed, and fan is on LO-speed.
Remote Temperature sensor (T
8200
-TB
20
-
9
JR
0
/ T
8200
-TF
20
-
9
JR
0
/T
8200
-
TB
21
-
9
JR
0
):
When remote sensor is connected, the built-in sensor will be disable.
Timer Function:
On power on status, hold the "
" button for 5s to enter the Timer interface, where
the thermostat's accumulated running time is showing.
On power off status, hold the "
" button for 10s to enter the Timer interface,
accumulated running time can be cleared by pressing "
".
使用说明
开关机设置:
按“ ”键一次开机;再按一次关机,同时关闭风机盘管、电动
阀。
模式调节:
开机状态下,按“
M
”键进行工作模式切换。液晶显示“ ”表示
制冷,显示“
”表示制热,显示“ ”表示通风。(注:在T8200-TF20-
9JS0/9JR0中,当自动模式有效时,“
M
”键失效,无通风模式,当设定温度
比测量温度高1℃以上时,自动进入制热模式,当设定温度比测量温度低1℃
以上时,自动进入制冷模式)
温度设置:
在开机状态下,按“
∧
”或“
∨
”可进行设置温度的调节,每按
一次,温度变化0.5℃。
风速调节:
制冷、制热模式下操作
温控器有4种风机速度,自动“
”、高“ ”、中“ ”、
低“
”风速。按“ ”按钮,将循环显示。
仅风机操作
温控器有3种风机速度,高“
”、中“ ”、低“ ”风
速。按“
”按钮,将循环显示。
注意:
每一次开关T8000系列温控器,开始时都将启动低速风机。这一软启
动特点防止了高启动电流,同时节约了用电,3秒以后,风机按设定运转。
时钟和定时开关机设置:
时钟调整:
按“
”键,直至出现“
hh:mm
”的“
mm
”闪烁,按“
∧
”或
“
∨
”键调整分钟。再按“
”键,“
hh:mm
”的“
hh
”闪烁,按“
∧
”
或“
∨
”键调 整小时。再按“
”键, 星期的显示符闪 烁,按“
∧
”或
“
∨
”键调整星期。
定时开关机设置:
开机状态下,按“
”键,直至出现“
hh:mm
”、“ ”、
“
ON
”符号,并且“
”、“
ON
”闪烁,按“
∧
”或“
∨
”键调整,每按
一次变化30分钟。再按“
”键,直至出现“ ”、“
OFF
”符号闪烁,用
上述方法,设置定时关机的时间。设定一次定时开关机时间只能执行一次,
即只在一天内有效。
取消定时开关机设置:
开机状态下,按“
”键,直至出现“
hh:mm
”、
“
”、“
ON
”符号,并且“ ”、“
ON
”闪烁,按“
∧
”或“
∨
”键调整
定时开机的时间调至“
00
:
00
”;再按“
”键,直至出现“ ”、“
OFF
”
符号闪烁,用上述方法,将定时关机的时间调整为“
00
:
00
”。
按键锁功能
:
锁按键功能:
如果温控器开启了锁按键功能,在没有人使用的情况下30秒后
会自动把按键锁上,禁止其他人员对温控器进行操作。
按键解锁:
按风速按键5秒即可解锁(在没有人使用的情况下30秒后会自动把
按键锁上)。
门卡功能
(T
8200
-TB
20
-
9
JS
0
/ T
8200
-TF
20
-
9
JS
0
/T
8200
-TB
21
-
9
JS
0
)
如安装了有人/无人监控装置,有人/无人模式“
”将会启动。可通过门卡
进入有人/无人模式。
在T8200-TB20-9JS0和T8200-TB21-9JS0型号中,当门卡拔出后,进入无人
模式,此时液晶显示“
”,如果温控器处于制冷模式时,温度自动设置为
26℃,风机低速运行。如果温控器处于制热模式时,温度自动设置为18℃,
风机低速运行。此时上下键调节温度功能失效。插入门卡后,恢复正常。
在T8200-TF20-9JS0型号中,手动模式下,当门卡拔出后,如果温控器处于制
冷模式时,温度自动设置为26℃,风机低速运行。如果温控器处于制热模式
时,温度自动设置为18℃,风机低速运行。自动模式下,当门卡拔出后,如
果室内温度大于26℃,温控器自动变成制冷模式并且冷水阀打开,风机低速
运行;当室温小于18℃,温控器自动变成制热模式并且热水阀打开,风机低
速运行;在18℃~26℃之间,冷水阀和热水阀关闭,风机低速运行。
外接温度传感器
(T
8200
-TB
20
-
9
JR
0
/ T
8200
-TF
20
-
9
JR
0
/T
8200
-TB
21
-
9
JR
0
):
当温控器接上外置传感器时,内置NTC自动失效。
计时功能
:
在开机状态下,长按“
”键5S,此时进入计时界面,此时显示的时间为温
控器累计运行的时间。
在关机状态下,长按“
”键10S,进入计时界面,此时按“ ”键可以将累
计时间清零。