Specications
Service Hot and chilled water models,
up to 50% glycol.
System Static Pressure Limits 1.6 MPa (PN16)
Max Close-Off Pressure
Differential
200 kPa
Seat Leakage < 0.01% Kvs, ANSI (IV)
Fluid Temperature Limit
Ambient Temperature Limit
5…60º C
5…40º C
Travel time open
Travel time close
18 seconds
7 seconds
Materials
Body
Stem
Seat
Paddle
Forged Brass
Nickel Plated Brass
Brass
Styrene Butadiene Rubber (SBR)
Actuator Voltage
ZVnnnT-x-B
ZVnnnT-x-A
Power Requirements
220 VAC ±10% 50/60Hz
24 VAC ±10% 50Hz
6.2 Watts
Housing Type IP20, Indoor Use Only
Noise Level <35db
Two-Position Motorized Valve Assembly (G Thread)
Part Num-
ber
Ports Pipe Size Kv Actuator
Voltage
ZV215T-2-B
2-Way
DN15 1/2” 2.2
220 Vac
ZV220T-3-B DN20 3/4” 2.6
ZV225T-3-B DN25 1” 3.2
ZV315T-2-B
3-Way
DN15 1/2” 2.2
ZV320T-3-B DN20 3/4” 2.6
ZV325T-3-B DN25 1” 3.2
ZV215T-2-A
2-Way
DN15 1/2” 2.2
24 Vac
ZV220T-3-A DN20 3/4” 2.6
ZV225T-3-A DN25 1” 3.2
ZV315T-2-A
3-Way
DN15 1/2” 2.2
ZV320T-3-A DN20 3/4” 2.6
ZV325T-3-A DN25 1” 3.2
ZV Series
Zone Valve Assemblies
Installation
Inspect the package for damage. If package is damaged, notify
the appropriate carrier immediately. If undamaged, open the pack-
age and inspect the device for obvious damage. Return damaged
products.
Required Tools
• Tools (not provided)
• Wrench 1 to 1-5/8” (if threaded valve)
• Soldering equipment (if sweat t) or are
• Training: Installer must be a qualied, experienced technician
• Other accessories as appropriate
Mounting
The valves can be mounted in horizontal or vertical piping. When
installed in horizontal piping, the actuator must be above the valve
body and can be tilted up to 85 degrees from vertical.
Make certain there is no overhead water source that may drip onto
valve actuator.
In normal service, some condensation may occur on or around
the valve. A drip pan may be necessary or the valve body may be
insulated.
Installing Actuator on Valve Body
Slowly latch the manual operating lever in the open, en-
gaged position. Depress the release button. Align the
body with the actuator to ensure the stem is inserted
into the large mating hole on the bottom side of the
actuator. Engage the actuator on the body and release
the button.
Notes
• For high-rise buildings, a reduction valve should
be used to ensure static and differential pressure
requirements are met.
• Manual open lever: When the manual open lever
is in the locked position (valve open), it will remain
locked until power is applied to the actuator.
When power is applied, the manual open lever
will automatically disengage and the actuator will
function per the control signal.
• The direction of water ow should be the same as
the arrow on the valve body.
• The actuator should not be used as the fulcrum of
force during installation.
Installation angle
HAZARD OF ELECTRIC SHOCK
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and operation of this
electrical equipment and the installation, and has received safety training to recognize and avoid the hazards
involved. NEC2011 Article 100
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
DANGER NOTICE
RISK OF EQUIPMENT DAMAGE
• Avoid electrical noise interference.
• Do not install near large contactors, electrical machinery, or welding equipment.
• Only use manual override when power is off.
• Do not use manual override with actuators mounted in tandem.
Failure to follow these instructions will result in damage to the
gear train or other mechanical damage.
© 2023 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. July, 2023 cp
Document Number: F-28269-3
www.schneider-electric.com
schneider-electric.com | 1
Installation Instructions
3-Way Valve in Diverting Conguration,
Normally Closed to the Coil
2-Way Valve with Normally
Closed Actuators
ZVnnnT Series Hazardous Substance
Pb Hg Cd Cr6+ PBB PBDE
Cables & cabling
accessories oooooo
Metal parts x o o o o o
Plastic or rubber
parts oooooo
Grease o o o o o o
PCB electronic x o o o o o
This table is prepared in accordance with the provisions of SJ/T 11364.
o Indicates that said hazardous substance contained in all of the homogeneous
materials for this part is below the limit requirement of GB/T 26572.
x Indicates that said hazardous substance contained in all of the homogeneous
materials for this part is above the limit requirement of GB/T 26572.
All of the other components not listed in the table do not contain the restricted sub-
stances above the threshold level.
Wiring Diagram