Warning
Please read this instruction sheet carefully before use.
Switch off the power before wiring.
DVP04TC-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damages on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on.
Make sure the ground termnial is correctly grounded in order to prevent electromagnetic interference.
Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire
to prevent interference.
When setting the
thermocouple temperature sensor mod e, please make sure that the setting of CR#1 is correct, or it will cau se
serious errors.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta’s DVP series PLC. DVP04TC-H2 is able to receive 4 points of external
thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type) and convert them into 14-bit
digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, the data in
DVP04TC-H2 can be read or written. There are 49 16-bit control registers (CR) in DVP04TC-H2.
DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
D - L + L - L +
24V 0V
L - L + L - L + L -
D + SLD
8
SLD SLD SLD
CH 1 CH 2 CH 3 CH4RS-4 85
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension unit/module
7
Mounting hole
3
Model name
8
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension unit/m odule
5
DIN rail clip
ENGLISH
External Wiring
CH4
DC/ DC
5V
AG
+15 V
-15 V
AG
24+
0V
L -
*2
*3
+
-
The rmoc ouple
The rmoc ouple
Shi eldi ng
cabl e *1
Shi eldi ng
cabl e *1
gro undi ng
Termin al of
powe r mo dul e
Ear th
(10 0 or les s)
*1: The wiring used for analog input should adopts the connection cable or shielding cable of thermocouple temperature sensor
J-type / K-type / R-type / S-type / T-type and should be separated from other power cable or wirings that may cause interference.
The screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).
*2: Terminal SLD is the ground location for noise suppression.
*3: Please connect the
terminal on both the power module and DVP04TC-H2 to the system earth point and ground the system
contact or connect it to the cover of power distribution cabinet.
Note: DO NOT wire empty termina l . Use 60/75°C copper conductor on ly.
Specifications
Temperature
measurement module
Explanation
Power supply voltage 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog output channel 4 channels/module
Applicable sensor types
J-type, K-type, R-type, S-typ e, T-type Floating thermocouple sensor
Range of input
temperature
See the table in Section
Range of digital
conversion
See the table in Section
Resolution 14 bits (0.1°C/0.18°F)
Overall accuracy
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response tim e 200ms × the number of channels
Isolation Isolation between digital area and analog area. No isolation among channels.
Digital data format 13 significant bits out of 16 bits are available; in 2’s complem ent
Average function Yes; available for setting up in CR#2 ~ CR#5 ; range: K1 ~ K20
Self-diagnosis Upper and lower bound detection/channel
Communication mode
(RS-485)
ASCII/RTU mode. Com munication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps.
ASCII data form at: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop
bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the
closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to connect to MPU
and will not occupy any digital I/O points.
Other Specifications
Power supply
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W supplied b y external power.
Environment
Operation/storage
1. Operation: 0°C~ 55°C (Temperature), 50 ~ 95% (Humidity), pollution degree 2
2. Storage: -25°C ~ 70°C (Temperature), 5 ~ 95% Hum idity
Vibration/shock immunity
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-2 7 (TEST Ea)
Control Register
CR
b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0
R Model name
Set up by the system.
DVP04TC-H2 model code = H ’6403.
You can read the model name from the program and see
if the extension module exists.
Reserved CH4 CH3 CH2 CH1
#1
Thermocouple type
Take the setting of CH1 for example:
1. When (b2, b1, b0) is set as (0,0,0), choose J-type
2. When (b2, b1, b0) is set as (0,0,1), choose K-type
3. When (b2, b1, b0) is set as (0,1,0), choose R-type
4. When (b2, b1, b0) is set as (0,1,1), choose S-type
5. When (b2, b1, b0) is set as (1,0,0), choose T-type
CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module. T here are
2 modes (J -type and K-t ype) for each channel which can be set u p separately. For example, if the user needs to set up
CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8 ~ b6 = 000) and CH4: mode 1 (b11 ~ b9 =
001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) h ave to be reserved. T he default value = H’0000.
#2
CH3 average time
#5 H’409B
R/W CH4 average time
Range of settings in CH1 ~ CH4: K1 ~ K20. Default =K10.
Please note that when PLC MPU writes in the average
time by TO/DTO instruction, please use the rising/falling
edge contact detection instructions (L DP/LDF…) in case
you may not obtain the correct average temperature.
#6
R Average °C temp. measured at CH1
R Average °C temp. measured at CH2
R Average °C temp. measured at CH3
R Average °C temp. measured at CH4
Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time settings in
CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the average of the most
recent 10 temperature signals in Ce lsius at CH1 ~ CH4.
#10
R Average °F temp. measured at CH1
R Average °F temp. measured at CH2
R Average °F temp. measured at CH3
R Average °F temp. measured at CH4
Average Fahrenheit temperature m easured at CH1 ~
CH4.
Unit: 0.1°F
CR#10 ~ CR# 13: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time settings
in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#10 ~ CR#13 will be the average of the
most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4.
#14
R Present °C temp. measured at CH1
R Present °C temp. measured at CH2
R Present °C temp. measured at CH3
#17
R Present °C temp. measured at CH4
Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
#19
R Pres ent °F temp. measured at CH1
R Pres ent °F temp. measured at CH2
R Pres ent °F temp. measured at CH3
R Pres ent °F temp. measured at CH4
Present Fahrenheit temperature measured at CH1 ~ C H4.
OFFSET value of CH4
Adjustable OFFSET settings at CH1 ~ CH4.
Range: -1,000 ~ +1,000
Default = K0
Unit: 0.1°C
#30
R Error status
Register for storing all error status.
See the table of error status for more information.
CR#30: Error status (see the table below)
Error status Content b15 ~ b8 b7 b6 b5 b4 b3 b2 b1 b0
Abnormal po wer supply K1 (H’1) 0 0 0 0 0 0 0 1
Wiring to empty external contact
K2 (H’2) 0 0 0 0 0 0 1 0
Incorrect mode setting K4 (H’4) 0 0 0 0 0 1 0 0
OFFSET/GAIN error K8 (H’8) 0 0 0 0 1 0 0 0
Hardware malfunction K16 (H’10) 0 0 0 1 0 0 0 0
Abnormal digital range K32 (H’20) 0 0 1 0 0 0 0 0
Incorrect average times setting
K64 (H’40) 0 1 0 0 0 0 0 0
Instruction error K128 (H’80)
1 0 0 0 0 0 0 0
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the
same time. 0 = normal; 1 = error.
#31
Communication address se tting
For setting RS-485 communication address.
Range: 01 ~ 254, Default = K1.
#32
Communication speed (b aud rate)
setting
For setting up communication speed: 4,800/9,600/19,200/
38,400/57,600/115,200 bps. ASCII data format: 7-bit
bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1
stop bit (8, E, 1). Default: H’00 02.
b0: 4,800 bps.
b1: 9,600 bps (default).
b2: 19,200 bps.
b3: 38,400 bps.
b4: 57,600 bps.
b5: 115,200 bps.
b14: High/low bit exchange of CRC checksum (only valid
in RTU mode)
b15: Switch betwe en ASCII/RTU modes; 0 = ASCII mode
(default)
b15
ERR LED CH4 CH3 CH2 CH1
#33
R/W Returning to default setting
Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to
default settings.
ERR LED definition: default of b12 ~ b15 = 1111
1. When b12 = 1, CH1 wiring to empty external contact,
ERR LED will flash.
2. When b13 = 1, CH2 wiring to empty external contact,
ERR LED will flash.
3. When b14 = 1, CH3 wiring to empty external contact,
ERR LED will flash.
4. When b15 = 1 CH2 wiring to empty external contact,
ERR LED will flash.
#34
R Firmware version
Displaying the current firmware version in hex; e.g.
version 1.0A is indicated as H’010A
#35 ~ #48 For system use
PID Control Registers
CR#
CH1
Register content Explanation
#51
Temperature SV Range: K-1,000 ~ K8,000. Default = K0.
#52
Sampling time (s) Range: K1 ~ K30 (s). Default = K2.
#53
KI Integral constant, Default = K2,098.
#55
KD Derivative constant, Default = K-29.
#56
Upper limit of I value Range: K-32,760 ~ K32,760. Default = K0.
#57
Lower limit of I value Range: K-32,760 ~ K32,760. Default = K0.
#58
R
I value Current accumulated offset value. Default = K0.
#59
Heating/cooling control 0: Heater, 1: Cooler. Default = K0.
#60
Upper limit of output Range: K-32,760 ~ K32,760. Default = K4,000.
#61
Lower limit of output Range: K-32,760 ~ K32,760. Default = K0. .
#62
R
Output percentage (%) Range: K0 ~ K1,000 (Unit: 0.1%). Default = K0.
#63
R Output width (ms) Width of control output, Unit: ms. Default = K0.
#64
R
Output cycle (ms) Cycle of control output, Unit: ms. Default = K0.
#65
R Output volume Default = K0.
#66
PID_Run/Stop 0: Stop, 1: Run. Default = K0.
#67
Auto Tune 0: Disabled, 1: Auto-tuning. Default = K0.
CR#0 ~ CR#127: The corresponding parameter address H’4096 ~ H’4115 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
1. Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU
data format (8-bit, even bit, 1 stop bit (8, E, 1)).
2. Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data
into register).
3. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction
4. Symbols: : Latched. : Non-latched. R: Able to read data by FROM instruction or RS-485
communication. W: Able to write data by TO instruction or RS-485 communication.
Temperature / Digital Curve
°C/°F Temperature Measurement Mode:
Max.
Min.
Measured
temp eratur e input
Min.
Max.
Range of input temperature
Range of digital con version
Thermo
Min. (°C /
°F
) Max. (°C /
°F
) Min. (°C /
°F
) Max. (°C /
°F
)
J type -100°C / -148°F
-10°C / -14°F 1,700°C / 3,092°F
K-100 / K-140 K17,000 / K30,920
-10°C / -14°F 1,700°C / 3,092°F
K-100 / K-140 K17,000 / K30,920
350°C / 662°F K-1,000 / K-1,480
K3,500 / K6,620
(OPEN TYPE)
CR#1
DVP DVP04TC-H2 4 J, K, R, S,
T 14 DVP-PLC EH2 FROM/TO
49 CR (Control Register) 16 bits
0.1
°C
0.18
°F
mm
D - L + L - L +
24V 0 V
L - L + L - L + L -
D + SL D
8
SLD SLD SL D
CH 1 CH 2 CH3 CH 4RS-485
1
DIN (35mm)
6
2
7
3
8
4
9
5
DIN
1 J / K / R / S / T
1.95 kg-cm (1.7 in-lbs)
2 SLD
3 DVP04TC-H2
60/75°C
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
4
J-type, K-type, R -type, S-type, T-type
14 bits (0.1°C/0.18°F)
±0.5% (25°C, 77°F) ± 1% (0 ~ 55°C, 32 ~ 131°F)
200ms ×
16 13 bits
CR#2 ~ CR#5 K1 ~ K20
(RS-485)
ASCII/RTU (4,800/9,600/19,200/38,400/57,600/115,200 ) ASCII
7-bit 1 stop bit (7, E, 1) RTU 8-bit 1 stop bit
(8, E, 1) PLC RS-485
DVP-PLC
0 7 8 I/O
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W,