CR# Attrib. Register name Explanation
#3 O R/W CH2 output mode setting
Mode 0 (H’0000): Voltage output (10V)
Mode 1 (H’0001): Current output
(0~+20mA)
Mode 2 (H’0002): Current output
(+4~+20mA)
Mode -1 (H’FFFF): All channels are
unavailable
#4 O R/W CH3 output mode setting
#5 O R/W CH4 output mode setting
#16 X R/W CH1 output signal value Voltage output range: K-32,000~K32,000.
Current output range: K0~K32,000.
Default: K0.
CR#18~CR#19 of DVP02DA-E2 are
reserved.
#17 X
R/W CH2 output signal value
#18 X
R/W CH3 output signal value
#19 X
R/W CH4 output signal value
#28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH4.
Default = K0
Definition of Offset:
The corresponding voltage (current) input
value when the digital output value = 0
#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
#34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value of CH1 ~ CH4.
Default = K16,000.
Definition of Gain:
The corresponding voltage (current) input
value when the digital output value = 16,000
#35 O R/W Adjusted Gain value of CH2
#36 O R/W Adjusted Gain value of CH3
#37 O R/W Adjusted Gain value of CH4
Adjusted Offset Value, Adjusted Gain Value:
Note1: When using Mode 2, the channel do NOT provide setups for adjusted Offset or Gain
value.
Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to
defaults.
#40 O R/W
Function: Set value changing
prohibited
Prohibit set value changing in CH1 ~ CH4.
Default= H’0000.
#41 X R/W
Function: Save all the set
values Save all the set values. Default =H’0000.
#43 X R Error status Register for storing all error status. Refer to
table of error status for more information.
#100 O R/W Function: Enable/Disable limit
detection
Upper and lower bound detection, b0~b3
corresponds to CH1~CH4 (0: Disable/ 1:
Enable). Default= H’0000.
#101 X R/W Upper and lower bound status
Display the upper and lower bound status.
(0: Not exceed /1: Exceeds upper or lower
bound value), b0~b3 corresponds to
Ch1~Ch4 for lower bound detection result;
b8~b11 corresponds to CH1~CH4 for upper
bound detection result..
#102 O R/W Set value of CH1 upper bound
Set value of CH1~CH4 upper bound. Default
= K32000.
#103 O R/W Set value of CH2 upper bound
#104 O R/W Set value of CH3 upper bound
#105 O R/W Set value of CH4 upper bound
#108 O R/W Set value of CH1 lower bound
Set value of CH1~CH4 lower bound. Default
= K-32000.
#109 O R/W Set value of CH2 lower bound
#110 O R/W Set value of CH3 lower bound
#111 O R/W Set value of CH4 lower bound
#114 O R/W Output update time of CH1 Set value of CH1~CH4 lower bound. Setting