4
in the buckle state. At the same time, the energy storage indicator board and auxiliary switch are reset,
and the motor power supply circuit is connected. If the external power supply is also connected, it will
enter the energy storage state again, and the connecting rod will pull the on / off indicator to indicate the
position of "┃", at the same time, pull the counter to realize counting, and drive the connecting rod to pull
the spindle to drive the auxiliary switch to switch.
Note: when the circuit breaker is in the closing state, or the closing locking device is selected but the
external power supply is not connected, and the handcart type circuit breaker is in the process of propulsion,
the closing operation cannot be carried out.
2-2-3 Opening
It can not only press the "opening" button, but also connect the external power supply to make the
opening coil or over-current coil act, so that the opening holding switch and the opening half axis are
unlocked to realize the opening operation. The energy stored by the contact spring and the opening
spring 25 separates the dynamic and static contacts of the arc extinguishing chamber 21. In the later stage
of the opening process, the hydraulic buffer absorbs the residual energy and limits the opening position.
Pull the "O" connecting rod to switch off the switch.
2-2-4 Undervoltage protection function
When the secondary control voltage is less than or equal to 90% of the rated voltage, the
undervoltage module must start to store energy for components and enter the holding state; when the
secondary control voltage drops to 65% of the rated voltage, the energy of the undervoltage module is
released to the opening coil of the circuit breaker to release the opening holding switch and the opening
half shaft So as to realize the opening operation.
2-3 Anti misoperation interlock
The circuit breaker can provide perfect anti misoperation function
1. After the closing operation of the circuit breaker is completed, the closing interlocking board 18
rotates against the closing board 13, and it cannot be closed again when the circuit breaker is not opened.
2. After closing the circuit breaker, if the closing electric signal is not removed in time, the internal
anti tripping controller of the circuit breaker will cut off the closing circuit to prevent multiple reclosing.
3. When the handcart type circuit breaker fails to reach the test position or working position, the
handcart interlocking board 19 shall buckle the closing board and cut off the closing circuit to prevent the
circuit breaker from entering the load area in the closing state.
4. After the handcart type circuit breaker is closed in the working position or test position, the trolley
will not be able to move if the roller presses the pushing mechanism, so as to prevent pulling out or
pushing the load area in the closing state.
5. If electrical closing locking is selected, manual closing operation is prevented when the secondary
control power supply is not connected.