Bernard Controls AQ Range SWITCH Installation & Operation Manual

タイプ
Installation & Operation Manual
1
AQ SWITCH
RANGE
Start Up Guide
Instructions de mise en service
SUG_17003 - Ind. A
Art : 5100510
TABLE OF LANGUAGES
1 English --------------------------------------------------- 3
2
中文
------------------------------------------------------ 3
3
한국어
--------------------------------------------------- 5
4
日本語
--------------------------------------------------- 7
3
42
29
16
2
2
TABLE OF CONTENTS
1 SAFETY ---------------------------------------------------------- 3
2 PACKAGING, STORAGE AND MAINTENANCE----------------- 3
Packaging
Storage
Maintenance
3 ASSEMBLY ------------------------------------------------------- 5
Changing closing direction indication
4 EMERGENCY HANDWHEEL OPERATION ---------------------- 6
5 ELECTRICAL COMMISSIONNING ------------------------------- 6
5.1 Connection and preliminary tests
5.2 Position feedback potentiometer (OPTION)
5.3 TAM position transmitter (OPTION)
5.4 Heating resistor
6 TRAVEL LIMIT SETTINGS------------------------------------- 11
Single cam setting
Cams and mechanical stops setting
7 TORQUE LIMITING DEVICE (AQ25 / 30 / 50 only) -------- 14
3
4
4
15
12
7
7
6
English
3
1 SAFETY
This device complies with current applicable safety standards.
Installation, maintenance and use of this unit require a skilled and
trained staff.
Please carefully read this whole document before mounting and
starting-up the actuator.
2 PACKAGING, STORAGE AND MAINTENANCE
Packaging
AQ actuators are delivered in a cardboard box of a size equivalent to
the actuator and sit in a cardboard wedge.
Storage
Actuators should be stored under a shelter, in a clean and dry place
and protected from wide temperature variations.
Avoid placing the actuator directly on the floor.
Check that plugs on cable entries are correctly tightened.
Check that cover screws are correctly tightened to ensure
weatherproof sealing of the cover.
AQ actuators include electrical components and lubricated gears.
Even with a weatherproof enclosure, oxidation, seizing and other
alterations may occur if actuators are not correctly stored.
What to check after storage
1. Visually check the electrical equipment.
2. Manually operate micro-switches, buttons, selectors, etc., to
ensure their proper mechanical functioning.
3. Manually operate the actuator.
Heating element should be connected to power supply especially
if the storage place is wet (standard 230 VAC, except
otherwise specified).
4
English
4
What to check on installed non-commissioned actuators
If you expect a long period between actuator mounting and electrical
wiring:
1. Visually check that cable entries and cover are tightly closed.
2. In case of outdoor installation, cover the unit with a plastic
protective film.
Actuators equipped with electronic components
Long term storage of electronic components which are not in service
increases the risk of malfunction. This is not advisable.
If a long term storage is absolutely necessary, we strongly
recommend a revision of the electronic boards in our factory
before actuator usage.
Maintenance
This actuator features lifetime lubrication. While the device is
correctly mounted and sealed, no specific maintenance is required.
Test once a year the motor operation and make sure that the
electrical compartment is free from condensation.
If it operates in a wet atmosphere, this actuator includes an anti-
condensation heater to avoid condensation build-up.
5
English
5
3 ASSEMBLY
Actuator should be attached directly to the valve using proper bolts
or via a proper interface.
After assembly, the actuator can operate in any position.
However:
do not lift the actuator by the handwheel to avoid damage on
internal gearing
cable glands must not be oriented upwards
(loss of water
tightness)
Changing closing direction indication
As a standard, AQ actuator is configured to close clockwise. If the
actuator must close counter-clockwise, you can change
orientation of the position indicator cap.
Standard indicator orientation
for clockwise closing
Reverse indicator orientation
for counter-clockwise closing
How to change cap orientation
1. Disassemble the cover then the cap.
2. Turn the cap 90°.
3. Reassemble the cap then the cover.
6
English
6
4 EMERGENCY HANDWHEEL OPERATION
AQ actuators feature a handwheel for emergency operation.
To avoid potentially harmful turning protruding parts during
electrical operation, AQ handwheels feature a foldable handle: you
can fold it during electrical operation and unfold it if you need to
operate the actuator manually.
5 ELECTRICAL COMMISSIONNING
Connection and preliminary tests
8 - Capacitor
7 - Switches board
6 - Torque limiter
5 - Motor
4Heating resistance
3 - Cams
2 - Terminal block
1 - Position indicator
Actuator and its components are wired to internal terminal blocks.
To proceed to the wiring, remove the cover and pass the cables
through the M20 cable entries or ¾” NPT cable entries
(depending on order).
Please refer to the wiring diagram enclosed for terminal numbering.
Both thermal protector and torque limit switches must be integrated
into your control system in order to prevent potential damage to the
actuator or valve.
7
8
English
7
What to check after wiring
Once actuator wiring is completed, please check the following:
1. Make sure that power supply voltage matches information on
the sticker on the side of the actuator.
2. Check that all connectors or cable glands are correctly
tightened.
3. Manually drive the valve to a mid-travel position.
4. Electrically operate counter-clockwise rotation and check that
the motor rotates in the right direction.
5. Manually press on the counter-clockwise travel limit switch
then the motor should stop.
6. Repeat steps 4 and 5 for clockwise direction.
If any fault is detected at this stage, please check again the
whole wiring.
Position feedback potentiometer (OPTION)
The potentiometer used for actuator
position feedback is driven by the travel
cam block system.
For clockwise closing:
0% position indicates a closed valve
100% position indicates an open valve.
Resistance value is measured between 16 and 17 terminals.
English
8
How to set the potentiometer circuit board
You can set the zero of the potentiometer with the 0% position
screw. Use a flat blade screwdriver to turn this screw.
1. Drive the actuator to the CLOSED position.
2. Untighten the positioner pinion blocking screw.
3. Adjust the potentiometer by turning its shaft so that the
resistance value exceeds 0 Ohm and regularly increases then
turn backwards to reach the closest value to 0 Ohm. Tighten
back the positioner pinion blocking screw.
4. Drive the actuator to the OPEN position and write down the
resistance value corresponding to the 100% position.
5. Come back to the CLOSED position and check that the
resistance shows a repeatable near zero value for the 0%
position.
Signal inversion
To change the signal variation direction, invert potentiometer wires
on the terminal block (e.g. for a connection on 16/17/18,
invert 16 and 18).
Position feedback potentiometer (Left) & TAM position transmitter (Right)
9
English
9
TAM position transmitter (OPTION)
The TAM transmitter delivers a 4 to 20 mA signal linearly proportional
to the angular position of the valve.
Electrical connections
To connect TAM, refer to the wiring diagram supplied.
Filtered or stabilized power supply should be provided within the 12
to 32 VDC range. Maximum admissible resistance values are given
in the following table:
DC supply
(volts)
Max. admissible resistance
(ohms)
12 150
24 750
32 1050
Signal direction inversion
The TAM transmitter, when supplied with a clockwise closing
actuator, provides a signal that rise from close position to open
position.
If an opposite signal variation is required, simply move 2 jumpers on
the board near the potentiometer:
direct signal: jumpers on 1-3 and 2-4
reversed signal: jumpers on 1-2 and 3-4
10
English
10
How to set TAM
1. Connect a milli-amp meter on terminal block.
2. Always start by adjusting the 4mA.
3. Drive actuator to the position corresponding to the 4 mA
(CLOSED position).
4. Untighten the potentiometer pinion blocking screw. Adjust the
potentiometer shaft so that the output current reaches a
minimum value.
5. Turn backwards until the current value regularly increases
then turn backwards again and stop as soon as the minimum
value determined here above is reached and tighten back the
potentiometer pinion blocking screw.
The potentiometer is then positioned at the very beginning of
its track.
6. Then, use the TAM adjustment screw marked as 0/4mA to
adjust the current to a value as close to the 4 mA as possible.
7. Drive actuator to the position corresponding to the 20 mA
(open position).
8. Turn the screw marked 20mA in order to read exactly 20 mA
on the milli-amp meter.
9. Come back to the closed position and check that, for the 0%
position, the signal current shows a close to 4 mA and
repeatable value.
11
English
11
5.4 Heating element
Each actuator includes a heating resistor.
As soon as the actuator is installed in the field, it is recommended
to power the resistor to prevent condensation.
ensuring its seal is clean.
components without their protection cover.
In case of water intrusion:
Dry electrical components before putting back the cover.
Check electrical insulation.
6 TRAVEL LIMIT SETTINGS
The actuator is factory-set for a 90°travel.
It features 2 devices to limit the travel:
Cams trigger switches to switch off power at an end position or
to signal a position
Mechanical stops mechanically block rotation to protect the valve
in case of over-travel. They must not be used as travel limits.
Single cam setting
The cam rotates with the
output shaft and
triggers a switch by
pushing on its lever.
Cams orientation are factory
pre-set, yet you can still
re-adjust them
during
the commissioning
if necessary.
Rep. Function Status before installation
1
Clockwise travel limit
Pre-wired, cam pre-set
2
Counter-clockwise travel limit
Pre-wired, cam pre-set
3
Clockwise signaling
To wire, to set
4
Counter-clockwise signaling
To wire, to set
12
English
12
How to adjust a single cam
At the desired position of the actuator output:
1) Turn the setting screw of
the corresponding cam
with a flat blade
or a
Phillips screwdriver.
cam disk is then turning.
2) Set the cam disk until you
hear a click from the
switch. It indicates the
trigger of the switch.
Cams and mechanical stops setting
On AQ switch actuators, both cams and mechanical stops can be set.
The actuator stops on open and closed position when the travel limit
switch is tripped.
Travel limit settings
The mechanical stops (1: counter-
clockwise 2: clockwise)
avoid over-travel in case of
handwheel operation.
They can be set on the actuator or
on the gearbox if a gearbox is
fitted on the actuator.
Fine adjustment of the stop
screws position is possible
within a limit of ±
maximum. These screws
are located on the lower side of the actuator.
Take care that cams get to the lever according to its inclination
direction, otherwise you could damage the switch.
If the actuator is supplied mounted on a valve,
following settings should have been performed by the
valve
supplier.
13
English
13
How to adjust cams and mechanical stops for both directions
One turn of the adjustment screw = 4° angle variation at
the actuator output.
Clockwise mechanical stop setting
1. Untighten the nut corresponding to clockwise mechanical
stop and turn the mechanical stop 2 turns back.
2. Drive the actuator to clockwise travel limit position.
3. Get the clockwise mechanical stop in contact with output
sleeve then move it back of 1.5 turns.
4. Retighten nut to keep mechanical stop in position.
Clockwise travel limit switch cam setting
5. Set the cam corresponding to clockwise travel limit switch.
Clockwise signaling switch cam setting (if wired)
6. Drive slightly the output in the counter-clockwise direction
using manual override.
7. Set the cam corresponding to clockwise signaling switch.
Counter-clockwise settings
8. Untighten the nut corresponding to counter-clockwise
mechanical stop and turn the mechanical stop 2 turns back.
9. Drive the actuator to the counter-clockwise travel limit
position.
10. Redo settings steps 3 to 7 for counter-clockwise direction.
Perform complete electrical valve opening and closing operations. It
is mandatory that the motor stops on the travel limit switch and
not on the mechanical stop (check available extra travel to the
stop with handwheel).
14
English
14
7 TORQUE LIMITING DEVICE (AQ25 / 30 / 50 only)
The actuator is protected by a torque limiting device in case of over-
torque.
If the actuator stops in a position which is not the one
desired, please check if actuator did not reach
mechanical stops or that valve has no stiff point.
Actuators are set and tested in factory according to torque stated on
orders. If no torque is specified, the actuator is supplied with
limiter set to the maximum output torque. In both of these
cases, you can adjust torque limiter if necessary.
Torque limiter operation
Please check below torque limiter setting components.
5Clockwise direction
cam
4Clockwise direction
switch
3 – Counter-clockwise
direction cam
2 – Counter-clockwise
direction switch
1Torque scale disk
Torque limiter is triggered as (3) and (5) cams trigger their
corresponding (2) and (4) switches when rotating.
Torque scale disk (1) allows to set torque limit for both directions.
It has torque graduations from 40 to 100% of the maximum
torque deliverable by the actuator.
To adjust torque, set the tip of cam to match the torque
percentage desired on the disk.
Torque scale disk is factory-set and is a reference for cams setting.
Do not modify its position or you will not be able to set the
torque limiter accurately.
15
2
内容
1
2
安全 ---------------------------------------------
包装,存储和维护 ----------------------------------
包装
存放
维护
3
4
5
组装 ----------------------------------------------
更改关位方向指示
紧急手轮操作 --------------------------------------
电气调试 -----------------------------------------
5.1 电气连接和初步测试
5.2 位置反馈电位器(选配)
5.3 TAM 位置变送器(选配)
5.4 加热电阻
6 行程限位设定 --------------------------------------
单个凸轮设置
凸轮和机械限位设置
7 扭矩限位装置( 仅限 AQ25 / 30 / 50 )--------------
17
17
19
20
20
25
28
16
中文
3
1
本装置满足当前适用安全标准。
本装置的安装,维护和使用仅限于接受过培训的专业人员。
在安装和使用本装置之前,请仔细阅读此用户指南。
2 装,
AQ 系列所使用的包装为与执行器同等大小的纸板箱,并装配纸板楔。
AQ 系列不应该存放于开放空间里,避免较大温度差对其造成损害。存
放环境应该为干净和干燥的环境。
避免将执行机构直接放于地面之上。
检查电线入口插头得到适当拧紧。
检查外盖螺丝得到适当拧紧,确保外盖的防水密封。
AQ 执行器包含电气部件和润滑齿轮两大部分。如果执行器存储不得当,
即使在防水外壳的防护下,也会产生氧化等其他变化。
存放后需检查
1. 目视检查所有电气设备。
2. 手动操作微动开关,按钮,选择器等,确保其机械运转正常。
3. 手动操作执行器。
针对已安装但并未调试完成的执行器,需检查
如果从执行器安装到接线需要一段较长时间,则:
1. 目视检查电线入口和外盖是否关闭紧密
2. 在室外安装的情况下,请使用塑料保护膜保护执行器。
当执行器处于潮湿环境中尤其注意接通相应加热设施电(标
准为 230 VAC,除非另有规定)
17
中文
4
装备电子元件的执行器
长时间存放容易造成部件失灵问题。不建议长期存放。
如果必须长期存放,我们强烈建议您在使用执行器之前,将电子板让
我们工厂内部进行一定改善。
作为本执行器的一大特色,它可以实现终身润滑。在执行器所有装置
正确安装和密封的条件下,不需要进行特殊维护。
每年对电机操作进行一次测试,并且确保电气隔室内不会产生凝结积
聚。
若使用环境为极其湿润的环境,本执行器将会装配防冷凝加热器,
避免内部产生凝结积聚
18
中文
5
3
执行器应该通过合适的螺栓或接口直接与阀门相连。
安装完成之后,执行器可在任意位置操作。
但是:
不能通过手轮举起执行器,避免对执行器内部齿轮造成损害
禁止电缆接口面朝上(以防止进水)
方向
标准条件下,AQ 执行器顺时针关闭。若执行器必须逆时针关闭,可以
通过更改位置指示器盖方向来实现。
标准指示器方向
顺时针关闭
反向指示器方向
逆时针关闭
更改位置指示器盖方向
1. 卸下外盖和指示器盖。
2. 90°度转动指示器盖。
3. 重新装上指示器盖和外盖。
19
中文
6
4 急手
AQ 执行器可以通过手轮实现紧急操作,这是本执行器另一大特色。
在进行电气操作过程中,为了避免可能会转动其他突出部件,AQ 执行
器手轮带有可折叠手柄:在电气操作过程中,将其折叠起来,而在需
要对执行器进行手动操作时,则可以展开。
5 气调
5.1 和初
执行器和其部件均与内部的接线端子相连。
在进行接线的时候,打开外盖,将电缆穿过 M20 电缆入口。
请查阅随产品附带的接线图,并参考相应的端子号。
为了避免对执行器或阀门造成任何损害,热保护器和扭矩限位器开关
必须集成于您的控制系统中。
8 - 电容器
7 - 开关板
6 - 扭矩限位器
5 - 电机
4 - 加热电阻
3 - 凸轮
2 - 接线端子
1 - 位置指示器
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Bernard Controls AQ Range SWITCH Installation & Operation Manual

タイプ
Installation & Operation Manual