3 Please read this instruction carefully before use.
3 DOP series Extension Digital I/O Module should be used with DOP-AE series HMI product. Ensure to
switch off the power before wiring.
3 Please install this DOP series Extension Digital I/O Module in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from
operating the device (e.g. key or specific tools are required for opening the enclosure) in case danger
and damage on the device may occur.
3 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may
occur. Check all the wiring again before switching on the power.
3 DO NOT touch any internal circuit in 1 minute after the power is switched off. Do NOT touch any
terminal when the power is switched on.
3 Make sure the ground terminal
is correctly grounded in order to prevent electromagnetic
interference.
3 DO NOT place any heavy objects on the connection port of DOP series Extension Digital I/O Module.
Doing so may damage the product.
X Introduction
1.1 Model Explanation
DOP - EXIO 14 R AE
(1) (2) (3) (4)
(5)
(1) Product Name DOP: Delta Operation Panel
(2) Series EXIO: Extension Digital I/O
(3) Input / Output Point
14: 8 input points / 6 output points
28: 16 input points / 12 output points
(4) Output Contact Type R: Relay
(5) Applicable HMI Series AE: DOP-AE Series HMI
1.2 Product Outline
1. Connection Port
2. Direct Mounting Hole
3. Input / Output Terminals
4. Nameplate
1.3 Model Name
Input / Output
Input Unit Output Unit
Model Name
Power
Point Type Point Type
DOP-EXIO14RAE 8 6 Relay
DOP-EXIO28RAE
5VDC,
supplied
by HMI
16
DC Type
Sink or
Source
12 Relay
Y Function Specifications
Item Specifications Remark
Control Method Stored program, cyclic scan system -
I/O Processing Method Batch I/O (refresh)
Immediate refresh command available
only with I/O of the MPU
Execution Speed Basic command (30 us)
Application command (30 ~ hundreds
us)
Program Language
Commands + Ladder Diagram +
SFC
Step commands included
Program Capacity 999 Steps Built-in EEPROM
Commands
Basic commands: 32 (including the
STL commands)
Application commands: 59
Step Relay
(Latched)
General
Step Point
128 Points S10 ~ S127
General 1280 Points
M0 ~ M511, M768 ~ M999, 744 points;
M1000 ~ M1279, 280 points
*1
Auxiliary
Relay
Latched 256 Points M512 ~ M767
64 Points T0~T63 (100 ms time base)
63 Points T64~T126 (10 ms time base)
Timer Digital
1 Points T127 (1 ms time base)
General 112 Points C0 ~ C111
Latched 16 Points C112 ~ C127
Counter
32bit 13 Points
C235,C236,C237,C238,C241,C242,
C244,C246,C247,C249,C251,C252,
C254 (all of them are latched type)
General 408 Points D0 ~ D407
Data Register
Latched 192 Points D408 ~ D599
Pointer P 64 Points P0 ~ P63
Index
Register
E / F 2 E, F
Decimal K 16bit: -32768 ~ +32767 32bit: -2147483648 ~ +2147483647
Constant
Hexadecim
al H
16bit: 0000 ~ FFFF 32bit: 00000000 ~ FFFFFFFF
Self Diagnosis / Protection
I/O check, system execution timeout check, invalid command check, program
check and password settings
Monitor / Debug Program execution time display, bit / word, device settings
*1: M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the special auxiliary relays (special M).
Z Electrical Specifications
Item / Model Name DOP-EXIO14RAE DOP-EXIO28RAE
Power Supply Voltage 5VDC, 1A (supplied by HMI)
Power Consumption 0.25W 0.5W
Noise Immunity
RS: Frequency: 80MHz ~ 1GHz, 1.4GHz ~ 2.0GHz, Test level 10V/m
CS: Frequency: 0.15MHz ~ 80MHz, Test level 10V (HMI power port & I/O line)
ESD: Air discharge ±8KV
EFT: ±1.5KV (HMI power port)
±1KV (I/O line)
Surge: ±2KV (HMI power port)
Ambient Temperature /
Humidity
Operation: 0°C ~ 50°C (Temperature), 10 ~ 90% (Humidity),
Storage: -40°C ~ 85°C (Temperature), 10 ~ 90% (Humidity)
Vibration / Shock
IEC 61131-2 Compliant
5Hz≦f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz≦f≦150Hz = Continuous: 0.5g / Occasional: 1.0g
X, Y, Z directions for 10 times
Weight Approx. 95.5g Approx. 116g
Input Point Electric Specifications
Input Type DC (SINK or SOURCE)
Input Voltage 24VDC (5mA)
Off→On, above 16VDC
Active Level
On→Off, below 14.4VDC
Response Time Approx. 10ms
Output Point Electric Specifications
Output Type Relay-R
Current Specifications 1.5A / 1 Point (5A/COM)
Voltage Specifications 250VAC, below 30VDC
75VA (Inductive)
Maximum Loading
90 W (Resistive)
Response Time Approx. 10 ms
Mechanical Life 2 × 10
7
times (without load)
Output Point Electric Specifications
Electrical Life
100,000 times (3A 250VAC/30VDC)
6,000 times (5A 250VAC/30VDC)
[ Installation & Wiring
4.1 Wiring
22-16AWG
< 1.5m m
1. Please use the 28-16 AWG (1.5mm
2
) single-core bare wire (Solid type) or
the multi-core wire (Stranded type) for the I/O wiring. The stripped length of
the wire should be 6-7mm, and the torque specification of the screw for the
terminal is 4.5lb-in. Please refer to the specifications of the terminal
shown
in the figure on the left.
2. DO NOT place the I/O signal wires and power supply wire in the same
wiring duct.
4.2 Caution
Environment
1. DO NOT install the Extension Digital I/O Module in a place subjected to corrosive or flammable gases,
liquids, or airborne dust or metallic particles.
2. DO NOT install the Extension Digital I/O Module in a location high temperature and high humidity (where
temperature and humidity will exceed specification).
3. DO NOT install the Extension Digital I/O Module in a location where vibration and shock will exceed
specification.
Wiring Note
1. Please avoid any conductive debris and tiny metal material enter the Extension Digital I/O Module when
screwing and wiring.
2. Allow a minimum space of 50mm between the Extension Digital I/O Module and other control devices, and
keep the Extension Digital I/O Module away from the high-voltage lines or any power equipment.
4.3 Input Point Wiring
There are two types of DC inputs, SINK and SOURCE, and they are defined as follows:
Sink = (common port for current input S/S) Source = (common port for current output S/S)
S/S
X0
Sinking
S/S
X0
Sourcing
Wiring
DC Signal IN
Input point loop equivalent circuit Wiring loop
SINK mode
24VDC
0V
X0
S/S
+24V
SINK
+5V
OV
S/S
X0 X1 X2+24V
Sink Type
24VDC
DC Signal IN
Input point loop equivalent circuit Wiring loop
SOURCE mode
24VDC
0V
X0
S/S
+24V
SOURCE
+5V
0V
S/S
X0 X1 X2+24V
Source Type
24VDC
NOTE
1) The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most
updated version at http://www.delta.com.tw/industrialautomation.
http://www.delta.com.tw/industri alautomation/
Extension Digital I/O Module
Instruction Sheet
Warning
1
2
3
4