EMC
EMC .
.
.
! EMC . EMC
.
. EN 61010 73/23/EEC .
. .
, -30oC ~ +75oC .
. .
. . .
. . .
.
. EMC Directive 89/336/EEC . EN 61326
.
: . 2 .
.
. .
! , )
. BSEN61010 II 2 .
• II (CAT II). 230V 2500V .
• 2. . .
.
. .
: . .
. , 240Vac CATII
.
. .
, IEE (BS7671) NEC Class 1 .
! AC .
. 240Vac .
• , DC ;
• .
(star) 3 . 240Vac
.
. ( ) .
. .
. .
.
.
. .
.
: .
EMC . EMC :
• . EMC
, HA025464 .
• . . .
Schaffner FN321 FN612 .
• . , .
Schaffner FN321 FN612 .
EMC
EMC
! EMC
EMC
EN 61010 73/23/EEC
-30oC +75oC
EMC 89/336/EEC EN 61326
!
BSEN61010 II 2
• II (CAT II)230V 2500V
• 2
240Vac CATII
IEE (BS7671) NEC 1
!
240Vac
•
•
240Vac
EMC EMC
• EMC HA025464
• Schaffner FN321 FN612
• Schaffner
FN321 FN612
Operator Level 2
Parameters are available in deeper levels of access protected by security codes.
Level 2 parameters are typically used when commissioning the controller.
To Select Level 2
1. From any display press and hold until LEv1 is shown
2. Release and press V or W to choose Lev 2 (Level 2)
3. Press V or W to enter the pass code. Default = ‘2
Level 2 Parameters
Press to step through a list of parameters. After 5 seconds the parameter mnemonic is
followed by a scrolling description. Press V or W to adjust the value of the parameter.
Mnemo
nic
Scrolling Text Range. Adjust using V or W
WRK.OP WORKING OUTPUT Active output value. Shown when the controller is in AUTO
or OFF mode. Read only.
WRK.SP WORKING
SETPOINT
Active setpoint value (SP1, SP2, SP3 or REM.SP). Shown when
the controller is in MAN or OFF mode. Read only
UNITS DISPLAY UNITS oC, oF, ok, none, perc (%)
SP.HI SETPOINT HIGH High and low setpoint limit applied to SP1, SP2, SP3 and
Remote Setpoint REM.SP.
SP.LO SETPOINT LOW
SP1/2/3 SETPOINT 1, 2 or 3 Setpoint 1, 2 or 3 adjust. Alterable between SP.HI and SP.LO.
SP.RRT SETPOINT RISING
RATE LIMIT
Sets increasing rate of change
of SP. Alterable: OFF to 3000
units/min.
When set to a value,‘RUN’
illuminates when the
setpoint is changed.
SP.FRT SETPOINT FALLING
RATE LIMIT
Sets decreasing rate of change
of SP. Alterable: OFF to 3000
units/min.
HOLD.B HOLDBACK SX90 only. Stops the setpoint ramp if deviation between SP
and PV > the set value. Range OFF or 1 to 9999.
TM.CFG TIMER
CONFIGURATION
none = no timer configured
SF.St = A soft start timer starts automatically on power up.
It applies a power limit (SS.PWR) until the PV reaches a
threshold value or the timer times out (DWELL). The
threshold value = WKG.SP - SS.SP. It does not operate with
boundless valve position.
Further parameters are shown if soft start is configured. See note 1.
A1/2.xx ALARM 1/2
SETPOINT
(if configured)
xx = HI (high), LO (low), D.HI (deviation high), D.LO
(deviation low), BND (deviation band).
Alterable over the controller range.
MTR.T MOTOR TRAVEL
TIME
Set this to the time taken for the motor to travel from fully
closed to fully open. 0.0 to 999.9 seconds.
A.TUNE AUTO-TUNE
ENABLE
Automatically sets the control parameters to match the
process characteristics. Set to On to start the process.
PB PROPORTIONAL
BAND
1 to 9999 display units
Default: 20.
TI INTEGRAL TIME
1 to 9999 seconds. OFF can be set if control type = PID.
Default: 360.
TD DERIVATIVE TIME OFF, 1 to 9999 seconds. Default:: 60 for PID.
MR MANUAL RESET Not for VP. Otherwise range -100.0 to 100.0%
R2G RELATIVE COOL
GAIN
Adjusts the cooling proportional band relative to the heating
proportional band. Heat/cool only. Range 0.1 to 10.0.
Default 1.0.
D.BAND CHANNEL 2
DEADBAND
Sets a zone between heating and cooling outputs when
neither output is on. Quick Code Function 2 = A only.
Range OFF or 0.1 to 100.0% of the cooling proportional band.
These parameters are further described in manual HA027986.
Note 1: TM.RES, TIMER RESOLUTION; SS.PWR, SOFT START POWER LIMIT; SS.SP, SOFT
START SETPOINT; DWELL, SET TIME DURATION; T.REM, TIME REMAINING.
2
2
2
1. LEv1
2. V W Lev 22
3. V W = ‘2
2
2
2
1. LEv1
2. , V W Lev 2 ( 2)
3. V W . = = ‘2
2
5
V W
V W
WRK.OP AUTOOFF
WRK.SP SP1SP2SP3 REM.SPMAN
OFF
UNITS oCoFok (%)
SP.HI
SP.LO
SP1SP2SP3 REM.SP
SP1/2/3 12 3 12 3 SP.HI SP.LO
SP.RRT SP OFF
3000 /
SP.FRT
SP OFF
3000 /
RUN
HOLD.B SX90 SP PV
OFF 1 9999
TM.CFG none =
SF.St = (SS.PWR)
PV (DWELL) = WKG.SP - SS.SP
1
A1/2.xx 1/2
xx = HILOD.HID.LOBND
MTR.T 0.0 999.9
A.TUNE On
PB 1 9999
20
TI 1 9999 = PID OFF
360
TD OFF1 9999 PID 60
MR VP -100.0 100.0%
R2G 0.1
10.0 1.0
D.BAND 2
2 = A only AOFF 0.1
100.0%
HA027986
1TM.RESSS.PWRSS.SPDWELL
T.REM
2
. 5
. V W .
. V W
WRK.OP WORKING OUTPUT . OFF
. .
WRK.SP WORKING
SETPOINT
(SP1, SP2, SP3 REM.SP).
OFF . .
UNITS DISPLAY UNITS oC, oF, ok, , (%)
SP.HI
SP.LO
SETPOINT HIGH
SETPOINT LOW
SP1, SP2, SP3 REM.SP
.
SP1/2/3 SETPOINT 1, 2 or 3 1, 2 3 . SP.HI SP.LO .
SP.RRT SETPOINT RISING
RATE LIMIT
SP .
: OFF ~ 3000 /.
SP.FRT SETPOINT FALLING
RATE LIMIT
SP .
: OFF ~ 3000 /.
‘RUN’
.
HOLD.B HOLDBACK SX90 . SP PV
. OFF 1 ~ 9999.
TM.CFG TIMER
CONFIGURATION
=
SF.St = .
PV (DWELL)
(SS.PWR) . = WKG.SP - SS.SP.
.
. 1 .
A1/2.xx ALARM 1/2
SETPOINT
(if configured)
xx = HI (), LO (), D.HI ( ), D.LO ( ), BND
().
.
MTR.T MOTOR TRAVEL
TIME
. 0.0 ~ 999.9 .
A.TUNE AUTO-TUNE
ENABLE
.
On .
PB PROPORTIONAL
BAND
1 ~ 9999
: 20.
TI INTEGRAL TIME
1 ~ 9999 . PID OFF .
: 360.
TD DERIVATIVE TIME
OFF, 1 ~ 9999 . : PID 60.
MR MANUAL RESET
VP . -100.0 ~ 100.0%
R2G RELATIVE COOL
GAIN
(heating proportional band)
. / . 0.1 ~ 10.0. 1.0.
D.BAND CHANNEL 2
DEADBAND
. 2 = A . OFF
0.1 ~ 100.0%.
HA027986 .
1: TM.RES = TIMER RESOLUTION; SS.PWR = SOFT START POWER LIMIT; SS.SP = SOFT START
SETPOINT; DWELL = SET TIME DURATION; T.REM = TIME REMAINING.