OPERATION
1. Make BGM signal input from A terminal while EMC signal input from B terminal on the rear panel.
We also can make A, B together with short circuit if there is none of BGM amplifier.
2. Press down any Distributor key to switch on channels which you want.
3. Click All call button with its LED lit and all Switch indicators lit. In this case, all Switching keys
are no use. Click All call button again and its LED gone off, In this case, all Switching keys are use.
4. Pin 1-10 of “ALARM IN”port are live terminals of CH1-CH10 respectively while pin 14-25 are
com. Every channel will be switch to B while alarm signal (short circuit signal) is fed to ALARM IN.
5. An grounded Alarm signal will be send out from“ALARM OUT”while any alarm signal
appears on“ALARM IN”.
SPECIFICATIONS
Channels 10, switch able
Input capacity
70-100V ,10A
Channel capacity
70-100V ,5A/CH
ALM
0/+24V, 0(short circuit)is Valid
Protection AC fuse
Power Requirement AC 220-240V/50-60Hz
Outer Packing Size( mm)
(L×W×H)530×440×195
Unit Size (mm)
(L×W×H)484×365×88
Gross weight 8.3kg
Net weight 6.5kg
Specifications are subject to be changed without notice.
CAUTION
● When the “Power switcher” is off, please pull out the power cord from the socket.
Please keep the equipment out of water.
● To reduce the risk of electric shock, do not remove the cover.
● No user parts inside. Refer servicing to qualified service personnel.
Guangzhou DSPPA Audio Co., Ltd.