Danfoss Liquid level sensor Type AKS 4100 / AKS 4100U - Coaxial D14 version インストールガイド

タイプ
インストールガイド
en
Liquid Level Sensor AKS 4100/4100U - Coaxial D14
zh
位传感 AKS 4100/4100U - 同轴套管式 D14
jp
タイ AKS 4100/4100U - イプ D14
ru
Уровнимер AKS 4100/4100U - КОАКСИАЛ. D14
148R9622
148R9622
Installation Guide
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 1
20 mm /
0.8 in.
Reference point / 参照点 /
基準点 / Начальная точка
50 mm
(2 in.)
36 mm
(1.4 in.)
Danfoss
M84H0030_1
100 N
(23 lbs)
Available lengths:
可选长度:
使用できる長さ:
Доступные длины::
AKS 4100, 500 mm
AKS 4100, 800 mm
AKS 4100, 1000 mm
AKS 4100, 1200 mm
AKS 4100, 1500 mm
AKS 4100, 1700 mm
AKS 4100, 2200 mm
AKS 4100U, 19.2 in.
AKS 4100U, 30 in.
AKS 4100U, 45 in.
AKS 4100U, 55 in.
AKS 4100U, 65 in.
AKS 4100U, 85 in.
Push the wire through
the center hole.
将线缆
插入中间孔
ワイヤ
中央の穴に
し込みます
Пропустите трос через
центральное отверстие.
Danfoss
M84H0023_1
Reference point / 参照点 /
基準点 / Начальная точка
Danfoss
M84H0024_1
Danfoss
M84H0025_1
1 2
3
4 5
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 2
* Values to be entered into HMI Quick Setup menu and recorded on the setting label.
Stick the setting label onto the Signal Converter either inside or outside.
将数值输入到 HMI 快速设置菜单,并在设置标签上标明。
将设置标签粘贴到信号转换器上,内侧或外侧均可。
HMI 高速設置ーに入力設定ラベルに記録する値。
内側か外側の設定ラベルを信号ンバータに付けます
Значения установленные при быстрой настройке уровнемера, необходимо
записать на бирку. Бирку можно разместить как и на преобразователе сигнала,
так и в нутри его.
6
Dielectric Constant εr always set during Quick Setup
速设置时总是要设介电常 εr
誘電率 εr は必ず高速設置中に設ださい
Величина диэлектрической проницаемости (εr) всегда вводится через меню
«Быстрая настройка»
Refrigerant
制冷剂
冷媒
Хладагент
Probe length
探头长
ーブ
Длина измерительной
части
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
[mm] [in.] [mm] [in.]
CO
2
500 19.7
170 6.7
800 31.5
1000 39.4
1200 47.2
1500 59.1
1700 66.9
2200 86.6
Factory setting / 出厂设 / 工場出荷時の設定 / Заводская настройка
Refrigerant
制冷剂
冷媒
Хладагент
Probe length
探头长
ーブ
Длина измерительной
части
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
[mm] [in.] [mm] [in.]
Ammonia
アンニア
Аммиак
500 19.7 95 3.7
800 31.5 104 4.1
1000 39.4 110 4.3
1200 47.2 116 4.6
1500 59.1 125 4.9
1700 66.9 131 5.2
2200 86.6 146 5.8
Improved Bottom dead zone values after the adjustment of dielectric constant
调整介电常数底端死区值有所改善
誘電率調整後の改良された下部デンの値
Оптимизированные величины верхней и нижней мёртвых зон после введения
значения диэлектрической проницаемости
Refrigerant
制冷剂
冷媒
Хладагент
Probe length
探头长
ーブ
Длина измерительной
части
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
[mm] [in.] [mm] [in.]
Ammonia
アンニア
Аммиак
500 19.7
80 3.2
800 31.5
1000 39.4
1200 47.2
1500 59.1
1700 66.9
2200 86.6
Please note: It is mandatory to input dielectric constant for CO
2
applications.
请注意:对于 CO
2
应用,必须输入介电常数。
注意い:CO
2
使用す場合には誘電率の入力が必須です
Внимание: при использовании с CO
2
обезательно необходимо установить значение εr.
B: 120 mm (4.7 in.)
H: (see tables)
Min: 30 mm (1.2 in.)
I: Ø2 mm (0.08 in.)
4 mA (0 %)*
Danfoss
M84H0072_1
20 mA
(100 %)*
A
G
C
D*
E
F
Factory setting / 出厂设 / 工場出荷時の設定 / Заводская настройка
Refrigerant
制冷剂
冷媒
Хладагент
Probe length
探头长
ーブ
Длина измерительной
части
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
[mm] [in.] [mm] [in.]
HCFC,HFC
500 19.7 115 4.5
800 31.5 124 4.9
1000 39.4 130 5.1
1200 47.2 136 5.4
1500 59.1 145 5.7
1700 66.9 151 5.9
2200 86.6 166 6.5
Improved Bottom dead zone values after the adjustment of dielectric constant
调整介电常数底端死区值有所改善
誘電率調整後の改良された下部デンの値
Оптимизированные величины верхней и нижней мёртвых зон после введения
значения диэлектрической проницаемости
Refrigerant
制冷剂
冷媒
Хладагент
Probe length
探头长
ーブ
Длина измерительной
части
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
Bottom Dead Zone
底端死区
下 部 ーン
Нижняя мертвая зона
[mm] [in.] [mm] [in.]
HCFC,HFC
500 19.7
100 3.9
800 31.5
1000 39.4
1200 47.2
1500 59.1
1700 66.9
2200 86.6
en zh
jp
ru
A Reference
point
参照点
準点
B Top dead
zone
顶端死区
ッド
ーン
C Measuring
range
测量范围
計測範囲
D Probe
length
探头长度
ーブ
E Distance 距离
距離
F Inner length
of stand-
pipe
立管内部
长度
直立管の内
長さ
G Surface
level
液位 面レ
H Buttom
dead zone
(see tables)
底端死区
(参见)
ッド
ン (表を
参照
I Steel wire
insertion
length
钢线插入
长度
挿入
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 3
Cover stop. 2.5 mm / 0.2 in. Allen Key.
盖挡. 2.5 mm / 0.2 in. 内六角
カバー止め 2.5 mm / 0.2 インチ六角レン
Фиксатор крышки ключ на 2.5 мм/
0.2 дюйма.
Connector for HMI
HMI 连接头
HMI 用コ ネ
Подсоединение HMI
Loosen cover stop
松开盖挡
カバー止めを緩めます
Фиксатор крышки
Danfoss
M84H0010_1
AKS 41/41U with a.c supply to
AKS 4100/4100U with d.c supply.
AKS 41/41U(交流电源)至
AKS 4100/4100U(直流电源)
AC 電源付き AKS 41/41U か DC 電源付き
AKS 4100/4100U へ
Замена AKS 41 на AKS 4100
AKS 41/41U перененный ток на
AKS 4100/4100U постоянный ток
7
9
8
Danf
oss
M84H0010_1
10
①②
④①
Danfoss EKC 347
or PLC
24 V a.c (L)
24 V a.c (N)
(+)
AKS 41/41U
(–)
4-20 mA
Danfoss EKC 347
or PLC
24 V d.c (+)
24 V d.c (–)
AKS 4100/4100U
+
Danfoss
M84H0027_1
Unscrew
拧开
ねじ
Отвинтите
Screw
ねじ
Закрутите
Screw
ねじ
Закрутите
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 4
AKS 4100/4100U connected to EKC 347
AKS 4100/4100U 连接到 EKC 347
EKC 347 に接続た AKS 4100/4100U
AKS 4100 подсоединение к EKC 347
24 V DC from ICAD can also be used /
ICAD
24 V d.c
/
ICAD からの 24 V d.c 使 用 で き ま す / Может использовать питание 24 в пост. тока от ICAD
2. yellow / / 黄色 / желтый
1. grey / 灰色 / グレ / серый
green / 绿色 / /зеленый
brown / 棕色 / / коричневый
orange / / オレン / оранжевый
yellow / / 黄色 / желтый
brown / 棕色 / / коричневый
white / / / белый
E.g./ 例如/ например
ICM/ICAD valve Feedback position
ICM / ICAD 阀反馈
ICM/ICAD バル位置
ICM/ICAD определение позиции клапана
AKS 4100/4100U connected to PLC
AKS 4100/4100U 连接到 PLC
AKS 4100/4100U PLC に接続
AKS 4100 подсоединение к PLC
+
AKS 4100/4100U
+
Danfoss
M84H0074_1
PLC
Active analog input 4 – 20 mA / 14 – 30 V DC
4-20 mA
14-30 V d.c.
クテブ アナログ入力 420 mA 1430 V DC
Активный аналоговый выход 4 – 20 мА 14-30 В пост. тока
11
12
EKC 347 5 VA
AKVA coil 20W 55 VA
AKS 4100/4100U
14-30 V d.c.
+
(+)
(–)
Danfoss
M84H0073_2
ICAD 1
st
generation (pre2010)
ICAD 2
nd
generation (2010+)
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 5
Enter menu system
Enter QUICK SETUP
Unit change at
distance/level
readout:
m, cm, mm, in, ft
Change between:
Distance*
Level**
Output (%)***
Output (mA)****
4 – 20 mA output displayed as bar graph
and in percentage [%]
Measurement name (in this example, DISTANCE)
Device tag name
Measurement reading and unit
Device status (markers)
Marker 1, 2 and 3 (Error)
Hardware problem; the Signal Converter hardware is
defective. Contact Danfoss.
Marker 4 and 5 (Notication)
Depending on the level, the marker is ON or OFF.
Used for Danfoss service information only.
Keypad buttons
Flashing star indicating unit in operation.
* DISTANCE is a display option.
If the display is set to “DISTANCE” the displayed value will
be the distance from the Reference point to the top
surface of the liquid refrigerant (see g. 5).
** LEVEL is display option.
If the display is set to “LEVEL then the value displayed
will be:
PROBE LENGTH (entered in QUICK SETUP)
– DISTANCE (see g. 5).
*** OUTPUT (%) is display option.
Will represent the level of refrigerant,in percent, scaled
(entered in QUICK SETUP) according to: SCALE 4 mA
(0%), SCALE 20 mA (100%) (see g. 5).
**** OUTPUT I (mA) is display option.
Will represent the level of refrigerant,in 4-20
milliampere, scaled (entered in QUICK SETUP)
according to: SCALE 4 mA (4 mA), SCALE 20 mA
(20 mA) (see g. 5).
*
AKS 4100
*
AKS 4100
13
13
DISTANCE
距离
进入Menue system (菜单系统)
进入 QUICK SETUP (快速设置)
单位随距离/液位
读数而变化:
m、cm、mm、in、ft
切换选项:
Distance(距离) *
Level(液位)液位**
Output(输出)(%)***
Output(输出)(mA)****
① 4 – 20 mA 输出(以柱状图和百分比[%]显示)
② 测量值名称(本例中为距离)
③ 设备名称
④ 测量读数和单位
⑤ 设备状态(标记)
标记1、2和3(错误)
硬件问题;信号转换器硬件有缺陷。请联系丹佛斯。
标记4和5(通知)
根据不同的液位,标记为开或关。只用于丹佛斯
务信息。
⑥ 按键
⑦ 闪烁的星星,表示设备正在工作。
* “Distance(距离)”是一个显示选项。
若将显示设为“Distance”,则显示的值是参照点至
制冷剂液面顶部的距离(参考图 6)。
** “Level(液位)”是一个显示选项。
若将显示设为“Level”,则显示的值为:
探头长度(在快速设置中输入) 距离(参考图 6
)。
*** “Output(输出)(%)”是一个显示选项。
将以百分比形式显示制冷剂的液位,根据下列条件确
定标度(在快速设置中输入):
SCALE 4 mA(0%),SCALE 20 mA(100%)参考图6)。
**** “Output(输出)(mA)”是一个显示
选项。
将以 4-20 毫安显示制冷剂的液位,根据下列条件确
定标度(在快速设置中输入):
SCALE 4 mA(4 mA),SCALE 20 mA
(20 mA)(参考图 6)。
en
zh
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 6
*
AKS 4100
13
13
距離
jp
4 – 20 mA 出力をバーグラパーセ
[%] で表示
計測名 (の例では「距離)
装置グ名
計測読み値単位
装置ステース (数値)
数値 1、2、3 (ー)
ハ ーの問題; 信号変換器 ハーアが故障。
Danfoss にご連絡ださい。
数値 4 おび 5 (通知)
レベルに応て数値がたはオフになます
Danfoss のサース情報てのみ使用ます
キーパッド ボタ
点滅する星印は装置が動作中であを示
* 「距離」は表示オプシンです
表示が
距離
に設定さる場合、表示
る値は基準
点か液体冷媒の上面での距離になます (図 6 を参
照)。
** 「LEVEL ”レベル”」は表示オプシです
表示が「LEVEL ベル”」に設定ている場合には、
表示さ値は以下のになます:プロブ長 (高
設置で入力) 距離 (図 5 を参照)
***「OUTPUT (%) “出力(%)”」は表示オプシです 冷媒
レベルを (プで入力た)
下のケールを基準したパーセ単位で表示す:
4mA位置 (0%)、 20mA位置 (100%) (図 5 を参照)。
****OUTPUT I (mA) “出力 (mA)”」は表示オプシです
媒のレベルを (プで入力た)
以下のールを基準 4~20m A の範囲で表
す:4mA位置 (4 mA)、 20mA位置 (20 mA) (図 5
を参照)。
ニュ シス
クイクセットアッ
に移動
距離/レベル読み値
の単位変更:
m、cm、mm、
、フ
以下のいずれかに変更:
距離*
レベル*
出力 (%)***
出力 (mA)****
Выходной сигнал 4 – 20 мА отображается на дисплее
в виде графической шкалы и виде процентов (%).
Наименование измеряемого параметра
(в данном примере это расстояние).
Модель уровнимера.
Единицы измерения.
Состояние прибора (в виде цифр):
Цифры 1, 2 и 3 (Ошибка)
Проблема с оборудованием; Отсутствие сигнала;
Низкое напряжение. Обратитесь в Danfoss.
Цыфры 4 и 5 (Уведомления)
В зависимости от значения уровня.
Кнопки панели управления
Мигающая звёздочка, показывает, что
прибор работает.
* РАССТОЯНИЕ.
В случае отображения на дисплее параметра
“РАССТОЯНИЕ”, измеряемой величиной будет являться
расстояние между нулевой точкой и поверхностью
жидкого холодильного агента (см. Рис. 5).
** УРОВЕНЬ.
В случае отображения на дисплее параметра
“УРОВЕНЬ, измеряемой величиной будет являться
разница значений “ДЛИНА ТРОСА” (вводится при
“БЫСТРОЙ НАСТРОЙКЕ”) – РАССТОЯНИЕ (см. Рис. 5).
*** Выходной сигнал (%).
Указываетпроцент заполнения сосуда холодильным
агентом в зависимости от значения:
Точки 4 мА (0%) и Точки 20 мА (100%)
(см. Рис. 5) (указываются при “БЫСТРОЙ
НАСТРОЙКЕ”).
**** Выходной сигнал (мА).
Указывает уровень холодильного агента в сосуде, в
соответствии с диапозоном
4 – 20 мА, в зависимости от значения:
Точки 4 мА (0%) и Точки 20 мА (100%)
(см. Рис. 5) (указываются при “БЫСТРОЙ
НАСТРОЙКЕ”).
*
AKS 4100
Дистанция
Вход в меню системы.
Запуск режима «Быст-
рая настройка».
Изменение единиц
измерения для
отображения рас-
стояния/ уровня:
м, см, мм, дюймы,
футы.
Переключение между:
Расстояние*
Уровень**
Выходной сигнал (%)***
Выходной сигнал (мА)****
ru
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 7
Please observe that AKS 4100/4100U is
intended to always be* installed in a
standpipe (column/bypass/stilling well).
A standpipe is commonly used when:
Servicing the AKS 4100/4100U
There is highly conductive foam in the tank.
The liquid is very turbulent or agitated.
AKS 4100/4100U Coaxial with or without
HMI does not need any change of setting to
operate, unless used in CO
2
.
Presetting:
4 mA : Probe length - 100 mm (4 in.)
20 mA: 120 mm (5 in.)
Refrigerants
AKS 4100/4100U is designed specically to
measure liquid level in the most commonly
used refrigerants, including R744 (CO
2
),
R717(ammonia), HCFC, HFC and non corrosive
gases/liquids.
Basic data
AKS 4100/4100U is a passive 2-wire 4 – 20 mA
sensor that is loop powered.
Supply Voltage
14 – 30 V DC min/max. value for a max. output of
22 mA at the terminal
Load
RL [Ω] ≤ ((Uext -14 V)/20 mA).
– Default (Error output set to 3.6 mA)
RL [Ω] ≤ ((Uext -14 V)/22 mA).
– (Error output set to 22 mA)
Cable gland
AKS 4100 PG 13, M20×1.5 ;
(cable diameter:
6-8 mm (0.24-0.31in.)
AKS 4100U ½ in. NPT
Terminals (spring loaded)
0.5-1.5 mm
2
(~20-15 AWG)
Enclosure
IP 67 (~NEMA type 4X)
Refrigerant temperature
-60 – 100 °C / -76 – 212 °F
Refrigerants
The listed refrigerants are qualied and approved
by Danfoss:
R717 / NH
3
: -40 – 50 °C / -40 – 122 °F
R744 / CO
2
: -50 – 15 °C / -58 – 59 °F
HCFC:
R22: -50 – 48 °C / -58 – 118 °F
HFC:
R404A: -50 – 15 °C / -58 – 59 °F
R410A: -50 – 15 °C / -58 – 59 °F
R134A -40 – 50 °C / -40 – 122 °F
Ambient temperature
-40 – 80 °C / -40 – 175 °F
For HMI : -20 – 60 °C / -4 – 140 °F
Process pressure
-1 – 100 barg / -14.5 – 1450 psig
Mechanical process connection with 5 m / 197 in.
Ø2 mm / 0.08 in. stainless cable:
AKS 4100 G1 inch pipe thread.
Aluminium gasket included
AKS 4100U ¾ in. NPT
(Further details in the Technical Brochure)
Mechanical Installation
Preparations prior to Mechanical Installation
Disassemble the Signal Converter from the
Mechanical process connection (use 5´mm hex
key, see g. 7). Fit the red protection cover on
top of the Mechanical process connection to
protect it againt any moisture or dirt paticles.
Content supplied (g 1)
 Signal Converter (with or without HMI)
 Mechanical process connection with
5 m / 197 in. Ø2 mm / 0.08 in. stainless wire
 Tube(s)
 Bag with:
End Connector (incl. 3 mm set screws.)
3 mm set crews (1 set screw pr. tube)
Red cover to protect Mechanical process
connection , before Signal converter is
mounted
Setting label.
Assembly of the segmented coaxial probe
Please observe that the stainless
steel wire is not permanently creased
or kinked.
1. Take the end of the stainless wire and feed it
through the center hole of the plastic spacer
located at the top of each tube (see g. 2).
Feed the entire length of the stainless wire
through the tube and out at the bottom. If
more than one tube; repeat the steps.
2. Assemble the segments of tube and
(see g. 3). Use a 17 mm open-end
wrench to tighten the assembled parts.
3. If more than one tube; repeat the steps
(see g. 3).
4. Prior to assemble, disassemble signal
converter and mechanical process connection,
and t red protection cap at mechanical
process connection. Thread the fully
assembled tube onto the mechanical process
connection .
5. Lock each tube by tightening the set screw
with a 3 mm hex key (see g. 3).
6. Pull the stainless wire through the end
connector (see g.4).
7. Attach the end connector to the bottom
of the fully assembled tube.
Tighten the set screw with a 3 mm hex key
(see g. 4).
8. Pull the end of the stainless steel wire
extending from the end connector with
pliers (see g. 4) to ensure that the tension in
the signal cable is correct. Tighten the 2 set
screws with a 3 mm hex key to lock the
stainless wire.
9. Cut the stainless wire about 20 mm / 0.8 in.
below the end connector (see g. 5).
10. Measure the probe length (without the signal
converter) before tting the assembled probe
in the standpipe (see g. 6).
Use a torque wrench to tighten the
mechanical process connection
(g. 1, item 2) to 120 Nm (89 lb/ft).
If factory setting needs adjustment
Probe length, scale 4 mA and 20 mA for HMI
Quick Setup.
Probe length:
See probe length on Danfoss product label or
measure probe length (see g. 6).
Scale 4 mA: (for max. measuring range)
= Probe Length
Bottom dead zone (see g. 6)
Scale 20 mA:(for max. measuring range:)
= Top dead zone (see g. 6)
Example (AKS 4100)
Given conditions:
Probe length: 1200 mm
Refrigerant: CO
2
, –35°C
The gas constant Er is always adjusted from
the Quick Setup
Probe length:
= 1200 mm
SCALE 4 mA setting for max. measuring range:
= Probe length (1200 mm)
Bottom dead zone (see g. 6)
(170 mm) = 1030 mm (40.9 in.)
SCALE 20 mA Setting for Max. Measuring
range:
= Top dead zone (see g. 6)
= 120 mm / 4.7 in.
From page 11:
Dielectric constant of refrigerant gas
parameter 2.5.3 GAS EPS.R
= 1.02
How to mount the AKS 4100/4100U Converter
(see g 7)
1. Unscrew the set and ventilation screws with a
5 mm Hexagon key in the Signal converter.
2. Push the Signal Converter downwards to stop
on the Mechanical process connection
3. Turn the Signal Converter to the wanted
position.
4. Screw the set screw with a 5 mm Hexagon key.
5. Screw the ventilation screw with a 5 mm
Hexagon key.
Electrical installation/connection
Output terminals (g. 8 and 9):
1. Current output –
2. Current output +
3. Grounding terminal
Electrical installation procedure
1. Use a 2.5 mm Allen wrench to loosen the
cover stop.
2. Remove the terminal compartment cover
from the housing.
3. Do not disconnect the wire from the
terminal compartment cover.
Put the terminal compartment cover
adjacent to the housing.
4. Connect the wires to the device.
Tighten the cable entry glands.
5. Attach the terminal compartment cover
to the housing.
6. Use a 2.5 mm Allen wrench to tighten the
cover stop.
Note:
The signal converter can be programmed
with or without mechanical process connector
assembled.
Start up:
Connect the converter to the power supply.
Energize the converter.
Devices with the HMI display option only:
After 10 seconds the screen will display "Starting
up". After 20 seconds the screen will display the
software version numbers. After 30 seconds the
default screen (g. 13) will appear.
Precausions when changing from
AKS 41/41U to the AKS 4100/4100U:
Please note:
The AKS 41/41U can be used with AC and DC
supply, but the AKS 4100/4100U can only be
used with a DC supply. Follow the instructions
in g. 10.
Connecting to controller or PLC
Follow the instructions in g. 11 or 12.
Note:
The current output will be set to 3.6 mA
whenever the AKS 4100/4100 detects an
error like Marker 1, 2 or 3 (see page 5).
Quick Setup
ENGLISH
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 8
Connect the device to the power supply
(see the section "Electrical installation/
connection").
Press 3 times.
Press
Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D14 and press to conrm.
Press (YES) to conrm
Press to change GAS EPS.R.
(Select the correct value from the tables
on page 8)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Wait for QUICK SETUP to complete.
Count down from 8 sec.
Press to conrm.
Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
You have the possibility of checking
your settings by pressing
twice.
Press
to return to
default screen.
Quick Setup (all values below are only examples)
When CO
2
is used:
Note:
The signal converter can be programmed with or without mechanical process connector assembled.
AKS 4100
QUICK SETUP?
YES NO
AKS 4100
PROBETYPE
SINGLECABLE
AKS 4100
LIQUID CO
2
?
YES NO
AKS 4100
GAS EPS R?
001.000
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4mA
04946 mm
AKS 4100
SCALE 20mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
COAXIAL D14 2200 mm
(0%) 4 mA 1900 mm
(100%) 20 mA 70 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 9
Connect the device to the power supply
(see the section "Electrical installation/
connection").
Press 3 times.
Press
Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D14 and press to conrm.
Press
(NO) to conrm
Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Wait for QUICK SETUP to complete.
Count down from 8 sec.
Press to conrm.
Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
For all other refrigerants:
AKS 4100
QUICK SETUP?
YES NO
AKS 4100
PROBETYPE
SINGLECABLE
AKS 4100
LIQUID CO
2
?
YES NO
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4mA
04946 mm
AKS 4100
SCALE 20mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 10
Default screen
Press
Press
Press
Enter password:
Press
Press
Press
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press 4 times to return to default
screen.
Default screen appears:
Force mA completed and disabled
How to force mA output (all values below are only examples)
Default screen
Press
Press
Press
Enter password:
Press 4 times.
Press
Press 2 times.
Press to check/change GAS EPS.R.
(Select the correct value from the tables
below and on page 8)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press 3 times.
Press
or
to select between
STORE NO or STORE YES.
Select STORE YES by pressing
Default screen appears:
Entering the dielectric constant of
refrigerant gas completed
How to enter dielectric constant of refrigerant gas (all values below are only examples)
Optional Procedure
If the temperature condition in the stand pipe is known, a constant (dielectric constant of the refrigerant gas) can be entered
(parameter 2.5.3 GAS EPS.R), in order to obtain lower Top and Bottom Dead Zone values (see g. 6).
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.2.0
TESTS
AKS 4100
2.2.1
SET OUTPUT
AKS 4100
SET OUTPUT
3.5 mA
AKS 4100
SET OUTPUT
8 mA
AKS 4100
DISTANCE
5000 mm
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.5.0
APPLICATION
AKS 4100
2.5.1
TRACING VEL.
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
GAS EPS. R
1.066
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 11
Saturated vapour dielectric constant (default value: 1.066)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -42 -76 – -43 1.00
-41 – -18 42 – 0 1.01
-17 – -5 1 – 23 1.02
-4 – 4 24 – 39 1.03
5 – 12 40 – 54 1.04
13 – 18 55 – 64 1.05
19 – 24 65 – 75 1.06
25 – 28 76 – 82 1.07
29 – 33 83 – 91 1.08
34 – 37 92 – 99 1.09
38 – 40 100 – 104 1.10
41 – 44 105 – 111 1.11
45 – 47 112 – 117 1.12
48 – 50 118 – 122 1.13
R717 (NH
3
)
Temperature range:
-60 – 50 °C / -76 – 122 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-56.0 – -42.0 -69 – -43 1.01
-41.0 – -28.0 -42 – -18 1.02
-27.0 – -17.0 -17 – 2 1.03
-16.0 – -9.0 3 – 16 1.04
-8.0 – -3.0 17 – 27 1.05
-2.0 – 2 28 – 36 1.06
3 – 7 37 – 45 1.07
8 – 11 46 – 52 1.08
12 – 14 53 – 58 1.09
15 59 1.10
R744 (CO
2
)
Temperature range:
-56 – 15 °C / -69 – 59 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -50 -76 – -58 1.00
-49 – -25 57 – -13 1.01
-24 – -10 -12 – 14 1.02
-9 – 0 15 – 32 1.03
1 – 8 33 – 46 1.04
9 – 15 47 – 59 1.05
16 – 21 60 – 70 1.06
22 – 26 71 – 79 1.07
27 – 31 80 – 88 1.08
32 – 35 89 – 95 1.09
36 – 39 96 – 102 1.10
40 – 42 103 – 108 1.11
43 – 45 109 – 113 1.12
46 – 48 114 – 118 1.13
R22
Temperature range:
-60 – 48 °C / -76 – 118 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -42 -76 – -43 1.00
-41 – -18 -42 – -0 1.01
-17 – -4 1 – 25 1.02
-3 – 5 26 – 41 1.03
6 – 13 42 – 56 1.04
14 – 20 57 – 68 1.05
21 – 25 69 – 77 1.06
26 – 30 78 – 86 1.07
31 – 34 87 – 94 1.08
35 – 38 95 – 100 1.09
39 – 42 101 – 108 1.10
43 – 45 109 – 113 1.11
46 – 48 114 – 119 1.12
49 – 50 120 – 122 1.13
R134a
Temperature range:
-60 – 50 °C / -76 – 122 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -47 -76 – -52 1.01
-46 – -35 -51 – -31 1.02
-34 – -26 -30 – -14 1.03
-25 – -19 -13 – -2 1.04
-18 – -14 -1 – 7 1.05
-13 – -9 8 – 16 1.06
-8 – -4 17 – 25 1.07
-3 – 0 26 – 32 1.08
1 – 3 33 – 38 1.09
4 – 6 39 – 43 1.10
7 – 9 44 – 49 1.11
10 – 12 50 – 54 1.12
13 – 15 55 – 59 1.13
R404A
Temperature range:
-60 – 15 °C / -76 – 59 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-65 – -47 -85 – -52 1.01
-46 – -35 -51 – -31 1.02
-34 – -26 -30 – -14 1.03
-25 – -19 -13 – -2 1.04
-18 – -13 -1 – 9 1.05
-12 – -8 10 – 18 1.06
-7 – -4 19 – 25 1.07
-3 – 0 26 – 32 1.08
1 – 4 33 – 40 1.09
5 – 7 41 – 45 1.10
8 – 10 46 – 50 1.11
11 – 12 51 – 54 1.12
13 – 15 55 – 59 1.13
R410A
Temperature range:
-65 – 15 °C / -85 – 59 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -48 -76 – -54 1.01
-47 – -36 -53 – -32 1.02
-35 – -28 -31 – -18 1.03
-27 – -21 -17 – -6 1.04
-20 – -15 -17 – -5 1.05
-14 – -10 -4 – 14 1.06
-9 – -6 13 – 22 1.07
-5 – -2 23 – 29 1.08
-1 – 2 30 – 36 1.09
3 – 5 37 – 41 1.10
6 – 8 42 – 47 1.11
9 – 11 48 – 52 1.12
12 – 13 53 – 56 1.13
14 – 15 57 – 59 1.14
R507
Temperature range:
-60 – 15 °C / -76 – 59 °F
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 12
Default screen
Press
Press
Press
Enter password:
Press
6 times
Press
Press
Press
or
to see the language
possibilities
Press to conrm.
Press 3 times
Press
or
to select between
STORE NO or STORE YES.
Select STORE YES by pressing
Default screen appears:
Language setup completed
How to change the language setting (Default: English)
Go to SUPERVISOR menu (see page 7).
Go to parameter 2.9.4 Reset Factory.
Select RESET FACTORY YES
Press 3 times to return to default screen.
Factory reset completed.
Reset to factory setting
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.7.0
DISPLAY
AKS 4100
2.7.1
LANGUAGE
AKS 4100
LANGUAGE
ENGLISH
AKS 4100
2.7.1
LANGUAGE
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 13
请注意,AKS 4100/4100U 总是*安装在
立管内。立管通常应用于下列情况:
• 检修 AKS 4100/4100U
• 罐体内存在高导热的泡沫
• 液体呈现湍流和翻腾状态
制冷剂
AKS 4100/4100U 专用于测量最常用制冷剂的
液位,包括二氧化碳、氨、HCFC、HFC 和非腐
蚀性气体/液体。
基本参数
AKS 4100/4100U 是一款回路供电的无源二线制
4 – 20 mA 传感器。
供电电压
14 – 30 V DC最小/最大值
端子最大输出为22 mA
负载
RL [Ω] ≤((Uext -14 V)/20 mA)
– 默认(差错输出设为 3.6 mA)
RL [Ω] ≤((Uext -14 V)/22 mA)
– 默认(差错输出设为 22 mA)
电缆封套
AKS 4100 PG 13, M20×1.5;
(电缆直径:6-8 mm(0.24-0.31in.)
AKS 4100U ¾ in. NPT
接线端子(弹簧承载)
0.5-1.5 mm
2
(~20-15 AWG)
防护等级
IP 67(~NEMA 4X )
制冷剂温度
-60 – 100 °C / -76 – 212 °F
制冷剂
丹佛斯认可适用的制冷剂:
R717 / NH
3
: -40 – 50 °C / -40 – 122 °F
R744 / CO
2
: -50 – 15 °C / -58 – 59 °F
HCFC:
R22: -50 – 48 °C / -58 – 118 °F
HFC:
R404A: -50 – 15 °C / -58 – 59 °F
R410A: -50 – 15 °C / -58 – 59 °F
R134A -40 – 50 °C / -40 – 122 °F
环境温度
-40 – 80 °C / -40 – 175 °F
HMI:-20 – 60 °C / -4 – 140 °F
操作压力
-1 – 100 barg / -14.5 – 1450 psig
用长 5 m(197 in.) Ø2 mm / 0.08 in.的不锈
钢线缆进行机械连接:
AKS 4100 1" G 管罗纹。包括铝制垫片
AKS 4100U ¾ in. NPT
(详情请参阅《技术手册》)
机械安装
机械安装前的准备
从机械连接件上卸下信号转换器(用 5' m m
角扳手,参阅图7)。将红色保护盖安装到机械
连接件的顶部,使之免受潮气或污垢的影响。
装箱清单(图1)
① 信号转换器(带/不带 HMI)
② 机械连接件,带 5 m(197 in.)
Ø2 mm(0.08 in.)不锈钢线
③ 同轴管道
④ 附件包:
终端连接器(包括 3mm 螺丝组)
3 mm 螺丝(每根管道螺丝)
安装信号转换器前用于保护机械连接件
的红色保护盖
组装分段的同轴套管
请确保不锈钢线缆没有出现永久性折痕
或永久性的扭结。
1. 手持不锈钢线末端,将它穿过每根管道顶部
的塑料垫片的中心孔(图2)。让整条不锈钢
线缆穿过管道并伸出管道底端。若管道不止
一根,请重复上述步骤。
2. 组装管道① ②(图3)。使用17 mm 开口
扳手拧紧装好的部件。
3. 若管道不止一根,请重复上述步骤(图3)。
4. 组装之前,先拆下信号转换器和机械连
件,并将红色保护盖装在机械连接件上
将完全组装好的管道装到机械连接件 上。
5. 用 3mm 六角扳手拧紧固定螺钉 ④,以锁紧
每一管段(图3)。
6.将不锈钢线缆拉出终端连接器(图4)。
7.将终端连接器紧贴组装好的管道底端。
用3mm 角扳手拧紧螺钉(图4)。
8.用钳子拉紧不锈钢线缆(图4),确保信号线
缆的张力正确。
3 mm 六角扳手拧紧2颗螺钉,以锁定不锈
钢线缆。
9. 从终端连接器外约 20 mm(0.8 in.)剪断不锈
钢线缆(图5)。
10.将探测器安装到立管之前,先测量探测器长
度(无信号转换器)(图6)。
用扭力扳手拧紧连接件(图1,第2条),力矩
值为 120 Nm(89 lb/ft)。
标定探测器长度,针对 HMI 快速设置标定 4
mA 和 20 mA:
探测器长度
参阅丹佛斯产品标签上的探头长度,或者测量
探头长度(图6)。
标定 4 mA :(最大测量范围)
= 传感器长度
– 底部死区(图6)
标定 20 mA :(最大测量范围)
= 顶部死区(图6)
示例(AKS 4100)
给定条件:
探测器长度:1200 mm
制冷剂:CO
2
, –35℃
在快速设置中调整气体常数 Er
探头长度:
= 1200 mm
标定 4 mA 设置(最大测量范围):
= 探测器长度(1200 mm)
–底部死区(参阅图6)
(170 mm)= 1030 mm (40.9 in.)
标定 20 mA 设置(最大测量范围):
= 顶部死区(参阅图6)
= 120 mm(4.7 in.)
第17页:
制冷剂气体的介电常数 2.5.3 GAS EPS.R
= 1.02
如何安装 AKS 4100/4100U 转换器(图7)
1. 使用信号转换器里面的 5mm 内六角扳手拧开
固定螺栓与通风螺栓。
2.向下推动信号转换器,直至它停在机械连接件
上。
3. 转动信号转换器至想要的位置。
4. 用 5 mm 内六角扳手拧紧固定螺栓。
5. 用 5 mm 内六角扳手拧紧通风螺栓。
电气安装/连接
输出端子(图 8和 图 9):
1.电流输出 –
2.电流输出 +
3.接地端子
电气安装步骤
1. 2.5 mm 内六角扳手松开顶盖。
2. 从壳体上取下端子舱盖。
3. 不要从端子舱盖上卸下电缆。将端子舱盖近壳
体放置。
4. 将钢缆连接到设备。上紧线缆入口封套。
5. 将端子舱盖安装到机壳上。
6. 2.5 mm 内六角扳手拧紧顶盖。
注意:
无论是否具有机械连接件,信号转换器都可以
进行参数设置。
启动
• 将转换器连接到电源。
• 将转换器通电。
若设备带选配的 HMI 显示屏,则仅在:
10秒后屏幕将显示“启动”。20秒后屏幕将显
示软件版本号。30秒后显示默认屏幕(图13)。
AKS 41/41U 改为 AKS 4100/4100U 时需要注意。
注意:
AKS 41/41U 支持交流和直流电源,而 AKS
4100/4100U 只能使用直流电源。按照图10的说
明进行操作。
连接到控制器或 PLC
按照图11或12的说明进行操作。
注意:
AKS 4100/4100 检测到错误,电
流输出就会被设为 3.6 mA,设备
状态将标记为 1、2、3。
中文
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 14
将设备连接到电源(参阅“电气安装/连
接”一节)。
连按 3 次。
• 按下
按下 ,,在SINGLE(电缆形
式), COAXIAL (同轴形式)D14或
COAXIAL (同轴形式)D22之间选择一项。
按下 以示确认。
• 按下 (YES)以示确认
• 按下 更改GAS EPS.R.
(从第8页的表格中选择正确的数值)
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
按下 更改探头长度。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
按下 更改标度 4 mA。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
按下 更改标度 20 mA。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
等待快速设置完成。倒数8秒
按下 以示确认。
按下 ,在 STORE NO (保存
否) 和 STORE YES (保存 是)
之间进行选择。按下 以示确认。
显示默认屏幕:
快速设置完成
您可以连按两次 ,以便对设置进行检查。
按下 ,返回默认屏幕。
快速设置(下面所有数值均为举例)
应用:二氧化碳:
注意:
无论是否装有机械连接件,均可对信号转换器进行编程。
AKS 4100
快速设置?
AKS 4100
探头类型
线缆式
AKS 4100
液体CO
2
AKS 4100
气相Er
001.000
AKS 4100
探头长度
05000 mm
AKS 4100
4mA对应量程
04946 mm
AKS 4100
20mA对应量程
00070 mm
AKS 4100
快速设置
完成 8
AKS 4100
1.0.0
快速设置
AKS 4100
1.0.0
保存设置 NO
AKS 4100
距离
5000 mm
AKS 4100
同轴套管式 D14 2200 mm
(0%) 4 mA 1900 mm
(100%) 20 mA 70 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 15
将设备连接到电源(参阅“电气安装/连接”
一节)。
按下 3次。
按下
按下 ,在SINGLE(电缆形式)和
COAXIAL (同轴形式)之间进行选择。选择
COAXIAL并按下 以示确认。
• 按下 (NO)以示确认
按下 更改探头长度。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
按下 更改标度 4 mA。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
按下 更改标度 20 mA。
按下 更改游标位置。
按下 调低数值,或者按 调高数值。
按下 以示确认。
• 等待快速设置完成。倒数8秒
• 按下 以示确认。
按下 ,在 STORE NO (保存 否)
STORE YES (保存 是)之间进行选择。
按下 以示确认。
显示默认屏幕:
快速设置完成
若使用其他制冷剂:
AKS 4100
快速设置?
AKS 4100
探头类型
线缆式
AKS 4100
液体CO
2
AKS 4100
探头长度
05000 mm
AKS 4100
4mA对应量程
04946 mm
AKS 4100
20mA对应量程
00070 mm
AKS 4100
快速设置
完成 8
AKS 4100
1.0.0
快速设置
AKS 4100
1.0.0
保存设置 NO
AKS 4100
距离
5000 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 16
默认屏幕
• 按下
• 按下
• 按下
输入密码:
• 按下
按下
按下
按下 调低数值,或者按下
调高数 值。按下 以示确认。
按下 4次返回默认屏幕。
显示默认屏幕
强制 mA 完成并禁用
如果强制 mA 输出(下面所有数值均为举例)
默认屏幕
• 按下
• 按下
• 按下
输入密码:
• 按下 4次
按下
按下 2次
按下 ,以便检查/修改 GAS EPS.R.
(从下表和第8页的表格中选择正确的数值)
按下 更改游标位置。按下 调低数值,
者按调高数值。
• 按下 以示确认。
按下 3次
按下 ,在STORE NO(保存 否)
和STORE YES(保存 是)之间进行选择。
按下 3选择STORE YES(保存 是)
显示默认屏幕:
输入制冷剂气体的介电常数
如何输入制冷剂气体的介电常数(以下所有数值均为举例)
可选步骤
若已知立管的温度条件,可以输入一个常数(制冷剂气体的介电常数)(参数 2.5.3 GAS EPS.R),以降低顶端和底端死区的数值(参阅图6)
AKS 4100
距离
5000 mm
AKS 4100
1.0.0
快速设置
AKS 4100
2.0.0
操作员
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
信息
AKS 4100
2.2.0
测试
AKS 4100
2.2.1
测试电流
AKS 4100
测试电流
3.5 mA
AKS 4100
测试电流
8 mA
AKS 4100
距离
5000 mm
AKS 4100
距离
5000 mm
AKS 4100
1.0.0
快速设置
AKS 4100
2.0.0
操作员
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
信息
AKS 4100
2.5.0
工况参数
AKS 4100
2.5.1
追従速度
AKS 4100
2.5.3
气相Er
AKS 4100
2.5.3
气相Er
AKS 4100
1.0.0
保存设置 NO
AKS 4100
距离
5000 mm
AKS 4100
气相Er
1.066
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 17
饱和蒸气的介电常数
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-60 – -42 -76 – -43 1.00
-41 – -18 42 – 0 1.01
-17 – -5 1 – 23 1.02
-4 – 4 24 – 39 1.03
5 – 12 40 – 54 1.04
13 – 18 55 – 64 1.05
19 – 24 65 – 75 1.06
25 – 28 76 – 82 1.07
29 – 33 83 – 91 1.08
34 – 37 92 – 99 1.09
38 – 40 100 – 104 1.10
41 – 44 105 – 111 1.11
45 – 47 112 – 117 1.12
48 – 50 118 – 122 1.13
R717 (
)
温度范围:
-60 – 50 °C / -76 – 122 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-56.0 – -42.0 -69 – -43 1.01
-41.0 – -28.0 -42 – -18 1.02
-27.0 – -17.0 -17 – 2 1.03
-16.0 – -9.0 3 – 16 1.04
-8.0 – -3.0 17 – 27 1.05
-2.0 – 2 28 – 36 1.06
3 – 7 37 – 45 1.07
8 – 11 46 – 52 1.08
12 – 14 53 – 58 1.09
15 59 1.10
R744 (
二氧化碳
)
温度范围:
-56 – 15 °C / -69 – 59 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-60 – -50 -76 – -58 1.00
-49 – -25 57 – -13 1.01
-24 – -10 -12 – 14 1.02
-9 – 0 15 – 32 1.03
1 – 8 33 – 46 1.04
9 – 15 47 – 59 1.05
16 – 21 60 – 70 1.06
22 – 26 71 – 79 1.07
27 – 31 80 – 88 1.08
32 – 35 89 – 95 1.09
36 – 39 96 – 102 1.10
40 – 42 103 – 108 1.11
43 – 45 109 – 113 1.12
46 – 48 114 – 118 1.13
R22
温度范围:
-60 – 48 °C / -76 – 118 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-60 – -42 -76 – -43 1.00
-41 – -18 -42 – -0 1.01
-17 – -4 1 – 25 1.02
-3 – 5 26 – 41 1.03
6 – 13 42 – 56 1.04
14 – 20 57 – 68 1.05
21 – 25 69 – 77 1.06
26 – 30 78 – 86 1.07
31 – 34 87 – 94 1.08
35 – 38 95 – 100 1.09
39 – 42 101 – 108 1.10
43 – 45 109 – 113 1.11
46 – 48 114 – 119 1.12
49 – 50 120 – 122 1.13
R134a
温度范围:
-60 – 50 °C / -76 – 122 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-60 – -47 -76 – -52 1.01
-46 – -35 -51 – -31 1.02
-34 – -26 -30 – -14 1.03
-25 – -19 -13 – -2 1.04
-18 – -14 -1 – 7 1.05
-13 – -9 8 – 16 1.06
-8 – -4 17 – 25 1.07
-3 – 0 26 – 32 1.08
1 – 3 33 – 38 1.09
4 – 6 39 – 43 1.10
7 – 9 44 – 49 1.11
10 – 12 50 – 54 1.12
13 – 15 55 – 59 1.13
R404A
温度范围:
-60 – 15 °C / -76 – 59 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-65 – -47 -85 – -52 1.01
-46 – -35 -51 – -31 1.02
-34 – -26 -30 – -14 1.03
-25 – -19 -13 – -2 1.04
-18 – -13 -1 – 9 1.05
-12 – -8 10 – 18 1.06
-7 – -4 19 – 25 1.07
-3 – 0 26 – 32 1.08
1 – 4 33 – 40 1.09
5 – 7 41 – 45 1.10
8 – 10 46 – 50 1.11
11 – 12 51 – 54 1.12
13 – 15 55 – 59 1.13
R410A
温度范围:
-65 – 15 °C / -85 – 59 °F
温度
[°C]
温度
[°F]
制冷剂气体的介电常数
参数 2.5.3
GAS EPS.R
-60 – -48 -76 – -54 1.01
-47 – -36 -53 – -32 1.02
-35 – -28 -31 – -18 1.03
-27 – -21 -17 – -6 1.04
-20 – -15 -17 – -5 1.05
-14 – -10 -4 – 14 1.06
-9 – -6 13 – 22 1.07
-5 – -2 23 – 29 1.08
-1 – 2 30 – 36 1.09
3 – 5 37 – 41 1.10
6 – 8 42 – 47 1.11
9 – 11 48 – 52 1.12
12 – 13 53 – 56 1.13
14 – 15 57 – 59 1.14
R507
温度范围:
-60 – 15 °C / -76 – 59 °F
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 18
默认屏幕
• 按下
• 按下
• 按下
输入密码:
• 按下 6次
•按下
•按下
按下 查看语言选项
按下 以示确认。
• 连按 3次
• 按下 ,在 STORE NO(保存 否)
和STORE YES(保存 是)之间进行选择。
按下 选择 STORE YES(保存 是)
显示默认屏幕:
语言设置完成
如何修改语言设置(默认:英文)
• 进入SUPERVISOR(查看)菜单(参见第7页)
• 进入参数2.9.4 恢复出厂设置
• 选择RESET FACTORY YES(恢复出厂设置:是)
• 按下 三次,返回默认屏幕
恢复出厂完成
重置为出厂设定
AKS 4100
距离
5000 mm
AKS 4100
1.0.0
快速设置
AKS 4100
2.0.0
操作员
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
信息
AKS 4100
2.7.0
显示
AKS 4100
2.7.1
语言
AKS 4100
语言
中文
AKS 4100
2.7.1
语言
AKS 4100
1.0.0
保存设置 NO
AKS 4100
距离
5000 mm
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 19
日本
AKS 4100/4100U は必ず直立管 (柱/バイ
ス/静止筒) に設置すださ
直立管は以下の場合に使用さす:
AKS 4100用の整備
内にアワが多る場合
液体が非常に激乱れる場合
HMI 付たはの AKS 4100/4100U 同軸バ
ジョン C O
2
に使用ない場合は動作設定
る必はあません。
プリセット:
4 mAプロブ長 - 100 mm (4 インチ)
20 mA120 mm (5 イチ)
冷媒
AKS 4100/4100U は、特にR744 (CO
2
)、R717
(ンモニ)、HCFC、HFCた最も使用さ
る冷媒や非腐食性ス/液体のレベルを計
るた計されています
ータ
AKS 4100/4100U は、ループ給電のパ2
4
~20 mA センサーです
供給電圧
端子における最大出力 22 mA における最小/最
大値
負荷
RL [Ω] ((Uext -14 V)/20 mA).
– デ (エー出力は 3.6 mA に設定)
RL [Ω] ((Uext -14 V)/22 mA).
– (エー出力は 22 mA に設定)
ンド
AKS 4100 PG 13、M20×1.5 ;
(ケーブル径:
6~8 mm (0.24~0.31インチ)
AKS 4100U ½ インチ NPT
端子 (バネ懸架式)
0.5~1.5 mm
2
(~20-15 AWG)
保護構造
IP 67 (~NEMA プ 4X)
冷媒温度
-60 – 100 °C / -76 – 212 °F
冷媒
にある冷媒は Danfoss が認定したもの
す:
R717 / NH
3
: -40 – 50 °C / -40 – 122 °F
R744 / CO
2
: -50 – 15 °C / -58 – 59 °F
HCFC:
R22: -50 – 48 °C / -58 – 118 °F
HFC:
R404A: -50 – 15 °C / -58 – 59 °F
R410A: -50 – 15 °C / -58 – 59 °F
R134A: -40 – 50 °C / -40 – 122 °F
周囲温度
-40 – 80 °C / -40 – 175 °F
HMI の場合:-20 – 60 °C / -4 – 140 °F
処理圧力
-1 – 100 barg / -14.5 – 1450 psig
5 m (197 ンチ) Ø2 mm (0.08 イチ)
ス ケブルる機械プロセス接続部:
AKS 4100 G1 インチ管ネジ
アルミニウムケッ
AKS 4100U ¾ インチ NPT
(詳細は技術カグを参照)
機械設置
機械設置前の準備
信号変換器を機械プロセス接続部か
(5´mm 六角チを使用。図 6 を参照)赤色の
保護カバーを機械プロス接続部に取付け湿
気やほら保護ます
付属品の内容 (図 1)
信号変換器 (HMI がある場合ない場合が
りま )
5 m (197 ンチ) Ø2 mm (0.08 ンチ)
レス ケーブルる機械プロス接続
チュ
グ内容:
(3 mm の取付けネジ含む)
3 mm の取付けネジ (ブ 1 本につき
ネジ 1 本)
信号ンバーを取付ける前に機械プロ
接続部保護するための赤色のカバ
定ラベ
割されている軸プロー
レスヤが完全に曲がった
れたない
注意ださい。
1. レスヤの端を各チブの上にあ
プラスペーサーの中央の穴に
しま (図 2 参照)。テンレワイヤ
チューブ通して出します。ューブ
が複数ある場合にはの手順を繰ます
2. を組み立(図 3 を参照)
17 mm を組み立た部品を固定
す。
3. ブが複数ある場合にはの手順を繰
返しま (図 3 を参照)。
4. 組み立てる前に、信号コンバー機械プ
ス接続部を機械プロス接続部に赤
い保護キプを取付けます組み立てたチ
ブを機械プロセス接続部 ねじ
す。
5. 付けネ 3 mm 六角で締め
チューブ定しま (図 3 を参照)。
6. エン コネクタを通してステンレスワイヤ
りま (図.4 参照)。
7. コネを組み立てたチブの下に
取り付す。
付けネジを 3 mm 六角ンチで締め付け
ます(図 4 を参照)。
8. エンドコネクタから伸びるステンレスワイヤの
端をプライヤーでっ張 (図 4)、信
ルが適切に張れてを確認ます
2 本の取付けネ3 mm 六角で締
て、テンレワイヤ定します。
9. ステンレスワイヤをネクタの
20 mm (0.8 ンチ) で切断(図 5 を参
照)。
10. (信号ンバーの) プロブ長を組み立て
プロブを直立管に取付け前に測定ます
(図 6 参照)。
レンチを使用プロセス接続
(図 1 の項目 2) 120 Nm (89 lb/ft) で締
め付け
工場出荷時の設定に戻必要が場合
HMI ク プのプロブ長、スケ
ル 4 mA および 20 mA
プロブ長:
Danfoss 製品のベルにプロブ長を参考
るか、プロー長を計測ます (図 6 参照)。
ール 4 mA:(最大計測範囲の場合)
= プローブ長
– 下部デドゾー(図 6 を参照)
ール 20 mA: (最大計測範囲の場合)
= 上部デゾー(図 6 参照)
例 (AKS 4100)
条件:
プロブ長:1200 mm
冷媒:CO
2
, –35°C
定数 Er は必ず プで調整
プロブ長:
= 1200 mm
SCALE 4 mA 設定の最大計測範囲:
= プローブ長 (1200 mm)
下部デゾー(図 6 参照)
(170 mm) = 1030 mm (40.9 チ)
SCALE 20 mA 設定の最大計測範囲:
= 部デドゾー(図 6 を参照)
= 120 mm (4.7 イチ)
8 ペ より:
冷媒スの誘電率パ 2.5.3 GAS
EPS.R
= 1.02
AKS 4100/4100U ンバーの取付け方法 (図
7 参照)
1. 信号変換器の位置決めネジ通気ネジを5 mm
の六角ンチで外ださ
2. 信号変換器を下方向に止で押し込み
機械プロス接続部確実に勘合させま
3. 信号変換器を希望す向きに回ます
4. 位置決めネジを5mmの六角レンチで締め付け
ださい。
5. 通気ネジを5mmの六角レンチで締め付け
ださい。
電気接続
出力端子 (図 8 おび 9)
1. 電流出力 –
2. 電流出力 +
3. 接地端子
電気接続の手順
1. 2.5 mm 六角レンチを使用カバー止めを
めます
2. 筐体か端子部品カバーをます
3. ヤは端子部品バーかてはな
ん。筐体の横に端子部品カバーを置
4. を装置に接続ますケーブル入口金物
を締め付け
5. 端子部品カバーを筐体に取付けます
6. 2.5 mm 六角レンチを使用カバー止めを
めます
注:
信号コンバータは、械プロコネタ付き
なしでログるこす。
起動:
ンバーを電点に接続ます
ンバータに通電ます
HMI 装置のみ:
10 秒後に「Starting up」画面に表示
20 秒後にソのバーン番号が画面に
示されます30 秒後に画面
(図 13) が表示
AKS 41/41U AKS 4100/4100U に変更
の注意点:
注 意くだ い : AKS 41/41U は交流および直流
電源で使用できますが、AKS 4100/4100U は直流
電源でのみ使用で10 の説明に
ださい
ローは PLC への接続
11 12 従ってく
注:
AKS 4100/4100 がマーカー 1、2、3
なエを検知た場合には電流出力は
3.6 mA に設定れま(4 ペジ参照)
ット
© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.G3.ML | 520H8442 | 20
装置を電源に接続ます (「電気接続
ショ くだ )
3 押しす。
を押ます
たは   を押グルケー
ル式」同軸式 D14」たは「同
軸式 D22」を選択プ式 D14」
択し 押して定しす。
(確認実行) を確定ます
を押ガス誘電率」に変ます
(以下の表おび 8 ページの表か
い値を選ます)
を押てカソルの位置を変更ます
を押て値を減か、
押して
値を増やます
押してします。
押して「プ更しま
す。
を押てカソルの位置を変更ます
を押て値を減か、 押して
値を増やます
押して定しす。
を押「4mA位置に変更ます
を押カールの位置を変更ます
を押て値を減か、
押して
値を増やます
押して定しす。
を押「20mA位置に変更ます
を押カールの位置を変更ます
を押て値を減か、
押して
値を増やます
押して定しす。
• クプが完了で 8
秒間待ます
押してします。
または を押「保存中止または
「保存のいずれかを選択
押して定しす。
画面が表示さす:
クイクセットア
2 回押設定を確認す
す。
を押画面に戻
りま
高速設置 (以下の値一例す)
CO
2
使用す場合:
注:
信号コンバは、械プロコネタ付きまたはなでプログラムすができます
AKS 4100
クイクセットアッ
はい いえ
AKS 4100
ーブタイプ
ーブ
AKS 4100
液体CO
2
はい いえ
AKS 4100
气相Er?
001.000
AKS 4100
プロー長さ
05000 mm
AKS 4100
4mA位置
04946 mm
AKS 4100
20mA位置
00070 mm
AKS 4100
クイクセットアッ
コンプリト8
AKS 4100
1.0.0
クイクセットアッ
AKS 4100
1.0.0
保存中止
AKS 4100
距離
5000 mm
AKS 4100
パイプ式 D14 2200 mm
(0%) 4 mA 1900 mm
(100%) 20 mA 70 mm
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Danfoss Liquid level sensor Type AKS 4100 / AKS 4100U - Coaxial D14 version インストールガイド

タイプ
インストールガイド