EPDU1116S

APC EPDU1116S インストールガイド

  • APC by Schneider Electric Easy PDU EPDU1116SおよびEPDU1132Sの設置マニュアルの内容を読みました。このデバイスの設置、仕様、安全手順、トラブルシューティングなどについてご質問にお答えします。マニュアルには、安全な設置方法、ネットワーク接続、およびさまざまなモデル間の違いに関する情報が含まれています。
  • ラックPDUを安全に設置するにはどうすればよいですか?
    EPDU1116SとEPDU1132Sの違いは何ですか?
    ネットワーク設定にアクセスするにはどうすればよいですか?
    保守可能な部品はありますか?
Safety
Read the following information before installing or operating your APC by Schneider
Electric Rack Power Distribution Unit (PDU).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The Rack PDU is intended to be installed and operated by a skilled person in a
controlled location.
• Do not operate the Rack PDU with the covers removed.
• This Rack PDU is intended for indoor use only.
• Do not install this Rack PDU where excessive moisture or heat is present.
• Never install any wiring, equipment, or Rack PDUs during a lightning storm.
• Plug this Rack PDU into a grounded power outlet only. The power outlet must be
connected to appropriate branch circuit/mains protection (fuse or circuit breaker).
Connection to any other type of power outlet may result in a shock hazard.
• Do not use extension cords or adapters with this Rack PDU.
• If a socket-outlet is not accessible to the equipment, a socket-outlet shall be
installed.
• Do not work alone under hazardous conditions.
• Check that the power cord, plug, and socket are in good condition.
• Disconnect the Rack PDU from the power outlet before you install or connect
equipment to reduce the risk of electric shock when you cannot verify grounding.
Reconnect the Rack PDU to the power outlet only after you make all connections.
• Do not handle any kind of metallic connector before the power has been removed.
• Use one hand, whenever possible, to connect or disconnect signal cables to avoid a
possible shock from touching two surfaces with different grounds.
This unit does not have any user-serviceable parts. Repairs are to be performed only
by factory-trained service personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
FIRE HAZARD
This equipment should be connected to a single-outlet dedicated circuit protected by
a circuit breaker or fuse with the same current rating as the Rack PDU.
The plug or inlet serves as the disconnect for the Rack PDU. Make sure the utility
power outlet for the Rack PDU will be close to the Rack PDU and readily accessible.
Failure to follow these instructions can result in death or serious injury.
Easy PDU Switched Rack Power Distribution Unit
Installation
Worldwide Customer Support
Customer support for this product is available at www.apc.com
© 2020 APC by Schneider Electric. APC and NetShelter are trademarks owned by Schneider
Electric SE. All other trademarks are property of their respective owners.
Overview
This sheet provides installation information for your Easy PDU. Read the instructions
carefully.
Receiving
Inspect the package and contents for shipping damage. Make sure all parts were sent.
Immediately report any shipping damage to the shipping agent. Report missing
contents, product damage, or other problems with the product to APC by Schneider
Electric or your APC by Schneider Electric reseller.
Material recycling
The shipping materials are recyclable. Please save them for later use, or dispose of
them appropriately.
990-91367 1/2020
Installation
Option 1 - Vertical Installation with Brackets
1. Install the two (2) brackets to the Rack PDU with the
screws provided.
2. Install the PDU to the rack
with the provided four (4)
M5 x10 mm self tapping
screws.
Option 2 - Toolless Mounting Pegs
The mounting pegs of the Rack PDU are
installed at the factory. Slide both mounting
pegs into the holes located in the channel in
the rear panel of the rack. Snap the Rack PDU
into place by pushing it downward until it locks
into position.
NOTE: When installing the Rack PDU, ensure
that the power cord plug is accessible and that
it is connected to a grounded outlet.
pdu0891b
pdu0888 a
Display Interface
Use the up and down function buttons to view information on the LCD display.
To configure the network settings and access the Rack PDU
Connect the network cable to the Network port and apply power to the unit. When
you hear a “Beep” sound and the Status LED for the network connection is flashing
green, press the Down function button until the IP address appears.
To access the Rack PDU software interface, enter the IP address in your browser
address field. You will be prompted for a user name and password. Enter the default
apc” for each. See the User Guide for this device online at www.apc.com for more
detailed information.
Item Function Description
LCD Display View functional data
Run Indicator LED Indicates the status when the power is on
Reset Button Press and hold for 4 seconds to reset to the default
settings
Up Function Button Scroll for function status, Alarm shutoff
Down Function Button Scroll for function status, hold for Alarm shutoff
(Press and hold for 10 seconds to reboot)
Temp/Humidity Port Temp/Humidity Sensor connection port
Out Port RS485 port sharing connection
In Port RS485 port sharing connection
Network Port Connect the Rack PDU to your network
Specifications
EPDU1116S EPDU1132S
Electrical
Nominal Input Voltage 200 - 240 VAC 1 PHASE
Maximum Input Current (Phase) 16A 32A
Input Frequency 50/60Hz
Input Connection IEC309 16A 2P +E IEC309 32A 2P +E
Output Voltage 200 - 240 VAC
Output Connections
Twenty (20) C13
Max. output current 10A
Four (4) C19
Max. output current 16A
Bank 1:
Ten (10) C13
Max. output current 10A
Two (2) C19
Max. output current 16A
Bank 2:
Ten (10) C13
Max. output current 10A
Two (2) C19
Max. output current 16A
Circuit Breakers None
Two (2) 16A 1-pole
hydraulic-magnetic circuit
breakers
Physical
Dimensions (H x W x D) 1738 x 55 x 62 mm
(68.43 x 2.16 x 2.44 in)
Input power cord length 3 m (9.8 ft)
Shipping dimensions (H x W x D) 1950 x 160 x 110 mm
(76.77 x 6.30 x 4.33 in)
Weight/Shipping weight
EPDU1116S
EPDU1132S
7.3 kg (16.09 lb)/8.5 kg (18.74 lb)
7.9 kg (17.41 lb)/9.0 kg (19.84 lb)
Environmental
Maximum elevation (above MSL)
Operating/Storage
0–3000 m (0–10,000 ft) /
0–15000 m (0–50,000 ft)
Temperature: Operating/Storage –5 to 45°C (23 to 113°F)/
–25 to 65°C (–13 to 149°F)
Humidity: Operating/Storage 5–95% RH, non-condensing
Compliance
EMC verification CE EN55035, EN55032, EN55024
Safety verification CE, TUV, EN/IEC62368-1
CE EU Contact Address Schneider Electric, 35 rue Joseph Monier
92500 Rueil Malmaison France
Environmental RoHS & Reach
Life Support Policy
General policy
APC by Schneider Electric does not recommend the use of any of its products in the following
situations:
In life-support applications where failure or malfunction of the APC by Schneider Electric
product can be reasonably expected to cause failure of the life-support device or to affect
significantly its safety or effectiveness.
In direct patient care.
APC by Schneider Electric will not knowingly sell its products for use in such applications unless it
receives in writing assurances satisfactory to APC by Schneider Electric that (a) the risks of injury or
damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of APC by
Schneider Electric is adequately protected under the circumstances.
Examples of life-support devices
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve
stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices,
blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems,
peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants),
anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S.
FDA.
Hospital-grade wiring devices and leakage current protection may be ordered as options on many
APC by Schneider Electric UPS systems. APC by Schneider Electric does not claim that units with
these modifications are certified or listed as hospital-grade APC by Schneider Electric or any other
organization. Therefore these units do not meet the requirements for use in direct patient care.
Radio frequency interference
Changes or modifications to this unit not expressly approved by the party responsible for compliance
could void the user's authority to operate this equipment.
Factory Warranty
This warranty applies only to the products you purchase for your use in accordance with this manual.
Terms of warranty
APC by Schneider Electric warrants its products to be free from defects in materials and
workmanship for a period of one year from the date of purchase. APC by Schneider Electric will repair
or replace defective products covered by this warranty. This warranty does not apply to equipment
that has been damaged by accident, negligence or misapplication or has been altered or modified in
any way. Repair or replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly registered the product.
The product may be registered at the APC by Schneider Electric website, www.apc.com.
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused by end user’s or any third
person’s misuse, negligence, improper installation or testing. Further, APC by Schneider Electric shall
not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate
electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC by
Schneider Electric recommendations or specifications or in any event if the APC by Schneider
Electric serial number has been altered, defaced, or removed, or any other cause beyond the range
of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT
OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR
PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE
ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE
OUT OF, APC BY SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND
REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE
WARRANTIES SET FORTH ABOVE CONSTITUTE APC BY SCHNEIDER ELECTRIC’S SOLE
LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO
ANY THIRD PARTIES.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL,
CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR
INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR
TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC BY
SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS,
SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF
EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY
THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS AUTHORIZED
TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE
MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY SCHNEIDER ELECTRIC
OFFICER AND LEGAL DEPARTMENT.
Warranty claims
Customers with warranty claims issues may access the APC by Schneider Electric customer support
network through the Support page of the APC by Schneider Electric website, www.apc.com/support.
Select your country from the country selection pull-down menu at the top of the Web page. Select the
Support tab to obtain contact information for customer support in your region.
Switched Rack PDU 机架配电单元安装手册
全球客户支持
客户支持和保修信息,请访问:www.apc.com。
© 2020 施耐德电气 版权所有。
总览
此表提供了 Easy PDU 的安装信息。 请仔细阅读说明。
接收
检查包装和内容是否有运输损坏。 确保所有部件都已发送。 立即向运输代理商报告任何
运输损坏。
请通过 apc.com 联系您的 APC by Schneider Electric 经销商或全球客户支持,以报告
产品缺失的内容,产品损坏或其他问题。
材料回收
运输材料是可回收的。 请妥善保管以备日后使用,或妥善处理。
990-91367
1/2020
安全
在安装或操作您的 APC by Schneider Electric Rack 配电单元 (PDU)之前,请阅读以
下信息。
危险
触电、爆炸或电弧闪光的危险
如果盖板拆除,请勿操作机架 PDU。
内部没有用户可以检修的零件。请安排具有资历的人员进行检修。
连接固定和电缆控制附件时,只能使用我们提供的器件。
只能在室内的干燥位置使用。
安装机架 PDU 时,请遵守当地和国家的所有法规。
在无法确认是否接地时,在机架 PDU 连接设备前,请从市电电源插座断开机架
PDU。
机架 PDU 适当安装到机架式机柜,且完成了所有负载和信号连接后,在市电电源
插座,连接机架 PDU 的电源线。
确保市电电源插座和机架 PDU 电源线和插头状况良好。
请勿独自作业,亦不得在危险条件下作业。
高电流通过导电材料会引起严重烧伤。
检修负载设备或电源线前,从该产品断开负载电源线。
请务必使用具有合适额定电压的传感设备,确认电源已经关闭。
否则,可能导致死亡或严重受伤。
警告
起火危险
该设备应当连接到单一插座的专用电路,并利用具有与机架 PDU 相同电流等级的
断路器或保险丝加以保护。
插头或引入线用作机架 PDU 的断路器。确保机架 PDU 的市电电源插座靠近机架
PDU,且容易接近。
否则,可能导致死亡或严重受伤。
安装
把机架 PDU 垂直的安装在 NetShelter 机架或任何标准的
EIA-310 机架。
方式 1– 垂直支架安
1. 使用随附的硬件,把两个支架安装到机架 PDU
2. 使用随附的四个M5x10 mm
自攻螺丝,把机架 PDU 固
定在机架上。
方式 2- 免工具安
机架 PDU 的安装钉已经在工厂预安装。
把两个固定销滑入机柜背面板通道中的空洞。
向下按压机架 PDU, 将其卡入,直至锁紧。
注意:安装机架 PDU 时,请确保电源线插头易
于触及,并且 PDU 连接到一个接地插座。
pdu0891b
pdu0888 a
显示介
使用滚动按钮查看总电流,电压和功率。 按滚动按钮在显示的信息之间移动。
配置网络设置并访问机架 PDU
将网络电缆连接到网络端口 并为设备供电。 当您听到 声并且网络连接的状
LED 闪烁绿色时,按功能按钮 直到出现 IP 地址。
要访问机架 PDU 件界面,请在浏览器地址字段中输入 IP 地址。 系统将提示您输入用
户名和密码。 为每个输入默认的 “ apc”。 有关更多详细信息,请在线访问该设备的
《用户指南》,网址为 www.apc.com。
项目 功能 描述
液晶显示器 查看功能数据
运行指示灯 LED 指示电源打开时的状态
重置按键 按住 4 秒钟可重置为默认状态
上功能按键 滚动查看功能状态,警报关闭
下功能按键 滚动查看功能状态,警报关闭 / 重新启动
( 按住 10 秒钟可重新启动 )
温度 / 湿度端口 温度 / 湿度传感器连接端口
Out 级联口 共享网络连接 RS485 端口
In 级联口 共享网络连接 RS485 端口
网络端口 将机架 PDU 连接到网络
规格参
EPDU1116SEPDU1132S
电气参数
额定输入电压 200 - 240 VAC 1 PHASE
最大输入电流 16A 32A
额定输入频率 50/60Hz
输入接口 IEC309 16A IEC 309 32A 2P+E
输出电压 200 - 240 VAC
输出接口
IEC-320-C13 (20)
最大输出电流 10A
IEC-320-C19 (4)
最大输出电流 16A
Bank 1:
IEC-320-C13 (10)
最大输出电流 10A
IEC-320-C19 (2)
最大输出电流 16A
Bank 2:
IEC-320-C13 (10)
最大输出电流 10A
IEC-320-C19 (2)
最大输出电流 16A
断路器 没有 二 (2) 16A 1 极液磁
断路器
结构参数
产品尺寸 [ 高 X 宽 X 深 ] 1738 x 55 x 62 mm
(68.43 x 2.16 x 2.44 in)
电源线的长度 3 m (9.8 ft)
包装尺寸 [ 高 X 宽 X 深 ] 1950 x 160 x 110 mm
(76.77 x 6.30 x 4.33 in)
产品重量 / 包装重量
EPDU1116S
EPDU1132S
7.3 kg (16.09 lb)/8.5 kg (18.74 lb)
7.9 kg (17.41 lb)/9.0 kg (19.84 lb)
适应环境
海拔高度 (基于平均海平面 )
工作条件 / 储存条件 0–3000 m (0–10,000 ft) / 0–15000 m (0–50,000 ft)
温度 : 工作条件 / 储存条件 –5 to 45°C (23 to 113°F)/
–25 to 65°C (–13 to 149°F)
湿度 : 工作条件 / 储存条件 5–95% 相对湿度非凝结
认证
电磁兼容标准 遵循标准 EN55035, EN55032, EN55024
安全标准 CE, TUV, 遵循标准 EN/IEC62368-1
CE EU Contact Address Schneider Electric, 35 rue Joseph Monier
92500 Rueil Malmaison France
环境 RoHS & Reach
生命支持政策
一般策略
APC by Schneider Electric 不建议在以下情况下使用其任何产品:
在 APC 产品的故障或失效可能导致生命保障设备的故障,或极大地影响其安全性
效率的生命保障应用中
直接护理病人
APC by Schneider Electric ,除非 APC by
Schneider Electric 到令其满意的书担保,明确示:(a) 身伤害或设备的损坏风险已
降至最低,(b) 客户承担所有风险,(c) 如有此类情况发生,APC 的责任将受到充分地保护
生命保障设备的实例
生命保障设备
包括但不仅限于:新生儿氧气分析仪、神经模拟器 (用于麻醉、减轻疼
等)、自体输血设备、抽血、去纤颤器、心率不齐探测器和警报器、起搏器、血液透析系
统、腹膜透析系统、新生儿通风保育器、通风设备 (用于成人和婴儿)麻醉手术通风
备、输血以及由 U.S. FDA 指定为 “ 关键 ” 的其他设备。
对于很多 APC by Schneider Electric UPS 系统,可以作为可选项订购医院级的接线设备和
漏电保护设备。APC by Schneider Electric 未声明经过这些更改的设备经过 APC by
Schneider Electric 或其他组织验证或被列为医院级的设备。因此这些设备不符合直接护理
病人的要求。
射频干扰
未经合规负责方明确批准而对本设备进行更改或修改可能会使用户无权操作此设备
一年出厂担保
此担保适用于购买后遵照手册进行使用的产品。
担保条款
APC by Schneider Electric 保证其产品自购买之日起一年内不会出现材料和工艺缺陷。APC
by Schneider Electric 对本担保适用的故障产品提供修理或更换服务。本担保不适用于因
偶然、疏忽或误用所造成的损坏或以任何方式更改或改装过的产品。
故障产品或部件的修理或更换并不会延长原保修期。根据本担保所提供的任何部件可能是全
新的,也可能是工厂 - 翻新品。
不可转让担保
本担保只适用于适当注册过产品的原始购买者。可以通 APC by Schneider Electric 网站
www.apc.com 注册该产品。
免责条款
若经 APC 测试和检测发现,购买者所声称的缺陷根本不存在或由购买者或任何第三方误用、
疏忽、安装或测试不当引起,则 APC by Schneider Electric 不给予保修服务。如属下列
况,APC by Schneider Electric 亦不提供修服务:未授权擅自修理或改装、错误或
当电压或连接、现场操作条件不当、腐蚀性环境、修理、安装和打开设备外壳、自然因素、
火灾、失窃,或不依照 APC by Schneider Electric 建议或规格安装或更改、损坏、移除
APC by Schneider Electric 序列号的任何情形,或者进行其它超出使用范围的操作
对于根据本协议及其相关条款销售、维修或提供的产品,APC by Schneider Electric 在
律或相关法规允许的范围内不提供任何明示或暗示的担保。对于本产品用于特殊目的适销
性、满意度和适用性,APC by Schneider Electric 不提供任何形式的暗示担保。APC by
Schneider Electric 的明示担保不应被扩展缩减或受到责任义务影响,APC by Schneider
Electric 只提供与产品相关的技术或其他建议或服务。上述的担保和补救措施仅适用于本产
品并取代所有其他担保和补救措施。针对任何违反担保的情况,上述担保规定了 APC by
Schneider Electric 的全部责任以及购买者的全部补偿。APC by Schneider Electric 提供的
担保仅授予本产品购买者,任何第三方不得享受本担保
APC by Schneider Electric 及其官员、主管、子公司或员工不对使用、修理或安装品过
程中发生的任何间接的、特殊结果的或惩罚性的损害负责,不论此类损害是来自于合同或民
事侵权,不论是属于故障、疏忽或严格责任,或者 APC by Schneider Electric 是否已预
被告知损害的可能性。特别需要指出的是,APC by Schneider Electric 对任何费用不承担
责任,例如损失利润和收入、设备损坏、无法使用设备、软件损坏、丢失数据、替代物的成
本、第三方索赔或其它方面的费用。
APC by Schneider Electric 的任何销售人员、雇员或代理商无权对本担保进行任何补或
修改。如有必要,仅可由 APC by Schneider Electric 官员和法律部门以书面形式签署对
担保条款的修改。
担保索赔
发生担保索赔问题的客户可以通过 APC by Schneider Electric 网站 www.apc.com/
support 上的 “ 支持 面访问 APC by Schneider Electric 客户支持网络。
从网页顶部的国家 / 地区选择下拉菜单中选择您的国家 / 地区。选择 “ 支持 ” 选项卡以获
得您所在地区的客户支持联系信息。
/