1.1 Environmental Requirement
Operating temperature: SZ7 Series HMI can work stably in most industrial environments that the
temperature between 32°F to122°F (0~50°C).
NEMA rating: This Series HMI is NEMA 1 rated in front panel.
Input voltage:DC16V~DC32V.
Particularly note that there must be enough distance between this product and converters or switch
power supply. Make sure that the input and output cables of that kind equipment are shield cable
and the shielding network is connected with the ground.
Make sure that the DC power and AC power is isolated.
Do not use same power supply with the input circuit of inductance load or the controller.
2.1 Dimensional Drawing
2.2 Installation Instructions
2.2.1 Rack Mounting
2.2.2 Hanging Mounting
NOTE
:
There are only M4 installation screws in the packaging carton. The rack and the sheet metal
pendant are just schematic diagrams, needed to customize by customers.
Note
:
1.RS485
、
RS232
、
Ethernet are integrated in the 14-core shielded cable.
2. The Suffix of S indicates that products with hand holding switch, E is for Ethernet port.
3.1RS232 port
RS232 port is used to program and debug.
3.2 USB HOST
Connect with USB interface devices or U disks
This interface can be connected with USB keyboard, mouse and printers, and the
U disk can be used for user’s configuration uploading/ downloading as well as
data storage.
3.3RS485 port (SZ7 and SZ7S Support)
Note
:
When you create a project in Kinco HMIware SZ7 and SZ7S share a component icon.
3.4 Ethernet (SZ7E and SZ7ES Support)
Ethernet interface can adaptive 10 M/ 100 M.
Grey/red/black/yellow in the 14-core shielded cable (see below)
The port can be used for uploading/downloading HMI program, setting
system parameters and online simulation. It can connect multiple HMIs via
the Ethernet; it can communicate HMI and PLC via the Ethernet, as well as
communicate with a PC via the Ethernet port.
Note
:
When you create a project in Kinco HMIware,SZ7E and SZ7ES share a same icon
4.1 Instructions for entering Operation Mode selection window
Hold pressing on the touch panel when you power on HMI, then HMI will enter operation mode
selection window, select the operation mode according to your application. If there is not any operation in
20 seconds after entering operation mode selection window, HMI will enter application (normal working)
mode automatically.
4.2 Descriptions of functions in Operation Mode selection window
After entering operation mode selection window, it will pop up a menu. Follows are the descriptions of
the functions in the menu:
System Setup:Press this button to enter system setup window. This window is used to set initial
window, screen saver time, buzzer and brightness adjustment. After setting, press Restart button to
restart HMI.
Firmware Update:Press this button to enter firmware update mode. This window is used to update
firmware. Normally this mode is not advised to use without guiding by manufacturer.
Touch Calibration :Press this button to enter touch calibration window. It will restart HMI
automatically after calibration successful. There is a timer in this button, it will enter application window if
there is no operation within 20s.
Stop timer: Press this button to stop the 20s timer.
Note: There is a multi-languages button; it is used to switch English and Chinese.
5.1 Detailed description of the14-core shielded cable
SZ7 series HMI adopt 14-core shielded twisted cable to improve product stability.
The standard length of cable is 5 meters.
Note
:
1.Handhold signal
(
NO
)、
AUTO-Signal
、
Remote-Signal are connected with common ground
when they are selected.
2.When emergency switch
(
NC
)
is pressed down
,
it is disconnect with Common Ground.
3.
Rated voltage is DC24V,rated current is 0.35A,included emergency switch
、
handhold switch and
3-position selection switch
.
5.2 UTP Cable Socket Module Instruction
SZ7E and SZ7ES have Ethernet interface,the wire connection is in accordance with the T568B
standard,as follows:
1--yellow
2--black
3--red
6--grey
Pin 1, 2, 3, 6 are the pin number on the UTP Cable Socket Module, the color above is the wire
color in 14-core shielded cable.
For < Service Terms and Conditions for HMI >, please check :http://www.kinco.cn
Green/brown/pink in the 14-core shielded cable(see below)
The port is used to upload/ download user configuration program to the
HMI to set HMI system parameters and to communication.
Grey/red in the 14-core shielded cable(see below)
This port is used to connect the controller with RS-485port.
SZ7 series Teach Panel
Installation Instruction
Kinco Electric (Shenzhen) Ltd.
Tel:0755-26585555
Web: www.kinco.cn Email:sales@kinco.cn
Add: Building 1, No. 6 Langshan 1st Rd, Hi-tech Park
KincoWeChat North, Nanshan, Shenzhen, China.
2. Installation Description
Please take shielding measures
in the following places:
Places that exist electrostatic
Places that may be exposed
Please do not use in the following places:
Places direct in sunlight
Surrounding temperature and humidity beyond the
Places of temperature changes sharply and easily
Places that exist corrosive gas and combustible gas
Places of much dust, dirt, salt and iron powder
Places that will be splashed water, oil and drugs
Places that bring direct vibration and shock to host
3. Communication connections
On the back of the product, 4 M4 75*75mm thread holes are
reserved, and the hole position of the bracket (refer to the left)
is aligned with the thread hole, and the screw is screwed into
the M4 specification.
5. Detailed description of the14-core shielded cable
Through sketch left hanging structure, specifications of the M4
screws fixed in the shell reserved above two holes, can be
suspended in a desired position control.