Warning
This instruction sheet only provides introductory information on electrical specification, installation and wiring.
Switch off the power before wiring. DO NOT touch any terminal when the power is switched on.
ENA01- MOD is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may
occur.
Introduction
Features
1. Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detection.
2. The monitor table temporarily stores the monitored data for the user to fast save or acquire the data.
3. Supports MODBUS TCP protocol (supports Master and Slave mode)
4. Able to send out emails after being triggered.
5. The station address, RS-485 communication format and baud rate can be set up externally.
6. The communication parameters can be set up through Web.
Product Profile & Outline
Unit: mm
1
Communication ports: RS-485,
Ethernet, RS-232
2
Power indicator
3
Address setup switch
4
Data format/baud rate setup switch
5
Digit display
6
RS-485 indicator, Reset button,
Ethernet indicator
7
Module name
8
RS-485 connector, digital input points,
power input point, earth point
9
DIN rail connector
Specifications
Ethernet Interface
Interface RJ-45 with Auto MDI/MDIX
Transmission method Ethernet Type II
Transmission cable Category 5e, 100m (Max)
Transmission speed 10/100 Mbps Auto-Detection
Network protocol ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration
ENGLISH
RS-485 Connector
Interface RJ-11
Transm ission method RS-485
Transm ission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol
MODBUS
RS-232 Connector
Interface Mini Dim
Transm ission method RS-232
Transm ission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol
MODBUS, Delta Configuration
Transm ission cable DVPACAB215 / DVPACAB230 / DVPACAB2A30
Terminal Block
Interface Feed-through terminal 10PIN
Transm ission method RS-485
Transm ission distance 1,200m
Transm ission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol
MODBUS
Electrical Specifications
Power voltage 24V DC (-15% ~ 20%) supplied by feed-through terminal
Power consumption 3W
Insulation voltage 500V
Weight 140g
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~
80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 1KV CM, RS-485 0.5KV CM
Operation/storage
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -40ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27(TEST Ea)
Certificates
Installation
Dimension
Unit: mm [inches]
Address Setup Switch
Switch setting Content
00 … FF Valid MODBUS communication address
Data Format Setup Switch
Switch setting Format Switch setting Format
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1 A 7-O-2
3 8-O-1 B 8-O-2
6 7-E-1 E 7-E-2
7 8-E-1 F 8-E-2
Baud Rate Setup Switch
Switch setting Baud rate (bps)
Switch setting Baud rate (bps)
1 110 7 4,800
2 150 8 9,600
3 300 9 19,200
4 600 A 38,400
5 1,200 B 57,600
6 2,400 C 115,200
RJ-11 PIN Definition
PIN Signal Definition
1 -- N/C
2 -- N/C
3 D+ Positive pole for data
4 D- Negative pole for data
5 GND Ground
6 -- N/C
RJ-45 PIN Definition
PIN Signal Definition
1 Tx+ Positive pole for data transmission
2 Tx- Negative pole for data transmission
3 Rx+ Positive pole for data receiving
4 -- N/C
5 -- N/C
6 Rx- Negative pole for data receiving
7 -- N/C
8 -- N/C
RS-232 PIN Definition
PIN Signal Definition
1 -- N/C
2 -- N/C
3 -- N/C
4 Rx Reception data
5 Tx Transm ission data
6 -- N/C
7 -- N/C
8 GND Ground
Feed-through Terminal PIN Definition
PIN Signal Definition
1 SG Ground of signal
2 D- Data-
3 D+ Data+
4 X2 Digital input 2
5 X1 Digital input 1
6 X0 Digital input 0
7 S/S Ground of digital input
8 24V +24V
9 0V 0V
10 Earth ground
LED Indicators & Trouble-Shooting
There are 3 LED indicators and a digital display on ENA01-MOD. POWER indicator displays the status of the
working power. RS-485 and LINK/ACT indicators display the connection status of the communication. The
digital display shows the address of and errors in ENA01-MOD and the error messages from the slave.
POWER LED
LED status Indication How to deal with it?
Off Working power is abnormal Check if the working power of ENA01-MOD is normal.
Green light on Working power is normal --
RS-485 LED
LED status Indication How to deal with it?
Off
No communication or RS-485
connection is abnormal.
1. If the LED is off during the communication, check if the RS-
485 in
ENA01-MOD is normally connected.
2. Check at least 1 node on the network is communicating normally.
Constantly on Abnormal RS-485 connection Switch D+ and D-
Green light
flashes
RS-485 connection is normal. --
LINK/ACT LED
LED status Indication How to deal with it?
Off
No power, or no network
connection
1. Check the power of ENA01-MOD and make sure the network
connection is normal.
2. Re-power ENA01-MOD. If the error still exists, send your
ENA01-MOD back to the factory for repair.
Green light on
The connection is normal, but no
data transmission.
--
Green light
flashes
The data transmission is normal.
--
Codes in Digital Display
Code Indication How to deal with it?
0 ~ FF
The node address of ENA01-MOD
when in normal operation
--
F0 Returning to default setting --
F1 ENA01-MOD is booting. --
F2 Working power in low voltage Check if the working power is normal.
F3 Internal memory error
1. Re-power ENA01-MOD. If the error still exists, try step 2.
2. Reset ENA01-MOD. If the error still exists, send it back to the
factory for repair.
F4
Internal error caused by
manufacturing in the factory
1. Re-power ENA01-MOD. If the error still exists, try step 2.
2. Reset ENA01-MOD. If the error still exists, send it back to the
factory for repair.
F5 Network connection error Check if ENA01-MOD is normally connected to the network.
E1 Alarm 1 triggered Check Alarm Input Point 1
E2 Alarm 2 triggered Check Alarm Input Point 2
E3 Alarm 3 triggered Check Alarm Input Point 3
01
Incorrect
MODBUS
function Check if the
MODBUS
instruction is correct.
02 Incorrect address
Check if the
MODBUS
instruction is correct.
03 Incorrect data
Check if the
MODBUS
instruction is correct.
04 Slave error
1. Check if ENA01-MOD and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of
other nodes on the network.
0B No response from the station
1. Check if ENA01-MOD and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of
other nodes on the network.
(OPEN TYPE)
1. 10/100 Mbps MDI/MDI-X
2.
Monitor table
3. MODBUS TCP ( Master Slave )
4.
5. RS-485
6. Web
1
RS-485, Ethernet, RS-232
2
3
4
5
6
RS-485 Reset Ethernet
7
8
RS-485
mm
9
DIN
Ethernet
RJ-45 with Auto MDI/MDIX
Ethernet Type II
Category 5e, 100 (Max)
10/100 Mbps Auto-Detection
ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration
RS-485
RJ-11
RS-485
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS
RS-232
Mini Dim
RS-232
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS, Delta Configuration
DVPACAB215 / DVPACAB230 / DVPACAB2A30
10PIN
RS-485
1,200m
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS
24VDC (-15% ~ 20%)
3W
500V
140g
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital Input: 2KV,
Communication I/O: 2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~ 80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 1KV CM, RS-485 0.5KV CM
0ºC ~ 55ºC 50 ~ 95% 2
-40ºC ~ 70ºC 5 ~ 95%
/ IEC61131-2, IEC68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27(TEST Ea)
mm [inches]
00 … FF
MODBUS
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1 A 7-O-2
3 8-O-1 B 8-O-2
6 7-E-1 E 7-E-2
7 8-E-1 F 8-E-2
(bps) (bps)
1 110 7 4,800
2 150 8 9,600
3 300 9 19,200
4 600 A 38,400
5 1,200 B 57,600
6 2,400 C 115,200
RJ-11
1 -- N/C
2 -- N/C
3 D+
4 D-
5 GND
6 -- N/C
RJ-45
1 Tx+
2 Tx-
3 Rx+
4 -- N/C
5 -- N/C
6 Rx-
7 -- N/C
8 -- N/C
RS-232
1 -- N/C
2 -- N/C
3 -- N/C
4 Rx
5 Tx
6 -- N/C
7 -- N/C
8 GND
1 SG
2 D-
3 D+
4 X2
2
5 X1
1
6 X0
0
7 S/S
8 24V +24V
9 0V 0V
10
LED
ENA01-MOD LED POWER LED ENA01-MOD
RS485 LED LINK/ACT LED ENA01-MOD
ENA01-MOD
POWER
LED
ENA01-MOD
RS-485
LED
RS-485
1. ENA01-MOD RS-485
2.
RS-485
D+ D-
RS-485
LINK/ACT
LED
1. ENA01-MOD
2.
0 ~ FF
F0
F1
F2
F3
1. 2
2.
F4
1. 2
2.
F5
E1 1
1
E2 2
2
E3 3
3
01
MODBUS
02
MODBUS
03
MODBUS
04
1. RS-485
2.
0B
1. RS-485
2.
(OPEN TYPE)
1. 10/100 Mbps MDI/MDI-X
2. Monitor table
3. MODBUS TCP ( Master Slave )
4.
5. RS-485
6. Web
1
RS-485, Ethernet, RS-232
2
3
4
5
6
RS-485 Reset Ethernet
7
8
RS-485
mm
9
DIN
Ethernet
RJ-45 with Auto MDI/MDIX
Ethernet Type II
Category 5e, 100 (Max)
10/100 Mbps Auto-Detection
ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration
RS-485
RJ-11
RS-485
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS
RS-232
Mini Dim
RS-232
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS, Delta Configuration
DVPACAB215 / DVPACAB230 / DVPACAB2A30
10PIN
RS-485
1,200m
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
MODBUS
24VDC (-15% ~ 20%)
3W
500V
140g
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~ 80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 1KV CM, RS-485 0.5KV CM
0ºC ~ 55ºC 50 ~ 95% 2
-40ºC ~ 70ºC 5 ~ 95%
/ IEC61131-2, IEC68 -2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27(TEST Ea)
mm [inches]
00 … FF MODBUS
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1 A 7-O-2
3 8-O-1 B 8-O-2
6 7-E-1 E 7-E-2
7 8-E-1 F 8-E-2
(bps) (bps)
1 110 7 4,800
2 150 8 9,600
3 300 9 19,200
4 600 A 38,400
5 1,200 B 57,600
6 2,400 C 115,200
RJ-11
1 -- N/C
2 -- N/C
3 D+
4 D-
5 GND
6 -- N/C
RJ-45
1 Tx+
2 Tx-
3 Rx+
4 -- N/C
5 -- N/C
6 Rx-
7 -- N/C
8 -- N/C
RS-232
1 -- N/C
2 -- N/C
3 -- N/C
4 Rx
5 Tx
6 -- N/C
7 -- N/C
8 GND
1 SG
2 D-
3 D+
4 X2 2
5 X1 1
6 X0 0
7 S/S
8 24V +24V
9 0V 0V
10
LED
ENA01-MOD LED POWER LED ENA01-MOD
RS485 LED LINK/ACT LED ENA01-MOD
ENA01-MOD
POWER
LED
ENA01-MOD
RS-485
LED
RS-485
1. ENA01-MOD RS-485
2.
RS-485
D+ D-
RS-485
LINK/ACT
LED
1. ENA01-MOD
2.
0 ~ FF
F0
F1
F2
F3
1. 2
2.
F4
1. 2
2.
F5
E1 1 1
E2 2 2
E3 3 3
01 MODBUS
02 MODBUS
03 MODBUS
04
1. RS-485
2.
0B
1. RS-485
2.
  • Page 1 1
  • Page 2 2

Delta Electronics ENA01-MOD ユーザーマニュアル

タイプ
ユーザーマニュアル

他の言語で