www.dell.com | support.dell.com
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
O
UTLETS—The Rack PDU has (6) IEC 320-C13 and (12) IEC 320-C19 outlets.
P
OWER CORD—The Rack PDU attached power cord terminates with a 4-pin, 3f, IEC60309-60 A plug, 460P9W.
DELLB001A
Electrical
Input connection
IEC60309-60 A plug
Acceptable input voltage 200–240 VAC ± 10%
Maximum input current (phase) 60 A (48 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC ± 10%
Output connections (6) IEC 320-C13
(12) IEC 320-C19
Maximum output current (outlet) C13; 15 A maximum
C19; 20 A maximum
Maximum output current (total all output) 83.1 A maximum
Physical
Dimensions
(H
W D)
178.0 5.5 9.3cm
(70.1
2.2 3.7 in)
Shipping dimensions
(H
W D)
200.0 17.0 17.0 cm
(78.7
6.7 6.7 in)
Weight 8.4 kg (18.5 lb)
Shipping weight 10.8 kg (23.8 lb)
Environmental
Maximum elevation (above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
-15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95% non-condensing
5 to 95% non-condensing
Compliance
Safety approvals
PSE
ROHS Dell 6T198
EU DIRECTIVE 2002/95/EC-latest revision
Information in this document is subject to change without notice.
© 2010 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in
trademarks and trade names other than its own.
Model DELLB001A
04/2010 • 164201961 Rev 1