SM7001B Us e r Manual http://www.sonbus.com/
Sha nghai Sonbest Industrial Co., Ltd Page8
Response should be in the data, after the modification is successful, the first byte is the new device
address. After the general device address is changed, it will take effect immediately. At this time, the user
needs to change the query command of the software at the same time.
4 Read and Modify Baud Rate
(1) Read baud rate
The device default factory baud rate is 9600. If you need to change it, you can change it according to
the following table and the corresponding communication protocol. For example, read the current device's
baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.
Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600;
4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example the response data is: 01 03 02
00 03 F8 45, the format of which is as shown in the following table:
coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
(2)Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the
command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .
Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take
effect immediately, at which point the device will lose its response and the baud rate of the device should
be queried accordingly. Modified.
5 Read Correction Value
(1) Read Correction Value
When there is an error between the data and the reference standard, we can reduce the display error
by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that
is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can
correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If
you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of
FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The
correction value starts from 00 6B. We take the first parameter as an example. The correction value is read
and modified in the same way for multiple parameters.
For the correct query command, the device will respond, for example the response data is: 01 03 02
00 64 B9 AF, the format of which is as shown in the following table:
In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the